05000348/FIN-2008006-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Areas Where Omas Are Performed DID Not Have Elus Installed |
| Description | The team identified a non-cited violation of Farley Unit 2 Operating License Condition 2.C.(6), for the licensees failure to fully implement the approved fire protection program, in that emergency lighting units (ELUs) were not installed in all areas where local operator manual actions were required to support post-fire safe shutdown. Specifically, the team determined that there were no ELUs installed to illuminate the front panels of the Reactor Coolant Pump (RCP) switchgear, located in the Train A switchgear room, where post-fire safe shutdown local operator manual actions were required to trip the RCP 4160 Volt alternating current breakers. The finding was entered into the licensees corrective action program under Condition Reports 2008103335, 336, and 337. The finding is greater than minor because it is associated with the reactor safety Mitigating Systems cornerstone attribute of protection against external factors (i.e., fire) and it affects the cornerstone attribute of ensuring reliability and capability of systems that respond to initiating events. Specifically, the finding adversely affected the ability to perform local operator manual actions required to achieve and maintain safe shutdown conditions following a fire in the cable spreading room. The inspectors assessed the finding using IMC 0609, Appendix F, Fire Protection Significance Determination Process. The team determined that this finding was of very low safety significance (Green) because the operators had a high likelihood of completing the task using flashlights, which operators are directed to carry with them by procedure while performing local actions |
| Site: | Farley |
|---|---|
| Report | IR 05000348/2008006 Section 1R05 |
| Date counted | Jun 30, 2008 (2008Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | N Merriweather S Walker G Wiseman R Fanner D Merzke |
| INPO aspect | |
| ' | |
Finding - Farley - IR 05000348/2008006 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Farley) @ 2008Q2
Self-Identified List (Farley)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||