05000334/LER-2011-001, Regarding Use of Liquid Tight Flexible Conduits Installed in Fire Barrier Penetrations Results in Unanalyzed Configurations
| ML11362A358 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 12/20/2011 |
| From: | Harden P FirstEnergy Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-11-392 LER 11-001-00 | |
| Download: ML11362A358 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3342011001R00 - NRC Website | |
text
FENOC FirstEnergy Nuclear Operating Company Beaver Valley Power Station P.O. Box 4 Shippingport, PA 15077 Paul A. Harden Site Vice President 724-682-5234 Fax: 724-643-8069 December 20, 2011 L..11-392 10 CFR 50.73 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 LER 2011-001-00 Enclosed is Licensee Event Report (LER) 2011-001-00, "Use of Liquid Tight Flexible Conduits Installed In Fire Barrier Penetrations Results In Unanalyzed Configurations."
This event is being reported in accordance with 10 CFR 50.73(a)(2)(ii)(B).
There are no regulatory commitments contained in this submittal. Any actions discussed in this document that represent intended or planned actions are described for the NRC's information, and are not regulatory commitments.
If there are any questions or if additional information is required, please contact Mr. Darin M. Benyak, Manager, Regulatory Compliance at 724-682-4284.
Paul A. Harden Enclosure - BVPS Unit 1 LER 2011-001-00 c:
Mr. W. M. Dean, NRC Region I Administrator Mr. D. I. Spindler, NRC Senior Resident Inspector Ms. N. S. Morgan, NRR Project Manager INPO Records Center (via electronic image)
Mr. L. E. Ryan (BRP/DEP) x
- ý'&
Jý0ýý
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB NO. 3150-0104 EXPIRES 10/31/2013 (10-2010)
, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
- 3. PAGE Beaver Valley Power Station Unit Number 1 05000334 1 OF 4
- 4. TITLE Use of Liquid Tight Flexible Conduits Installed In Fire Barrier Penetrations Results In Unanalyzed Configurations
- 5. EVENT DATE
- 6. LER NUMBER 1
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL REV MONTH DAY YEAR NoneT NM NUME NO None_____
L IZ FAILITY NAME DOCKET NUMBER 11 02 2011 2011 - 001 - 00 12 20 2011
- 9.
OPERATING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply)
El 20.2201(b)
[: 20.2203(a)(3)(i)
El 50.73(a)(2)(i)(C)
El 50.73(a)(2)(vii)
LI 20.2201(d)
[] 20.2203(a)(3)(ii)
El 50.73(a)(2)(ii)(A)
[] 50.73(a)(2)(viii)(A)
[] 20.2203(a)(1)
El 20.2203(a)(4)
[D 50.73(a)(2)(ii)(B)
El 50.73(a)(2)(viii)(B)
_l 20.2203(a)(2)(i)
[L 50.36(c)(1)(i)(A)
El 50.73(a)(2)(iii)
DI 50.73(a)(2)(ix)(A)
- 10. POWER LEVEL LI 20.2203(a)(2)(ii)
LI 50.36(c)(1)(ii)(A)
El 50.73(a)(2)(iv)(A)
LI 50.73(a)(2)(x)
El 20.2203(a)(2)(iii)
LI 50.36(c)(2)
El 50.73(a)(2)(v)(A)
El 73.71(a)(4) 100 LI 20.2203(a)(2)(iv)
LI 50.46(a)(3)(ii)
El 50.73(a)(2)(v)(B)
LI 73.71 (a)(5)
[1 20.2203(a)(2)(v)
El 50.73(a)(2)(i)(A)
El 50.73(a)(2)(v)(C)
[]iO in Abstract below or in
- - 0 20.2203(a)(2)(vi)
[: 50.73(a)(2)(i)(B)
El 50.73(a)(2)(v)(D)
Energy industry identification system (EIIS) codes are identified in the text using the format [XX].
CONDITIONS PRIOR TO OCCURRENCE Unit 1: Mode 1 at 100 percent power There were no systems, structures, or components that were inoperable at the start of the event that contributed to the event other than as described below.
DESCRIPTION OF EVENT
On November 2, 2011, the Beaver Valley Power Station National Fire Protection Association (NFPA) 805 transition project personnel identified that samples taken from the outer coating from certain liquid tight flexible conduits (CND] installed through fire barrier penetrations [PEN] did not exhibit expected flame resistant characteristics and were not in conformance with documented previously tested fire barrier configurations at Beaver Valley Power Station Unit 1 (BVPS-1). Liquid tight flexible conduit is typically made from a segmented steel material and coated with a thin layer of polymer material (typically poly vinyl chloride (PVC) material) which provides the liquid tight function. The polymer material and thickness used varies from each manufacturer and type specified. Since the BVPS-1 installed configurations may not conform to previously qualified fire barrier configurations, it was postulated that a fire in one fire area could eventually spread to another fire area by burning or melting of the outer polymer coating material which may allow hot gas or flame to breach the three hour rated fire seal. Ignition of polymer coating on the opposite side penetration from heat transfer might also be a possible fire spread mechanism.
Following identification of this issue, compensatory actions were promptly implemented to provide an adequate level of protection for redundant equipment. These include a twice per twelve hour shift fire watch patrol in the affected plant areas, and the restrictions for performing hot work in the vicinity of the affected penetrations. In addition, transient combustible materials are prohibited in affected plant areas from being stored adjacent to electrical penetrations fire seals or adjacent to conduit within five feet of an electrical penetration fire seal as a compensatory action.
Walkdowns performed at BVPS-1 have identified that approximately 924 of the 2843 electrical conduit fire barrier penetrations between separate fire areas contain liquid tight flexible conduit. Sixteen different types of coating material have been identified based on external characteristics such as manufacturer markings or color. Preliminary test results for eight of the 16 types indicate that the lowest auto-ignition temperature was 734 degrees Fahrenheit, which is greater than the 700 degrees Fahrenheit maximum acceptance temperature for the cold side of a rated fire penetration seal specified in IEEE 634 - 1978.
No fire barrier penetrations containing liquid tight flexible conduit have been identified at Beaver Valley Power Station Unit 2 (BVPS-2) based on general area walkdowns. Furthermore, review of the BVPS-2 design specifications indicated that they prohibit use of PVC flexible conduit in BVPS-2 plant fire areas other than the Alternate Intake Structure. A fire in the Alternate Intake Structure does not affect post fire safe shutdown.
CAUSE OF EVENT
A significant number of BVPS-1 fire barrier penetrations contain liquid tight flexible conduit (excluding the reactor containment and the river water main intake structure) with a polymer jacket material typically made of PVC. The liquid tight flexible conduits were installed during initial plant construction in accordance with plant design specifications in effect at the time. Qualified fire seals were subsequently installed in the penetrations where these liquid tight flexible conduits passed through. However, no documentation has been found to show that this type of configuration meets NRC Branch Technical Position (BTP) Auxiliary and Power Conversion Systems Branch (APCSB) 9.5-1 requirements for a three hour fire barrier.
The apparent cause of this latent issue is inadequate review of accumulative effects to all field changes.
Specifically, the subsequent installation of otherwise qualified fire seals did not consider potential compromise by the jacket material of the previously installed liquid tight flexible conduit acting as a penetrant.
The inadequate design of the BVPS-1 fire barrier penetrations was due to a lack of knowledge on the part of the installation vendor at the time the fire seal program was initially implemented (approximately in the late 1970's). The liquid tight flexible conduit was installed during initial plant construction to a 1973 design specification that specifically called out the use of PVC jackets due to its temperature rating and moisture resistance qualities.
The 1973 design specification was developed prior to subsequent requirements (which derived from BTP APCSB 9.5-1 in 1976) that the penetrations through walls be sealed with material equivalent to the barrier rating. When BVPS-1 committed to sealing in accordance with the BTP in the late 1970's, it appears attention was focused on the type and depth of sealant to meet the existing tested configurations, without recognizing that the installation also depended upon the conduit sheathing against which the seal was being applied.
ANALYSIS OF EVENT
BVPS-1 fire barriers containing liquid tight flexible conduit are non-conforming with the provisions of NRC BTP APCSB 9.5-1, as documentation of a three hour barrier for this type of configuration was not found and some of the outer coatings did not exhibit expected flame resistant characteristics. Approximately 924 of 2843 electrical conduit fire barrier penetrations at BVPS-1 are currently known to be potentially affected (i.e., contain liquid tight flexible conduits). The BVPS-1 plant areas that require fire barriers for train separation for safe shutdown equipment are potentially affected, except for the reactor containment and the river water main intake structure. Following identification of the issue, compensatory actions including fire watch patrols and restrictions for performing hot work, and storage of transient combustible material near the affected penetrations were promptly implemented. Existing plant fire suppression and detection equipment and pre-planned fire response strategies along with the compensatory actions implemented provides for an adequate level of protection for redundant equipment.
A risk assessment was performed that evaluated the significance of multi-compartment fires generated from the BVPS-1 fire compartments that may contain liquid tight flexible conduits installed in fire barrier penetrations. This assessment was based on the fire scenarios developed for NFPA 805 using the BVPS-1 Probabilistic Risk Assessment (PRA) model, which were modified to determine the change in core damage frequency (CDF) due to a fire propagating through the analyzed fire barrier penetrations.
Based on the results of the risk evaluation described above, the overall safety significance due to the impact of these non-compliant liquid tight flexible conduits being used in penetration fire barriers is considered to be low to moderate, based on the summation of the analyzed individual fire compartment delta CDFs for the affected areas.
Since no documentation to prove qualification of the fire barrier penetrations containing liquid tight flexible conduits has been located, a conservative assumption was made that their function of preventing a fire from affecting redundant trains of safe shutdown systems for the required three hours could not be assured. NRC guidance on reportability, NUREG-1022, Event Reporting Guidelines for 10 CFR 50.72 and 50.73, Revision 2, states that if fire barriers are missing, such that the required degree of separation for redundant safe shutdown trains is lacking, the issue is reportable as an unanalyzed condition that significantly degraded plant safety. Therefore, this report is being submitted pursuant to 10 CFR 50.73(a)(2)(ii)(B). This event was previously reported as an unanalyzed condition that significantly degrades plant safety pursuant to 10 CFR 50.72(b)(3)(ii)(B) at 2041 hours0.0236 days <br />0.567 hours <br />0.00337 weeks <br />7.766005e-4 months <br /> on November 2, 2011 (Event Notification 47403).
CORRECTIVE ACTIONS
- 1. Samples of liquid tight flexible conduit jacketing obtained from the non-conforming fire barrier penetrations at BVPS-1 will be tested for auto-ignition temperature and flame resistance at an accredited laboratory in order to determine their ability to withstand the effects of postulated fires.
- 2. The existing penetration fire seal configurations with polymer conduit jackets identified as non-conforming will be evaluated in accordance with NRC Generic Letter (GL) 86-10 to determine their acceptability considering the results of testing. Modifications to the polymer jacketed conduit may also be performed on a case-by-case basis to restore compliance.
- 3. If any of the non-conforming penetration fire seal configurations being evaluated under NRC GL 86-10 are unable to be accepted with existing testing information, a specific penetration test utilizing an appropriate testing configuration will be performed at an accredited testing facility to qualify the configuration. The non-conforming fire barriers may be modified to restore compliance on a case-by-case basis in lieu of the specific penetration testing.
Completion of the above and other corrective actions are being tracked through the BVPS corrective action program.
PREVIOUS SIMILAR EVENTS
A review found no prior BVPS-1 or BVPS-2 Licensee Event Reports within the past five years for an event involving non-conforming fire barrier penetrations.
CR 2011-04769