05000440/FIN-2015003-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Inadequate Operating Procedure for Diesel Generator Building Ventilation System |
| Description | The inspectors identified a finding of very low safety significance and associated non-cited violation (NCV) of Title 10 of the Code of Federal Regulations Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the licensees failure as of July 8, 2015, to establish and maintain an adequate procedure for operation of the Diesel Generator Building Ventilation System (DGBVS). Specifically, the DGBVS operating procedure did not ensure that diesel room temperature would remain below limits during testing. The failure to establish and maintain an adequate procedure was a performance deficiency and resulted in the Division 2 Diesel Generator room temperatures exceeding specified limits. The performance deficiency was more than minor, and thus a finding, because it was associated with the equipment performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors determined that the finding was of very low safety significance because the finding is a deficiency affecting the design or qualification of a mitigating structure, system, and component (SSC) that maintained its operability. This finding has a cross-cutting aspect in the area of human performance, design margins, because the licensee did not incorporate the degree of redundancy specified in the Updated Safety Analysis Report for DGBVS into the applicable operating procedures. |
| Site: | Perry |
|---|---|
| Report | IR 05000440/2015003 Section 1R15 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | J Beavers J Nance M Kunowski M Marshfield T Briley T Go J Seymour |
| Violation of: | 10 CFR 50 Appendix B Criterion V |
| CCA | H.6, Design Margins |
| INPO aspect | WP.2 |
| ' | |
Finding - Perry - IR 05000440/2015003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Perry) @ 2015Q3
Self-Identified List (Perry)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||