ENS 43602
ENS Event | |
|---|---|
05:00 Aug 27, 2007 | |
| Title | One Channel of Low Main Steam Line Pressure Signal Mistakenly Removed from Service for 33 Minutes |
| Event Description | On 8/27/07 at approximately 12:05, during performance of STP 3.3.6.1-02 step 7.7.2 the jumper was installed on contacts 1 and 2 of relay A71B-K4A PCIS TRIP CHANNEL A1 A MAIN STEAM LINE LO PRESSURE. The jumper should have been installed on contacts 1 and 2 of relay A71B-K4C PCIS TRIP CHANNEL A2 C MAIN STEAM LINE LO PRESSURE.
The incorrectly installed jumper on contacts 1-2 of relay A71B-K4A resulted in the channel A1 not being able to trip on a low main steam line pressure signal of 850 psig (PS1014) thus making the function of PS1014 inoperable. At the same time PS1016 was being tested for channel A2 thus making the function for pressure switch PS1016 inoperable. Per Technical specification 3.3.6.1 'Primary Containment Isolation Instrumentation' function 1b 'Main Steam Line pressure - Low' with both PS1014 and PS1016 inoperable, the tripping capability for channel A for Main steam Line Pressure - Low would be lost. This would be a automatic function with isolation capability not maintained per TS 3.3.6.1 condition B. Required action B.1 requires isolation capability to be restored in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. The I&C techs entered the AOT time for PS1016 at 11:32 AM and exited the AOT at 12:05 PM. Therefore, the isolation capability was lost for 33 minutes of the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. There was no violation of Technical Specification 3.3.6.1 function 1b. This event is reportable under 10 CFR 50.72(b)(3)(v), 'Any event or condition that alone at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to (D) Mitigate the consequences of an accident. The licensee notified the NRC Resident Inspector.
An UFSAR review has determined that the Main Steam Line Low Pressure isolation is intended to mitigate a transient event. Specifically, the isolation is a safety feature intended to mitigate the consequences of an EHC Pressure Regulator Failure - Open. This transient is not a Design Basis Accident (DBA). Therefore this event resulted in a loss of a Safety Feature, not a loss of a Safety Function. This event is not reportable under 10CFR50.72(b)(3)(v)(D) because the event did not result in a condition that would have prevented the fulfillment of a safety function needed to mitigate the consequences of an accident. Notified the R3DO (Hills). The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Duane Arnold Iowa (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+15.43 h0.643 days <br />0.0918 weeks <br />0.0211 months <br />) | |
| Opened: | Ellis Vann 20:26 Aug 27, 2007 |
| NRC Officer: | Pete Snyder |
| Last Updated: | Oct 26, 2007 |
| 43602 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Duane Arnold | |
WEEKMONTHYEARENS 528812017-08-01T14:34:0001 August 2017 14:34:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Steam Supply Valve Failed to Reposition ENS 516972016-01-29T15:20:00029 January 2016 15:20:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Offsite Power Declared Inoperable Due to Lowering Generator Voltage ENS 510062015-04-23T15:50:00023 April 2015 15:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Safety Systems Declared Inoperable Due to Equipment Malfunction ENS 508912015-03-13T17:30:00013 March 2015 17:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Low Pressure Coolant Injection Declared Inoperable ENS 501542014-05-30T15:43:00030 May 2014 15:43:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Pump Received an Invalid Isolation Signal ENS 495662013-11-21T08:29:00021 November 2013 08:29:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Diesel Generator Inoperability ENS 480642012-07-02T20:05:0002 July 2012 20:05:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable ENS 475612011-12-30T02:09:00030 December 2011 02:09:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Lpci Instrumentation Required Repair and Recalibration ENS 466452011-02-26T15:48:00026 February 2011 15:48:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 450102009-04-23T00:45:00023 April 2009 00:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable ENS 436922007-10-05T09:08:0005 October 2007 09:08:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Both Emergency Service Water Pumps ENS 436022007-08-27T05:00:00027 August 2007 05:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident One Channel of Low Main Steam Line Pressure Signal Mistakenly Removed from Service for 33 Minutes ENS 433312007-05-01T01:17:0001 May 2007 01:17:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable Due to Primary Containment Nitrogen Leak ENS 432622007-03-28T18:41:00028 March 2007 18:41:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Surveillance Test Failure ENS 431612007-02-12T16:52:00012 February 2007 16:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Standby Filter Units Inoperable ENS 431182007-01-24T15:55:00024 January 2007 15:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Missing Pipe Clamp Bolt Found on High Pressure Coolant Injection (Hpci) System ENS 428352006-09-08T09:01:0008 September 2006 09:01:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Containment Atmospheric Dilution (Cad) System Inoperable ENS 420252005-09-29T20:34:00029 September 2005 20:34:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Declared Inoperable 2017-08-01T14:34:00 | |