05000324/LER-2006-002, Regarding Manual Scram Due to Conductivity Increase

From kanterella
(Redirected from 05000324/LER-2006-002)
Jump to navigation Jump to search
Regarding Manual Scram Due to Conductivity Increase
ML070170462
Person / Time
Site: Brunswick 
(DPR-062)
Issue date: 01/10/2007
From: Waldrep B
Progress Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
BSEP 07-0007 LER 06-002-00
Download: ML070170462 (6)


LER-2006-002, Regarding Manual Scram Due to Conductivity Increase
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3242006002R00 - NRC Website

text

4Progress Energy January 10, 2007 SERIAL: BSEP 07-0007 10 CFR 50.73 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

Subject:

Brunswick Steam Electric Plant, Unit No. 2 Docket No. 50-324/License No. DPR-62 Licensee Event Report 2-2006-002 Ladies and Gentlemen:

In accordance with the Code of Federal Regulations, Title 10, Part 50.73, Carolina Power

& Light Company, now doing business as Progress Energy Carolinas, Inc., submits the enclosed Licensee Event Report.

Please refer any questions regarding this submittal to Mr. Randy C. Ivey, Manager - Support Services, at (910) 457-2447.

Sincerely, B. C. tWad Iep Plant General Manager Brunswick Steam Electric Plant TMS/tms

Enclosure:

Licensee Event Report Progress Energy Carolinas, Inc.

Brunswick Nuclear Plant P.O. Box 10429 Southport, NC 2B461 CA

Document Control Desk BSEP 07-0007 / Page 2 cc (with enclosure):

U. S. Nuclear Regulatory Commission, Region II ATTN: Dr. William D. Travers, Regional Administrator Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, GA 30303-8931 U. S. Nuclear Regulatory Commission ATTN: Mr. Eugene M. DiPaolo, NRC Senior Resident Inspector 8470 River Road Southport, NC 28461-8869 U. S. Nuclear Regulatory Commission ATTN: Mr. Stewart N. Bailey (Mail Stop OWFN 8B 1) (Electronic Copy Only) 11555 Rockville Pike Rockville, MD 20852-2738 Ms. Jo A. Sanford Chair - North Carolina Utilities Commission P.O. Box 29510 Raleigh, NC 27626-051

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB NO. 3150-0104 EXPIRES 06/30/2007 (6-2004)

, the NRC may not conduct or sponsor, and a person is not required to respond to the information collection.

3. PAGE Brunswick Steam Electric Plant (BSEP), Unit 2 05000324 1 of 4
4. TITLE Manual Scram Due To Conductivity Increase
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL I REV FACILITY NAME DOCKET NUMBER MNHDY YA YER NUMBER NO MNHDY EA NME NO IFACILITY NAME DOCKET NUMBER 11 11 2006 2006 --

002 00 1

10 2007 FACILITYNAME DOCKET NUMBER

_________________05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check one or more) 2 0l 20.2201(b)

El 20.2203(a)(3)(i)

El 50.73(a)(2)(i)(C)

El 50.73(a)(2)(vii)

El 20.2201(d)

El 20.2203(a)(3)(ii)

El 50.73(a)(2)(ii)(A)

El 50.73(a)(2)(viii)(A)

[I 20.2203(a)(1)

El 20.2203(a)(4)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(viii)(B)

El 20.2203(a)(2)(i)

El 50.36(c)(1)(i)(A)

El 50.73(a)(2)(iii)

El 50.73(a)(2)(ix)(A)

10. POWER LEVEL El 20.2203(a)(2)(ii)

El 50.36(c)(1)(ii)(A) 0 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x) 1%

El 20.2203(a)(2)(iii)

[] 50.36(c)(2)

El 50.73(a)(2)(v)(A)

El 73.71(a)(4)

El 20.2203(a)(2)(iv)

El 50.46(a)(3)(ii)

El 50.73(a)(2)(v)(B)

E] 73.71(a)(5)

El 20.2203(a)(2)(v)

El 50.73(a)(2)(i)(A)

El 50.73(a)(2)(v)(C)

E]

OTHER Specify in Abstract below El 20.2203(a)(2)(vi)

El 50.73(a)(2)(i)(B)

El 50.73(a)(2)(v)(D) or in- (If more space is required, use additional copies of (If more space is required, use additional copies of NRC Form 366A) (17)

Previous Similar Events

A review of LERs and corrective action program condition reports for the past three years identified the following similar event at BSEP.

Nuclear Condition Report (NCR) 135131 On August 18, 2004 at 2138 EST, during power ascension following a shutdown initiated by a loss of offsite power, the presence of a condenser tube leak was observed when elevated chloride levels from the 1A North waterbox (i.e., 50 ppb) and the condensate discharge header (i.e., 13.7 ppb) were recorded. A Unit 1 downpower to 53% was made to identify the location of the leak and perform immediate corrective actions in the form of plugging 95 tubes identified with missing plugs. The long term corrective action of the NCR as a result of this event was to generate a preventive maintenance task to tighten the tube plugs each refueling outage. This has been determined to be an inadequate corrective action.

Commitments

No regulatory commitments are contained in this report.