Finding | |
|---|---|
| Title | Failure to Translate Design Requirements of the RHRHVAC System into Procedures |
| Description | The inspectors identified a finding of very low safety significance with an associated NCV of 10 CFR 50, Appendix B, Criterion III, Design Control. Specifically, the licensee failed to demonstrate the residual heat removal heating, ventilation, and air conditioning (RHRHVAC) system would be able to maintain a required minimum temperature of 40 degrees Fahrenheit (F) for the emergency diesel generator (EDG) fuel oil storage tank (FOST) rooms under minimum design conditions, potentially rendering the EDGs inoperable. The licensee entered this issue into the corrective action program and revised the operator rounds procedure to record ambient air temperature readings in the EDG FOST rooms on a daily basis when the outside ambient air temperature is below 45F. The performance deficiency was of more than minor safety significance because a failure to correctly incorporate design requirements into plant procedures has the potential to lead to a more significant safety concern if left uncorrected. Specifically, since the EDG FOST rooms were unmonitored and a subsequent calculation demonstrated the RHRHVAC system was not able to maintain the minimum required temperature in the rooms as described in the design basis, the EDGs could have been rendered inoperable without the licensees knowledge. The finding was determined to be of very low safety significance since it affected the design or qualification of a mitigating structure, system, or component (SSC), for which the SSC maintained its operability or functionality. The inspectors concluded that because this condition has existed for greater than three years, this issue would not be reflective of current licensee performance and no cross-cutting aspect was identified. |
| Site: | Fermi |
|---|---|
| Report | IR 05000341/2016001 Section 1R15 |
| Date counted | Mar 31, 2016 (2016Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | B Dickson B Kemker J Nance P Smagacz |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| INPO aspect | |
| ' | |
Finding - Fermi - IR 05000341/2016001 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fermi) @ 2016Q1
Self-Identified List (Fermi)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||