Finding | |
|---|---|
| Title | Failure to Declare High Pressure Coolant Injection and Reactor Core Isolation Cooling Inoperable when the High Pressure Coolant Injection and Reactor Core Isolation Cooling Pump Suction Swap Logic was Inoperable |
| Description | The inspectors identified a finding of very low safety significance, with two examples, and an associated NCV of Technical Specifications (TS) Sections 3.3.5.1, Condition D and 3.3.5.2, Condition D, for failure to initiate required TS action statements 3.3.5.1.D.1 and 3.3.5.2.D.1. Specifically, the licensee failed to declare the high pressure coolant injection (HPCI) and the reactor core isolation cooling (RCIC) systems inoperable when the automatic HPCI/RCIC pump suction swap function on low condensate storage tank (CST) level was revealed to be inoperable during surveillance testing. The licensee entered the inspectors concerns into the CAP as CR 2080489 and replaced the failed time delay relay. The inspectors determined the failure to declare the HPCI/RCIC systems inoperable when the pump suction swap function on low CST level failed during surveillance testing was a performance deficiency because it resulted in the licensees failure to implement TS required actions and the cause was reasonably within the licensees ability to foresee and should have been prevented. The performance deficiency was determined to be more than minor and a finding because if left uncorrected, failing to implement TS required actions reduced the margin of safety and had the potential to lead to significant safety concerns. The finding was determined to be of very low significance because the CST was assumed to contain sufficient inventory for HPCI and RCIC to perform their function for most scenarios. This finding was associated with the cross-cutting aspect of conservative bias in the area of human performance because the licensee failed to use decision-making practices that emphasize prudent choices over those that are simply allowable when the licensee failed to conservatively evaluate unexpected surveillance test results. [H.14] |
| Site: | Duane Arnold |
|---|---|
| Report | IR 05000331/2015004 Section 1R15 |
| Date counted | Dec 31, 2015 (2015Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | C Norton C Phillips G Hansen J Steffes K Stoedter R Edwards R Walton V Myers |
| Violation of: | Technical Specification |
| CCA | H.14, Conservative Bias |
| INPO aspect | DM.2 |
| ' | |