LER-1995-001, Cancels LER 95-001-00 for Facility.Licensee Determined That LaSalle County Station Not in Condition Prohibited by TS 3.4.3.2
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3731995001R00 - NRC Website

text

Commonwealth lilimn Company lahalle Gencrating Atation

~"

2601 North 21st Road Marseillen, 11.61341 9-(7 Tel H15357476 l January 23,1996 United States Nuclear Regulatory Conunission Attention: Document Control Desk Washington, D.C. 20555 The cwaHation ofLicensee Event Report #95-001-00, Docket #050-373 is being

)

submitted to your office in accordance with 10 CFR 50.73 (a) (2) (i) (B).

Upon further review of this licensee event report, it has been determined that LaSalle County Station was not in a condition prohibited by Technical Specification 3.4.3.2.

Technical Specification 3.4.3.2.d. states, "With one or more higMow pressure interface valve leakage pressure monitors inoperable, restore the inoperable monitor (s) to OPERABLE status within 7 days or verify the pressure to be less than the alarm setpoint at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by local indication". Since local verification was accomplished on a shiftly (8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />) basis by the Unit 1 Equipment Attendant, LaSalle was in full compliance with Tech Spec 3.4.3.2.

Our lack of thoroughness during the initial review of this event caused us to inappropriately classify this event as reportable under 10 CFR 50.73. LaSalle Station has implemented a more rigorous initial screening and technical review process.

Sin l

D. J.

y Station Manager LaSalle County Station Enclosure cc:

H. J. Miller, NRC Region III Administrator H. J. Simons, Acting NRC Senior Resident Inspector IDNS Resident Inspector F. Niziolek, IDNS Senior Reactor Analyst INPO-Records Center D. L. Farrar, Nuclear Regulatory Services Manager PRnno~

}\\ D 960t260231 960123 PDR ADOCK 05000373 j

g PDR A I!nicom Company