05000387/LER-2010-003, Regarding Unit 1 Manual Reactor Scram Due to Leakage from the Unit 1 Circulating Water System and Subsequent Flooding of the Unit 1 Condenser Bay

From kanterella
(Redirected from 05000387/LER-2010-003)
Jump to navigation Jump to search
Regarding Unit 1 Manual Reactor Scram Due to Leakage from the Unit 1 Circulating Water System and Subsequent Flooding of the Unit 1 Condenser Bay
ML102571841
Person / Time
Site: Susquehanna 
Issue date: 09/14/2010
From: Rausch T
Susquehanna
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
PLA-6648 LER 10-003-00
Download: ML102571841 (5)


LER-2010-003, Regarding Unit 1 Manual Reactor Scram Due to Leakage from the Unit 1 Circulating Water System and Subsequent Flooding of the Unit 1 Condenser Bay
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3872010003R00 - NRC Website

text

Timothy S. Rausch Sr. Vice President & Chief Nuclear Officer SEP 1 4 2010 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop OP 1 - 17 Washington, DC 20555 PPL Susquehanna, LLC 769 Salem Boulevard Berwick, PA 18603 Tel. 570.542.3445 Fax 570.542.1 504 tsrausch@pplweb.com SUSQUEHANNA STEAM ELECTRIC STATION LICENSEE EVENT REPORT 50-38712010-003-00 LICENSE NO. NPF-14 PLA-6648 Docket No 50-387 Attached is Licensee Event Report (LER) 50-387120 10-003-00. On July 16,201 0, at approximately 1641 EDT, the Susquehanna Steam Electric Station (SSES) Unit 1 reactor was manually scrammed due to a large unisolable circulating water system leak in the main condenser area. This event was determined to be reportable in accordance with 10 CFR 50.73(a)(2)(iv)(A) for an event that resulted in the manual actuation of the Reactor Protection System, Reactor Core Isolation Cooling and the High Pressure Coolant Injection system.

There were no actual consequences to the health and safety of the public as a result of these events.

No commitments were identified in this submittal.

Senior Vice President - Chief Nuclear Officer Attachment Copy: NRC Region I Mr. P. W. Finney, NRC Sr. Resident Inspector Mr. R. R. Janati, DEPIBRP Mr. B. K. Vaidya, NRC Project Manager

NRC FORM 366 (9-2007)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (9-2007)

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digitslcharacters for each block)

1. FACILITY NAME Susquehanna Steam Electric Station Unit 1 APPROVED BY OMB: NO. 3150-0104 EXPIRES: 08/31/2010

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

2. DOCKET NUMBER 05000387
4. TITLE Unit 1 Manual Reactor Scram due to Leakage from the Unit 1 Circulating Water System and Subsequent Flooding of the Unit 1 Condenser Bay
3. PAGE I OF 4
5. EVENT DATE MONTH 07
6. LER NUMBER
12. LICENSEE CONTACT FOR THlS LER
11. THIS REPORT IS SUBMllTED PURSUANT TO THE REQUIREMENTS OF 10 CFRS: (Check all that apply)

[7 20.2201(b) 1 20.2203(a)(3)(i) 1 50.73(a)(2)(i)(C)

[7 50.73(a)(2)(vii) 1 20.2201(d)

[7 20.2203(a)(3)(ii)

[7 50.73(a)(2)(ii)(A)

[7 50.73(a)(2)(viii)(A) 20.2203(a)(I)

[7 20.2203(a)(4)

[7 50.73(a)(2)(ii)(B)

[7 50.73(a)(2)(viii).(B) 1 20.2203(a)(2)(i)

[7 50.36(c)(l)(i)(A)

[7 50.73(a)(2)(iii)

[7 50.73(a)(2)(ix)(A)

[7 20.2203(a)(2)(ii) 1 50.36(c)(l)(ii)(A) 50.73(a)(2)(iv)(A)

[7 50.73(a)(2)(x)

[7 20.2203(a)(2)(iii) 50.36(~)(2)

[7 50.73(a)(2)(v)(A))

  • 73.71 (a)(4)

[7 20.2203(a)(2)(iv)

[7 50.46(a)(3)(ii)

[7 50.73(a)(2)(v)(B);

[7 73.71 (a)(5)

[7 20.2203(a)(2)(v)

[7 50.73(a)(2)(i)(A)

[7 50.73(a)(2)(v)(C)'

OTHER [7 20.2203(a)(2)(vi) 1 50.73(a)(2)(i)(B)

[7 50.73(a)(2)(v)(D)'

Specify in Abstract below or in NRC Form 366A

9. OPERATING MODE
10. POWER LEVEL DAY 16 YEAR 2010 Facility Name Jason Jennings, Senior Engineer - Nuclear Regulatory Affairs YEAR 2010
7. REPORT DATE Telephone Number (Include Area Code)

(570) 542-3 I 55 SEQUENT'AL NUMBER

- 0 0 3 -

MONTH 09

8. OTHER FACILITIES INVOLVED REV NO.

00 FACILITY NAME FACIL1"NAME

CAUSE

DAY 14 DOCKET NUMBER 05000 DOCKET NUMBER 05000 YEAR 2010 SYSTEM

14. SUPPLEMENTAL REPORT EXPECTED YES (If yes, complete 15. EXPECTED SUBMISSION DATE) a N o COMPONENT ABSTRACT (Limit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

On July 16, 201 0, at approximately 1641 EDT, the Susquehanna Steam Electric Station (SSES) Unit 1 reactor was manually scrammed due to a large unisolable circulating water system leak in the main condenser area. All control rods fully inserted. Reactor water level lowered to -28 inches causing Level 3 (+I 3 inches) isolations. Reactor water level was restored and maintained within normal operating range using the Reactor Core Isolation Cooling (RCIC) system. No steam relief valves opened. The main steam isolation valves (MSIVs) were manually closed and the circulating water system was shut down. Pressure control was initiated using the High Pressure Coolant Injection (HPCI) system in the pressure control mode. All safety systems operated as expected. It was estimated that approximately one million gallons of water leaked into the condenser bay area.

The cause of the unisolable circulating water system leak was due to the condenser waterbox manway gasket rolling out of position.

Investigation concluded that the gasket reached the point where it could no longer maintain system pressure and rolled out of position due to gasket creep (i.e., inadequate gasket preload to maintain joint integrity). The gasket extrusion was the result of inadequate preload, rather than a system pressure transient or a material defect. Corrective actions taken for Unit 1 included inspection and replacement of gaskets.

The root causes were determined to be an inadequate manway gasket installation process and inadequate control of information in controlled procedures. Planned actions to prevent recurrence include revising procedures to address gasket installation procedure deficiencies and revising procedures to address isolating individual waterboxes. An extent of condition inspection will be performed on Unit 2 during the next planned downpower.

There were no adverse consequences to the health and safety of the public as a result of this event.

This event is being reported under 10 CFR 50.73(a)(2)(iv)(A) due to the manual actuation of the RPS, RCIC and HPCI system.

15. EXPECTED SUBMISSION DATE MANU-FACTURER MONTH REPORTABLE TO EPlX DAY

CAUSE

YEAR SYSTEM COMPONENT MANU-FACTURER REPORTABLE TO EPlX CONDITION PRIOR TO THE EVENT Unit 1 - Mode 1, 89 percent Rated Thermal Power due to ambient conditions

EVENT DESCRIPTION

On July 16, 2010, at approximately 1641 EDT, the Susquehanna Steam Electric Station (SSES) Unit 1 reactor was manually scrammed due to a large unisolable circulating water system leak in the main condenser area. During attempts to isolate the leak, the operators lowered reactor power from approximately 89 percent to about 39 percent.

It was identified that the leak was coming from two separate condenser waterbox manway door seals. Due to delays in the identification of the leak's location and the failure of the condenser waterbox isolation valves to close electrically, the condenser bay continued to flood. Based on rising water level in the condenser area and the unsuccessful isolation of the source of the leakage, Operations manually scrammed Unit 1 by placing the mode switch in shutdown.

All control rods fully inserted. Reactor water level lowered to -28 inches causing Level 3 (+I3 inches) isolations.

Reactor water level was restored and maintained within normal operating range using the Reactor Core Isolation Cooling (RCIC) system. No steam relief valves opened. The main steam isolation valves (MSIVs) were manually closed and the circulating water system was shut down. Pressure control was initiated using the High Pressure Coolant Injection (HPCI) system in the pressure control mode. All safety systems operated as expected. It was estimated that approximately one million gallons of water leaked into the condenser bay area.

An ENS notification (# 46103) was made to the NRC in accordance with 10 CFR 50.72(b)(2)(iv)(B) for an event or condition that resulted in the actuation of the RPS when the reactor was critical, and 10 CFR 50.72(b)(3)(iv)(A) due to the manual actuation of the RPS, RCIC and HPCI system.

CAUSE OF THE EVENT

The circulating water system leak occurred due to the condenser waterbox manway gasket rolling out of position. The neoprene rubber gaskets tend to "creep" after installation, resulting in the torque on the gasket hold-down bolts to drop below the required torque values as defined in the installation procedure. The root cause determined that the lower preload torque resulting from the gasket "creep" would have been detected and the failure likely precluded had the installation procedure required a re-check of the manway hold-down bolt torque. The procedure does require a leak check to be performed at system operating conditions, but no requirement to re-check the torque values is required by the procedure.

Other contributing causes of the failure include use a bolt torque value not in accordance with current manufacturer recommendations, irregularities in the manway seating area, and less than optimal manway cover design.

Investigation concluded that the gasket reached the point where it could no longer maintain system pressure and rolled out of position due to gasket 'creep" (i.e., inadequate gasket preload to maintain joint integrity). The gasket extrusion was the result of inadequate preload, rather than a system pressure transient or a material defect.

During the flooding, Operations was not able to positively determine which waterbox was leaking due to procedural deficiencies. It is likely that if the correct waterbox was initially selected to isolate the leak, the leak would have been effectively isolated with minimal flooding in the condenser bay.

ANALYSIS 1 SAFETY SIGNIFICANCE A circulating water system rupture is an anticipated event as discussed in Section 10.4.1.3.3 in the SSES Final Safety Analysis Report (FSAR). The presence of any water accumulation in the condenser bay is detected by level switches which are mounted on the shielding wall at various points around its perimeter. These switches did alarm in the control room during the flooding event.

2. DOCKET 05000387
3. PAGE 2 0 F 4 6 LERNUMBER YEAR 201 0
- 003-00 SEQUENTIAL NUMBER REVISION NUMBER NRC FORM 366A U.S. NUCLEAR REGULATORY COMMISSION (9-2007)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET I. FACILITY NAME Susquehanna Steam Electric Station Unit I The condenser bay is designed to contain the water from a circulating water system rupture. The concrete shielding walls which surround the condenser bay are designed to withstand the possible 20 feet of differential water pressure they could experience in the event of a major rupture. Water level reached approximately 12 feet in the condenser bay during the event, which is well within the design flood level.

The 656 foot elevation doors, which provide access through the shielding walls, are pressure resistant. While not watertight, these doors do restrict water leakage out of the condenser bay in the event of flooding. Also, while penetrations through the walls are not watertight, they are filled with a sealant for radiation shine which serves to limit the quantity of water leaking out of the condenser bay in the event that it becomes flooded.

There is no safety-related equipment in the Turbine Building below grade (676 foot elevation), and the penetrations below grade, between the Turbine building and the Reactor Building, are designed to prevent flooding of the Reactor Building.

There was no significant water accumulation in the turbine building, outside of the condenser bay, during this event - the flooding was effectively contained within the condenser bay.

Neither a major rupture of the circulating water system nor a rupture of the condenser hotwell will have an effect on any safety-related system since no safety-related systems are located within this area.

Potential Consequences The SSES Plant Analysis group prepared a risk assessment for the plant shutdown initiating event. This risk assessment takes into consideration the plant conditions immediately leading to shutdown, the equipment out of service for maintenance at the time of shutdown, and the conditions at the time of shutdown. Flooding in the condenser bay is not considered an initiating event in the SSES Probabilistic Risk Assessment model. It is assumed in flood calculations that a flood in the condenser bay will eventually result in a plant shutdown due to loss of the main condenser. It is anticipated that the shutdown would occur by either an automatic or manual reactor scram. During the event, a manual scram was executed from approximately 39 percent power. The circulating water system was shutdown and the MSIV's were isolated. Equipment in the area that may have been out of service as a result of the flooding was non-safety related power generation equipment and therefore was not required for safe shutdown of the unit.

Actual Consequences There was no impact on plant safety as a result of this event. The reactor was manually scrammed and the unit safely shutdown. There was no impact on Unit 2 as a result of these actions. A manual reactor scram is consistent with expected operator actions for flooding events of this magnitude. The MSlVs were manually closed and circulating water was isolated. HPCl was used for pressure control, RClC for level control. HPCl tripped and RClC shut down by design when high vessel water level was received. No mitigating systems were out of service during this event.

Based upon the above discussion, the actual consequences of this event were minimal. There was no impact to the health and safety of the public.

CORRECTIVE ACTIONS

Com pleted Actions:

The following actions have been completed on Unit 1 :

All manway gaskets were inspected and replaced as required.

2. D O C M 05000387
3. PAGE 3 0 F 4
6. LERNUMBER YEAR 201 0
- 003-00 SEQUENTIAL NUMBER REVISION NUMBER NRC FORM 366A U.S. NUCLEAR REGULATORY COMMISSION (9-2007)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME Susquehanna Steam Electric Station Unit 1 The epoxy coating on the manway at the gasket seating surface has been re-worked to provide a smooth and uniform surface where the gasket fits over the end of the manway.

The manway hatch epoxy coated surfaces have been roughened to increase friction between the hatch and the gasket contact surface.

An installation check has been incorporated into the work packages to ensure proper seating of the gasket prior to installing the hatch.

The manway hatch bolt torque for new installation has been increased from 60 ft-lbs to 11 0 ft-lbs. Testing demonstrated that I 10 ft-lbs torque provides the desired 50% crush on the gasket as per vendor recommendation.

Bolt torquing was performed in a star pattern at 25% increments, let idle for a minimum of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, and then torque checked at 1 10 ft-lbs to address any gasket creep.

Planned Corrective Actions

Revise procedures to address gasket installation procedure deficiencies.

Enhance the inspection procedure to ensure compliance with Manway coating specification.

Revise procedures to address isolating individual waterboxes for leak between waterbox inlet and outlet valves and add diagrams to aid in leak isolation if required.

Perform an extent of condition inspection on Unit 2 during next planned downpower.

2. DOCKET 05000387
3. PAGE 4 0 F 4 6 LERNUMBER YEAR 201 0
- 003-00 SEQUENTIAL NUMBER REVISION NUMBER