- En tergy Entergy Nuclear Vermont Yankee, LLC Entergy Nuclear Operations, Inc.

185 Old Ferry Road Brattleboro, VT 05302-0500 April 30, 2004 BVY 04-039 United States Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

Subject:

Vermont Yankee Nuclear Power Station License No. DPR-28 (Docket No. 50-271)

Emerpencv Resnonse Data Svstem Data Point Library Update Attached are two revised Emergency Response Data System Data Point Library (DPL) sheets. These updated sheets are required to reflect a recent design change (MM 2003-039) to our Feedwater System Instrumentation. The two feedwater flow signals have been re-calibrated with a larger total range. The previous range for both feedwater flow signals had been (0 to 4.0 Mlb/hr). The extended range is now (0 to 5.0 Mlb/hr). In addition, the reference calibration density for these two signals has changed from 372 degF to 391.5 degF.

Should you have any questions on this matter, please contact me at (802) 258-4236.

Sincerely, ames M. DeVincentis Manager, Licensing Attachment cc:

USNRC Region I Administrator USNRC Project Manager - VYNPS USNRC Resident Inspector - VYNPS John R. Jolicoeur - USNRC Vermont Department of Public Service

'A02*

Rev. 3 4/2004 - DATA POINT LIBRARY REFERENCE FILE DATE:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC.:

GENERIC/COND DESC.:

ANALOG/DIGITAL:

ENER UNITS/DIG STATES:

ENGR UNITS CONVERSION:

-MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SET POINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC.:

04/30/04 REACTOR: VY1 DATA FEEDER: ERFIS Main FD Flow B015 Reactor Feedwater Inlet Flow A Feedwater Flow into the Reactor Svstem A

MLB/HR N/A 0

5 N/A N/A S

1 N/A Turbine Building 3.4 Hi Alarm N/A N/A Variable Densitv compensation applied: ref. conditions 391.5 deaF & 1025 Dsia Y

N/A Page 12 of 71

Rev. 3 4/2004 - DATA POINT LIBRARY REFERENCE FILE DATE:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC.:

GENERIC/COND DESC.:

ANALOG/DIGITAL:

ENER UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SET POINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC.:

04/30/04 REACTOR: VY1 DATA FEEDER: ERFIS Main FD Flow B016 Reactor Feedwater Inlet Flow B Feedwater Flow into the Reactor System A

MLB/HR N/A 0

5 N/A N/A S

1 N/A Turbine Building 3.4 Hi Alarm N/A N/A Variable Densitv compensation applied; ref. conditions 391.5 deaF & 1025 psia Y

N/A Page 13 of 71