/03L-0 on 790525:during Check of Control Room Chlorine Detection Sys,Both Detectors Declared Inoperable Due to Low Drip Rates in Sensor.Caused by Clogged Dispensers.Dispensers Cleaned,Restoring Operability
ML19269E552
Person / Time
Site: Millstone Dominion icon.png
Issue date: 06/22/1979
From: Bates R
NORTHEAST UTILITIES
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19269E544 List:
References
LER-79-013-03L-01, LER-79-13-3L-1, NUDOCS 7906290269
Download: ML19269E552 (1)


LER-1979-013, /03L-0 on 790525:during Check of Control Room Chlorine Detection Sys,Both Detectors Declared Inoperable Due to Low Drip Rates in Sensor.Caused by Clogged Dispensers.Dispensers Cleaned,Restoring Operability
Event date:
Report date:
3361979013R03 - NRC Website

text

NRC PORM 366 U. S. NUCLEAR REGULATORY COMMISSION mm LICENSEE EVENT REPORT CONTROL BLOCK: l I

l l

I I lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) 1 6

l Cl Tl M l N I S l 21@l 0 l 0 l-1010 l 01010 l-l010 l@l411 Il 11 11 l@l l

l@

o i

7 8 9 UCENSEE CODE 14

S LICENSE NLMSER 25 26 UCENSE TYPE JG

$7 CAT $8 CON'T 3O,3 L l@l 0 i 5 l 0 l 010 l 31316 !@l 015 l 215 l 719 )@l 01612121719 @

o i

7 3

60 61 OCCKET NUM8ER e8 69 EVENT OATE 14 75 REPORT DATE 80 EVENT CESCRIPT1oN AND PROBA8LE CONSEQUENCES h 0i2i l Following a periodic check of the control room chlorine detection system, both l

detectors were declared inoperable due to having low drip rates in the sentir l

0 3

0,A assembly. The control room emergency ventilation system was immediately placed in l

the recirculation mode in accordance with technical specifications section 3.3.3.6, l

0i3 i 1 action statement b.

Following sensor cleaning the detectors were returned to service !

0,a Oi7 i and the ventilation system was restored to normal.

i Jld l

E OE SLSC E COMPCNENT CODE SL8 COO'E SU E

I Il Fl@ lX l@ lZ l@ l Il Nl Sl Tl R U l@ l E l@ l Z l @

O 9

7 d

9 to 11 12 13 18 19 20 SECU ENTI AL OCOUR R ENCE REPORT REVISION LER EVENT Y EAR REPORT NO.

COOE TYPE NO.

@sgo/RO i Ti al I-I I o l n 31 1-I Ioi3I UJ l-l Laj g

a

_ 21 22 23 24 26 27 28 29 30 31 32 T

N AC O O P NT M

MOURS S 8 4 POR 8.

SLP L E MANUFAC RER I B l@l Z l@

l ZI@

l Zi@

l 01010101 I NI@

lNI@

lAl@

l W l 0 l 2 i S l@

33 54 35 06 37 40 41 42 43 44 47 CAUSE CESCRIPTION AND CORRECTIVE ACTIONS t to 1The detectors were declared inocerable due to low drio rates of detector solution anto the sensor assembly. The low drio rates were due to clogged dispensers which i

i i

]were cleaned, restoring proper drip rate and returning both detectors to operability. I

,,2 i,

2 i Frequency of drip rate checks will be increased to daily to prevent a similar I

irecurrence.

l

,4 7

3 3 30 ST

% PCWER OTHER STATUS is O RY OISCOVERY OESCRIPTION i i3 El @ l 0l 5 0l@l NA l

l8l@l Operator Observation l

ACTIVITY CO TENT

=ELEASED OF RELEASE AMOUNT OF ACTIVITY LOCATION OF RELEASE i is l Z l @ lZ lg NA l

NA l

3 3 to tt 44 45 30

  • ERSONNEL EXPCSURES NUV8ER