ENS 40816
ENS Event | |
|---|---|
14:44 Jun 14, 2004 | |
| Title | Unusual Event Due to Reactor Trip Due to Loss of Off Site Power |
| Event Description | On June 14, 2004, at approximately 07:44 Mountain Standard Time (MST) all three units at the Palo Verde Nuclear Generating Station experienced automatic reactor trips coincident with a grid disturbance and loss of offsite power in the Palo Verde Switchyard. Unit 3 declared a NOTIFICATION OF UNUSUAL EVENT at 07:53 MST due to a loss of offsite power to essential buses for greater than 15 minutes. The NOTIFICATION OF UNUSUAL EVENT was terminated at 12:07 MST.
Unit 3 received an automatic Main Steam Isolation System ESF actuation. Due to the loss of offsite power, the Emergency Plan Technical Support Center (TSC) was unavailable. The Unit 2 Satellite TSC was to be staffed by the Emergency Response Organization in response to the loss of assessment capability. Power to the TSC has since been restored. The unit was at normal operating temperature and pressure prior to the trip. All CEAs inserted fully into the reactor cores. All Emergency Diesel Generators (EDGs) (2 per unit) associated with the unit started as expected in response to the loss of offsite power to their safety buses. The offsite power grid had several perturbations for approximately one hour following the event but has been stable since. LCO 3.8.1, AC Sources - Operating, was entered as a result of this event. Heat removal is to atmosphere via atmospheric dump valves in natural circulation. Main steam safety valves may have lifted for a brief time. Restoration of forced reactor coolant circulation is pending assurance that the offsite power grid can reliably support the load. No major equipment was inoperable prior to the event that contributed to the event. The Unit is stable at normal operating temperature and pressure in Mode 3. The event did not result in any challenges to fission product barriers and there were no adverse safety consequences as a result of this event. The event did not adversely affect the safe operation of the plant NRC Resident Inspector was notified. FBI Jeff Muller and Mr. Rosales (Mexican National Commission of Nuclear Safety and Safeguards {CNSNS}) were notified.
Notified Reg 4 RDO (Graves), NRR (Bateman), DHS (Lee), FEMA (Canupp), DOE (Sal Moroni), EPA (Stalcup), EPA (Crews), HSS (Davidson), and Mexico (Rosales) Note: see related events 40815 , 40814 and 40818 |
| Where | |
|---|---|
| Palo Verde Arizona (NRC Region 4) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-3.08 h-0.128 days <br />-0.0183 weeks <br />-0.00422 months <br />) | |
| Opened: | Jim Moreland 11:39 Jun 14, 2004 |
| NRC Officer: | Bill Gott |
| Last Updated: | Jun 14, 2004 |
| 40816 - NRC Website
Loading map... | |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | A/R |
| Before | Power Operation (100 %) |
| After | Hot Standby (0 %) |
Palo Verde | |
WEEKMONTHYEARENS 582112026-03-19T15:19:00019 March 2026 15:19:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared for RCS Leakage for Greater than 15 Minutes ENS 576592025-04-10T14:11:00010 April 2025 14:11:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event - Loss of All But One AC Power Source to Emergency Buses ENS 576562025-04-09T02:24:0009 April 2025 02:24:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Emergency AC Electrical Power Systems ENS 570662024-04-04T23:18:0004 April 2024 23:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Fire Alarm in the Vital Area ENS 570472024-03-24T23:34:00024 March 2024 23:34:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Specified System Actuations of Unit 2 Train B Emergency Diesel Generator and Train B Auxiliary Feedwater ENS 565512023-06-02T11:05:0002 June 2023 11:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 564872023-04-26T06:15:00026 April 2023 06:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Spilled Sodium Hypochlorite ENS 564592023-04-09T04:44:0009 April 2023 04:44:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Loss of Reactor Coolant Pumps ENS 560442022-08-15T00:02:00015 August 2022 00:02:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuations of Unit 1 and Unit 3 Emergency Diesel Generators and Unit 1 Auxiliary Feedwater Pump ENS 558782022-05-05T02:55:0005 May 2022 02:55:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Unit 2 and Unit 3 Emergency Diesel Generators and Unit 3 Auxiliary Feedwater Pump ENS 556262021-12-06T19:03:0006 December 2021 19:03:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Unit 3 Automatic Trip ENS 555342021-10-20T21:46:00020 October 2021 21:46:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Specified System Actuations of Unit 1 and Unit 3 Emergency Diesel Generators ENS 552652021-05-19T10:15:00019 May 2021 10:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to High Pressurizer Pressure ENS 552052021-04-22T16:25:00022 April 2021 16:25:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Inadvertant Activation of Emergency Sirens ENS 551142021-02-26T17:33:00026 February 2021 17:33:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Loss of Two Reactor Coolant Pumps ENS 545602020-03-04T03:50:0004 March 2020 03:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Low Steam Generator Level ENS 542242019-08-16T15:21:00016 August 2019 15:21:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip ENS 537022018-10-29T07:00:00029 October 2018 07:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of Non- Work Related Fatality ENS 534772018-06-27T07:00:00027 June 2018 07:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Low Steam Generator Water Level ENS 534242018-05-23T18:28:00023 May 2018 18:28:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip on Low Departure from Nucleate Boiling Ratio ENS 532152018-02-16T04:53:00016 February 2018 04:53:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Automatic Reactor Trip Due to Low Departure from Nucleate Boiling Signal ENS 524352016-12-15T11:10:00015 December 2016 11:10:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared - Catastrophic Failure of an Emergency Diesel Generator ENS 522262016-09-08T04:31:0008 September 2016 04:31:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Stuck Open Pressurizer Main Spray Valve ENS 518442016-04-02T05:29:0002 April 2016 05:29:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Sodium Hypochlorite Spill on Site ENS 515222015-11-09T12:47:0009 November 2015 12:47:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Containment Fire Alarm ENS 514032015-09-17T06:01:00017 September 2015 06:01:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Rapid Combustion of a Load Center Breaker ENS 509842015-04-15T02:20:00015 April 2015 02:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Sodium Hydroxide Spill Onsite Exceeding Reportable Quantity ENS 502372014-06-29T05:06:00029 June 2014 05:06:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Earthquake Felt on Site ENS 496002013-12-03T00:58:0003 December 2013 00:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Following the Loss of the 1A Reactor Coolant Pump ENS 494822013-10-29T13:05:00029 October 2013 13:05:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Employee Fatality ENS 493172013-09-03T02:26:0003 September 2013 02:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Fire in the Turbine Building ENS 491692013-07-03T07:00:0003 July 2013 07:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to Explosion in a Non-Safety Related Load Center ENS 483472012-09-26T20:36:00026 September 2012 20:36:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Attempted Entry Onto the Site by an Illegal Alien with False Identification ENS 478372012-04-15T19:20:00015 April 2012 19:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Control Rod Deviation During Startup ENS 476882012-02-23T01:45:00023 February 2012 01:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Suspicious Package Discovered on Site ENS 474722011-11-23T02:25:00023 November 2011 02:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Control Element Deviation ENS 473332011-10-08T23:19:0008 October 2011 23:19:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Severe Electrical Fault in Rcp Junction Box ENS 471332011-08-06T18:19:0006 August 2011 18:19:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Dropped Control Element Assembly ENS 470502011-07-14T21:11:00014 July 2011 21:11:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release News Release Regarding Arrest of Illegal Immigrant Working at Palo Verde ENS 466342011-02-22T16:09:00022 February 2011 16:09:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Loss of Potable Water Supply ENS 466332011-02-22T03:01:00022 February 2011 03:01:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Auto Start and Load of Edgs on Units 1&3 Following Loss of Start-Up Transformer ENS 465562011-01-20T01:41:00020 January 2011 01:41:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Main Feedwater Pump Trip ENS 460252010-06-18T15:08:00018 June 2010 15:08:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Damaged Energized Equipment ENS 458232010-04-08T17:15:0008 April 2010 17:15:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Earthquake ENS 458112010-04-04T22:42:0004 April 2010 22:42:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to an Earthquake ENS 457842010-03-23T01:11:00023 March 2010 01:11:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Unidentified Leakage Greater than 10 Gpm ENS 457482010-03-07T18:24:0007 March 2010 18:24:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Electrical Fault Causing Damage to Equipment ENS 455372009-12-03T11:30:0003 December 2009 11:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip After Loss of Instrument Air to Containment ENS 449702009-04-04T06:54:0004 April 2009 06:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to High Vibrations in the Turbine ENS 445252008-09-28T04:51:00028 September 2008 04:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Unit 3 Reactor Manually Tripped Following Automatic Turbine Trip on High Vibration ENS 444962008-09-16T21:00:00016 September 2008 21:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip During Troubleshooting of Control Rod Drive Mechanism Motor Generators ENS 444012008-08-08T22:20:0008 August 2008 22:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Maricopa County Environmental Services ENS 442462008-05-29T04:34:00029 May 2008 04:34:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Improper Movement of Cea'S ENS 438762007-12-31T15:40:00031 December 2007 15:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Death of an Employee Outside the Protected Area ENS 437642007-11-02T14:44:0002 November 2007 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Suspicious Explosive Device Discovered in Vehicle at Oca Access Checkpoint ENS 436972007-10-06T17:59:0006 October 2007 17:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Condenser Tube Rupture ENS 429382006-10-27T06:53:00027 October 2006 06:53:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Loss of Power to the Unit 1 and Unit 3 Train B Safety Buses with Emergency Diesel Generator Actuation ENS 429252006-10-21T22:48:00021 October 2006 22:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Control Element Assembly Position Transmitter Output Deviations ENS 429202006-10-19T18:47:00019 October 2006 18:47:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Following the Trip of Secondary Condensate Pumps ENS 427302006-07-26T14:35:00026 July 2006 14:35:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Variable Overpower Reactor Trip Following Turbine Control Valve Maintenance ENS 426812006-07-02T02:28:0002 July 2006 02:28:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Following Large Leak in Condensate System ENS 426092006-05-30T15:13:00030 May 2006 15:13:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Loss of Power to Train "a" 4 Kv Safety Bus ENS 425592006-05-06T23:35:0006 May 2006 23:35:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Emergency Diesel Generator Due to Low Voltage Condition ENS 424682006-04-03T03:54:0003 April 2006 03:54:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Trip During Testing ENS 423872006-03-05T14:10:0005 March 2006 14:10:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Low Departure from Nucleate Boiling Ratio. ENS 423812006-03-02T21:30:0002 March 2006 21:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification ENS 421012005-10-31T19:02:00031 October 2005 19:02:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Media Interest ENS 419602005-08-29T17:30:00029 August 2005 17:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Off Site Notifications Due to Loss of Inoperable Emergency Evacuation Siren ENS 419512005-08-27T01:24:00027 August 2005 01:24:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Rps Actuation - Reactor Scram on High Steam Generator Level ENS 419412005-08-23T20:49:00023 August 2005 20:49:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Two Emergency Sirens Inoperable ENS 419122005-08-11T15:45:00011 August 2005 15:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness One Emergency Preparedness Siren Out of Service ENS 418102005-06-29T11:43:00029 June 2005 11:43:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Evacuation Siren Inoperable ENS 414972005-03-16T01:51:00016 March 2005 01:51:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notifications Due to Caustic Spill ENS 413792005-02-07T05:19:0007 February 2005 05:19:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Start Due to Bus Deenergization ENS 413042004-12-31T17:42:00031 December 2004 17:42:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Plant Had Auto Start and Loading of Two Emergency Diesel Gererators ENS 412682004-12-17T17:53:00017 December 2004 17:53:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notifications Made Due to Spill of Approximately 1400 Pounds of Sulfuric Acid ENS 408702004-07-14T08:35:00014 July 2004 08:35:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Following a Main Generator Trip ENS 408142004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Alert Declared - Reactor Trip Due to Loss of Off Site Power ENS 408152004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Reactor Trip Due to Loss of Off Site Power ENS 408162004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Reactor Trip Due to Loss of Off Site Power ENS 407952004-06-07T21:58:0007 June 2004 21:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Main Turbine Electro-Hydraulic Control System Failure ENS 407372004-05-09T03:39:0009 May 2004 03:39:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip During Physics Testing Due to Control Element Assembly Slipping 6 Inches. ENS 406802004-04-17T14:26:00017 April 2004 14:26:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Small Fire at Palo Verde 1: Two Employees Injured, No Plant Equipment Damage ENS 405612004-03-01T23:49:0001 March 2004 23:49:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Press Release Regarding Boron Residue ENS 405332004-02-20T17:33:00020 February 2004 17:33:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to a Press Release Concerning the Unit 2 Shutdown ENS 403492003-11-22T05:53:00022 November 2003 05:53:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of the "a" Emergency Diesel Generator During Testing 2026-03-19T15:19:00 | |