ENS 57066
ENS Event | |
|---|---|
23:18 Apr 4, 2024 | |
| Title | Notification of Unusual Event Due to Fire Alarm in the Vital Area |
| Event Description | The following information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
On 4/4/2024 at 1618 MST, a Notification of Unusual Event, HU4.2 was declared based on an unverified fire alarm in the containment building greater than 15 minutes. Palo Verde, Unit 3 was operating in Mode 1 at 91 percent power due to end of cycle coast down to a refueling outage. There is no known plant damage at this time. Offsite assistance cannot enter the containment building, therefore, offsite assistance was not requested. The plant is stable in Mode 1. The licensee notified State and local authorities and the NRC Senior Resident Inspector. Notified DHS SWO, FEMA Operations Center, CISA Central, FEMA NWC (email), CWMD Watch Desk (email), DHS NRCC THD Desk (email), and DHS Nuclear SSA (email).
The following information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance: At 2013 MST, Palo Verde Unit 3 terminated the notification of unusual event. The basis for termination was that a containment entry was performed. All levels were inspected, and no fires were found. The NRC Resident Inspector has been notified. Notified R4DO (Deese), IR-MOC (Crouch), NRR-EO (Felts), DHS SWO, FEMA Operations Center, CISA Central, FEMA NWC (email), CWMD Watch Desk (email), DHS NRCC THD Desk (email), and DHS Nuclear SSA (email). |
| Where | |
|---|---|
| Palo Verde Arizona (NRC Region 4) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-3.72 h-0.155 days <br />-0.0221 weeks <br />-0.0051 months <br />) | |
| Opened: | Yolanda Good 19:35 Apr 4, 2024 |
| NRC Officer: | Tenisha Meadows |
| Last Updated: | Apr 5, 2024 |
| 57066 - NRC Website
Loading map... | |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (91 %) |
| After | Power Operation (91 %) |
WEEKMONTHYEARENS 582112026-03-19T15:19:00019 March 2026 15:19:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared for RCS Leakage for Greater than 15 Minutes ENS 576592025-04-10T14:11:00010 April 2025 14:11:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event - Loss of All But One AC Power Source to Emergency Buses ENS 570662024-04-04T23:18:0004 April 2024 23:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Fire Alarm in the Vital Area ENS 524352016-12-15T11:10:00015 December 2016 11:10:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared - Catastrophic Failure of an Emergency Diesel Generator ENS 515222015-11-09T12:47:0009 November 2015 12:47:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Containment Fire Alarm ENS 514032015-09-17T06:01:00017 September 2015 06:01:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Rapid Combustion of a Load Center Breaker ENS 502372014-06-29T05:06:00029 June 2014 05:06:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Earthquake Felt on Site ENS 493172013-09-03T02:26:0003 September 2013 02:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Fire in the Turbine Building ENS 491692013-07-03T07:00:0003 July 2013 07:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to Explosion in a Non-Safety Related Load Center ENS 473332011-10-08T23:19:0008 October 2011 23:19:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Severe Electrical Fault in Rcp Junction Box ENS 460252010-06-18T15:08:00018 June 2010 15:08:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Damaged Energized Equipment ENS 458232010-04-08T17:15:0008 April 2010 17:15:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Earthquake ENS 458112010-04-04T22:42:0004 April 2010 22:42:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to an Earthquake ENS 457842010-03-23T01:11:00023 March 2010 01:11:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Unidentified Leakage Greater than 10 Gpm ENS 457482010-03-07T18:24:0007 March 2010 18:24:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Electrical Fault Causing Damage to Equipment ENS 437642007-11-02T14:44:0002 November 2007 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Suspicious Explosive Device Discovered in Vehicle at Oca Access Checkpoint ENS 408142004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Alert Declared - Reactor Trip Due to Loss of Off Site Power ENS 408162004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Reactor Trip Due to Loss of Off Site Power ENS 408152004-06-14T14:44:00014 June 2004 14:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Reactor Trip Due to Loss of Off Site Power 2026-03-19T15:19:00 | |