ENS 44748
ENS Event | |
|---|---|
19:30 Jan 1, 2009 | |
| Title | Two Emergency Diesel Generators Declared Inoperable Due to Component Failure |
| Event Description | EVENT DESCRIPTION: During return to service testing for Emergency Diesel Generator (EDG) #3, it was noted that the fuel rack limiting cylinder was not returning to its non-limiting position. The fuel rack limiting cylinder is designed to limit the stroke distance of the fuel rack assembly during the initial EDG start sequence. Once the EDG is at rated speed, ~10 seconds, the fuel rack limiting cylinder should return to its non-limiting position. Failure of this component to operate as expected may have prevented EDG #3 from fulfilling its safety function during the postulated Loss of Off Site Power and/or Loss of Coolant Accident conditions. As a result, EDG #3 remains inoperable.
During performance of subsequent surveillance testing on the remaining EDG's (#1, #2, and #4), in accordance with Technical Specifications, a similar condition as described above existed on EDG #4. EDG's #1 and #2 did not exhibit the same behavior and therefore, these EDG's remained operable during this sequence of events. Consequently, EDG #4 was declared inoperable at 1430 on 1/01/09. Failure of this component to operate as expected may have prevented EDG #4 from fulfilling its safety function during the postulated Loss of Off Site Power and/or Loss of Coolant Accident conditions. The concurrent failure of this component on EDG #3 and EDG #4 may have prevented on-site emergency power to Emergency busses 3 & 4 and thus the fulfillment of a safety function needed to mitigate the consequences of an accident. INITIAL SAFETY SIGNIFICANCE EVALUATION: Plant operation is being maintained within the limiting conditions of the license expected. However, transient analyses relating to accident mitigation could have been impacted due to the inability to ensure emergency on-site power supply to Emergency busses 3 & 4. Off-site power and the grid have been stable during the time period both EDG's were inoperable. CORRECTIVE ACTIONS: The fuel rack limiting cylinder for EDG #4 was repaired and EDG #4 was restored to Operable on January 1, 2009 at 1755 EST. Actions required per technical specifications for 2 EDG's were exited within the required time frame. Repair efforts are in progress for EDG #3. The licensee informed the NRC Resident Inspector.
On January 1, 2009, at 2106 hours0.0244 days <br />0.585 hours <br />0.00348 weeks <br />8.01333e-4 months <br />, the Control Room Shift Manager made a notification (i .e. Event Number 44748) to the NRC Operations Center in accordance with 10 CFR 50.72 (b) (3) (v) (D) (i.e., any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident). The notification was made due to two Emergency Diesel Generators (EDGs) being declared inoperable. During return to service testing for BSEP's EDG 3, it was noted that the fuel rack limit cylinder was not returning to its non-limiting position in a timeframe consistent with prior observations. The fuel rack limit cylinder is designed to limit the stroke of the fuel rack during the initial EDG start sequence, preventing too much fuel from being provided to the engine cylinders on initial start. Once the EDG is at half-rated speed (i.e., in approximately 5 to 8 seconds), the fuel rack limit cylinder should be released to return to its non-limiting position. Failure of this component to operate as expected may have prevented the EDG from fulfilling its safety function during the postulated Loss of Off-site Power (LOOP) and/or Loss of Coolant Accident (LOCA) conditions. As a result, EDG 3 was conservatively declared inoperable due to the potential for the unexpected response of the fuel rack limit cylinder to impact Design Basis Accident (DBA) transient loading criteria. During performance of subsequent surveillance testing on the remaining EDG's, (i.e.,1,2, and 4), in accordance with Technical Specifications, a similar condition was identified on EDG 4. EDGs 1 and 2 did not exhibit the same behavior and therefore, these EDGs remained operable during this sequence of events. Consequently, EDG 4 was also conservatively declared inoperable at 1430 on January 1, 2009. The concurrent failure of this component on EDG 3 and EDG 4 may have prevented the onsite emergency power from fulfilling its intended safety function needed to mitigate the consequences of an accident. Basis for Retraction Further investigation has demonstrated that both EDG 3 and EDG 4 were fully operable. The EDG 3 evaluation concluded that the fuel rack limit would remain in effect for approximately seven (7) seconds after the diesel output breaker closed during a LOOP loading event or a design basis LOOP/LOCA loading event. After that, the fuel limit cylinder would not have limited the governor response in any way. The generator capacity during the first seven seconds of load acceptance at the fuel rack limited position would be sufficient to ensure proper acceleration of the 480-volt design basis loads and the Nuclear Service Water pump. These are the only loads expected to start during the first seven seconds of the EDG loading. The generator frequency response during the acceleration of these loads would be well within the EDG design limits. The Residual Heat Removal and Core Spray pumps are sequenced onto the EDG at 10 seconds and 15 seconds, respectively, following the closure of its output breaker and are not affected by the fuel limiter impairment. The EDG 4 evaluation is bounded by the above analysis. Therefore, the fuel rack limiter impairment would not have prevented either EDG 3 or EDG 4 from fulfilling their intended safety function. On this basis, this event is not reportable under 10 CFR 50.72(b) (3) (v) (D). Investigation of this condition is documented in the corrective action program in Nuclear Condition Report (NCR) 312876. The NRC resident was notified of this retraction. R2DO (Musser) has been notified. |
| Where | |
|---|---|
| Brunswick North Carolina (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+1.6 h0.0667 days <br />0.00952 weeks <br />0.00219 months <br />) | |
| Opened: | C. Dunsmore 21:06 Jan 1, 2009 |
| NRC Officer: | Steve Sandin |
| Last Updated: | Mar 2, 2009 |
| 44748 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Brunswick | |
WEEKMONTHYEARENS 559972022-07-16T00:20:00016 July 2022 00:20:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (HPCI) Inoperable ENS 557802022-03-10T01:13:00010 March 2022 01:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (HPCI) Inoperable ENS 541162019-06-13T01:27:00013 June 2019 01:27:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Inoperable ENS 531232017-12-17T08:16:00017 December 2017 08:16:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable ENS 527882017-06-05T17:52:0005 June 2017 17:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Emergency Ventilation Systems Inoperable ENS 526792017-04-14T04:15:00014 April 2017 04:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Drywell and Suppression Chamber Simultaneously Aligned for Venting ENS 520642016-07-05T20:40:0005 July 2016 20:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable ENS 517692016-03-04T17:35:0004 March 2016 17:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Emergency Diesel Generator Declared Inoperable ENS 508162015-02-12T18:36:00012 February 2015 18:36:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable During Weekly Inspection ENS 485962012-12-14T18:06:00014 December 2012 18:06:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Building Emergency Ventilation System Inoperable for Two Minutes ENS 478932012-05-02T21:58:0002 May 2012 21:58:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inoperable Due to Erratic Governor Operation ENS 474932011-12-01T18:44:0001 December 2011 18:44:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Control Room Emergency Ventilation Systems Inoperable ENS 467632011-04-17T02:52:00017 April 2011 02:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Lube Oil Pressure Low Out of Band ENS 467402011-04-07T21:40:0007 April 2011 21:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of the Control Room Emergency Ventilation System ENS 452642009-08-14T23:58:00014 August 2009 23:58:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Automatic Closure of Inboard Isolation Valve ENS 448102009-01-28T01:07:00028 January 2009 01:07:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unit 2 Hpci System Inoperable for Two Hours Due to Condensate in Exhaust Line ENS 447932009-01-21T18:00:00021 January 2009 18:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Control Room Air Conditioning and Emergency Ventilation System ENS 447482009-01-01T19:30:0001 January 2009 19:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Two Emergency Diesel Generators Declared Inoperable Due to Component Failure ENS 443092008-06-19T21:35:00019 June 2008 21:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Ventilation Inoperable ENS 442622008-06-03T17:13:0003 June 2008 17:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Control Room Emergency Ventillation System for 12 Minutes ENS 441792008-04-30T03:13:00030 April 2008 03:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable Due to Seal Leak ENS 437112007-10-11T02:45:00011 October 2007 02:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unit 2 Hpci Pump Seal Failure ENS 431972007-02-28T03:26:00028 February 2007 03:26:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Inoperability ENS 429062006-10-13T17:57:00013 October 2006 17:57:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable Due to Potential Turbine Exhaust Diaphragm Failure ENS 424882006-04-10T20:30:00010 April 2006 20:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Emergency Ventilation System Declared Inoperable Due to Design Deficiency ENS 423052006-02-03T04:36:0003 February 2006 04:36:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable Due to One Hpci Turbine Exhaust Vacuum Breaker Isolation Valve Failure ENS 422542006-01-12T14:20:00012 January 2006 14:20:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Control Room Emergency Ventilation Systems Inoperable ENS 418952005-08-05T22:40:0005 August 2005 22:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperability of All Emergency Diesel Generators ENS 416922005-05-12T08:11:00012 May 2005 08:11:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.73(a)(1), Submit an LER Technical Specification Required Shutdown Due to Loss of Emergency Bus E1 ENS 408332004-06-22T13:00:00022 June 2004 13:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Presure Coolant Injection System Inoperable Due to Maintenance ENS 407142004-04-29T02:30:00029 April 2004 02:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci System Inoperable Following Planned Maintenance ENS 406362004-04-03T08:00:0003 April 2004 08:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 403182003-11-13T03:22:00013 November 2003 03:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Isolation During Testing 2022-07-16T00:20:00 | |