05000440/FIN-2010005-06
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | On November 16, 2010, the licensee identified a failure to meet the requirements of TS 3.0.2 by failing to enter Condition A of TS 3.8.1, AC Sources - Operating when the system was made inoperable. The licensee identified the missed TS entry after the Completion Time of Required Action A.1 had already expired. The licensee then entered Condition F, which required a plant shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. The cause was a failure to follow written procedures as well as inadequate communications regarding safety-related equipment. Corrective actions included entry into TS 3.8.1 Conditions A and F, completion of the surveillance to satisfy Condition A and subsequent exit from the shutdown requirement of Condition F. The violation was determined to be of very low safety significance. The licensee entered this performance deficiency in the CAP as CR 10-85870. |
Site: | Perry ![]() |
---|---|
Report | IR 05000440/2010005 Section 4OA7 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | M Marshfield D Reeser B Palagi M Phalen J Cameron P Voss C Scott T Hartman P Smagacz |
INPO aspect | |
' | |