Finding | |
|---|---|
| Title | Failure to Verify the Design Requirements for the Fuel Oil Transfer Pumps |
| Description | The team identified a finding of very low safety significance involving a non-cited violation (NCV) of 10 CFR 50, Appendix B, Criterion lll, Design Control because FENOC did not verify or check the adequacy of the Unit 1 emergency diesel generator (EDG) fuel oil transfer system design. Specifically, FENOC did not ensure adequate net positive suction head (NPSH) for the fuel oil transfer pumps during worst case design conditions, and did not evaluate the effect air voids in the suction piping would have on the pumps. FENOC entered the issue into the corrective action program, and performed testing on the fuel oil transfer system and consulted with the pump vendor to determine if the design of the system was adequate. Following completion of the testing and new calculations, FENOC determined that the pumps were operable but degraded. The team determined that the issue was more than minor because it was associated with the Mitigating Systems Cornerstone attribute of Design Control and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding was of very low safety significance (Green) because it was a design deficiency confirmed not to result in a loss of operability or functionality. The team determined that there was not a crosscutting aspect associated with this finding because it was not indicative of current performance. |
| Site: | Beaver Valley |
|---|---|
| Report | IR 05000334/2011007 Section 1R21 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | K Mangan G Skinner F Arner M Young J Ayala M Yeminy L Doerflein |
| INPO aspect | |
| ' | |
Finding - Beaver Valley - IR 05000334/2011007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Beaver Valley) @ 2011Q2
Self-Identified List (Beaver Valley)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||