05000331/FIN-2015004-01
From kanterella
(Redirected from 5000331/FIN-2015004-01)
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Scope Safety Related and Nonsafety Related Breaker Into the Maintenance Rule |
Description | The inspectors identified a finding of very low safety significance and an associated NCV of 10 CFR 50.65(a)(1), 10 CFR 50.65(a)(2), and 10 CFR 50.65(b), due to the licensees failure to scope the load-shed function of safety related and nonsafety related 4160 volt (V) and 480V breakers into the Maintenance Rule. The load-shed function of the breakers was to ensure upon receipt of load-shed signal that the required breakers would separate from the associated essential buses such that the Standby Diesel Generators (SBDGs) could close into the vital buses. The licensee entered the inspectors concerns into the CAP as CR 2065346. Corrective actions included scoping those breakers of concern into the Maintenance Rule program, establishing breaker performance criteria, and performing a review of past breaker failures against the established criteria. The performance deficiency was determined to be more than minor because it impacted the Mitigating Systems Cornerstone attribute of Equipment Performance, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage) with respect to the SBDGs. Because the finding did not affect the design or qualification of the SBDGs, nor did it represent a loss of a system or function, the finding screened as very low safety significance. This finding was not indicative of licensee performance since the scoping aspects were determined in 1994, which was prior to the rules effective date of July 10, 1996. Therefore, no cross-cutting aspect was assigned to this finding. |
Site: | Duane Arnold |
---|---|
Report | IR 05000331/2015004 Section 1R12 |
Date counted | Dec 31, 2015 (2015Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | C Norton C Phillips G Hansen J Steffes K Stoedter R Edwards R Walton V Myers |
Violation of: | 10 CFR 50.65(b) 10 CFR 50.65(a)(1) 10 CFR 50.65(a)(2) 10 CFR 50.65 |
INPO aspect | |
' | |
Finding - Duane Arnold - IR 05000331/2015004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Duane Arnold) @ 2015Q4
Self-Identified List (Duane Arnold)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||