Finding | |
|---|---|
| Title | Failure to Incorporate Design Requirements for Switchgear Room Cooling |
| Description | Green. The inspector identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, involving the failure to implement appropriate design control measures associated with a safety-related service water flow calculation. Specifically, several unverified and potentially nonconservative inputs were identified associated with Calculation MC-QIP41-97020, Revision 11, Determination of Minimum Allowable SSW Flows (LOCA Lineup) to Safety Related Heat Exchangers, used to analyze minimum service water flow to the vital switchgear room coolers. The licensee entered this issue into their corrective action program as Condition Report CR-GGN-2016-07597, initiated action to update Calculation MC-QIP41-97020, and initiated actions to analyze the ability of vital switchgear room cooling to meet its specified safety function. This performance deficiency was more than minor, and therefore a finding, because it was associated with the design control attribute of the Mitigating Systems Cornerstone, and it adversely affected the cornerstone objective to ensure availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the licensee did not assure that the vital switchgear ventilation system was capable of maintaining the rooms temperature below design requirements under all conditions. The NRC performed an initial screening of the finding in accordance with NRC Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power. Using Inspection Manual Chapter 0609, Appendix A, Exhibit 2, Mitigating Systems Screening Questions, dated July 1, 2012, this finding had very low safety significance (Green) because it: (1) was not a deficiency affecting the design or qualification of a mitigating system; (2) did not represent a loss of system and/or function; (3) did not represent an actual loss of function of a single train for greater than its technical specification allowed outage time; and (4) did not represent an actual loss of function of one or more nontechnical specification trains of equipment designated as high safety-significant in accordance with the licensees maintenance rule program for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. This finding had a cross-cutting aspect in the documentation aspect of the human performance cross-cutting area because the licensee failed to maintain complete, accurate, and up-to-date documentation of the design temperature limits for safety-related equipment. Specifically, the licensee failed to document and evaluate a change to temperature limits related to switchgear cooling to ensure that its use as a design parameter was consistent with original design specifications of the equipment [H.7]. |
| Site: | Grand Gulf |
|---|---|
| Report | IR 05000416/2016004 Section 1R15 |
| Date counted | Dec 31, 2016 (2016Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | C Young G Warnick J Drake L Carson M Hayes M Young N Day N Greene P Elkmann W Sifre |
| Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion III, Design Control Technical Specification |
| CCA | H.7, Documentation |
| INPO aspect | WP.3 |
| ' | |