05000324/FIN-2015002-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Degraded Fire Barrier Seals in the Unit 2 Cable Access Way |
| Description | An NRC-identified Green non-cited violation (NCV) of License Condition 2.B.(6), Fire Protection Program, was identified for the licensees failure to maintain the 3-hour fire seals in the Unit 2 cable access way. Specifically, three cables in the Unit 2 cable access way were not within continuously enclosed conduits, which failed to preserve the integrity of the 3-hour rated barrier. As corrective action, the licensee sealed all three penetrations with a qualified 3-hour seal. This issue was entered into the licensees corrective action program (CAP) as nuclear condition report (NCR) 740606. The inspectors determined that the licensees failure to maintain the 3-hour penetration fire barrier conduits in the Unit 2 cable access way, as required by licensee specification 118-003, Selection and Installation of Fire Barrier and Pressure Boundary Penetration Seals, was a performance deficiency. The finding was more than minor because it was associated with the external factors attribute (i.e. fire) of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, this resulted in the failure of the three conduits to perform their function. The finding was screened using NRC IMC 0609, Appendix F, Fire Protection Significance Determination Process, dated September 20, 2013, because the finding affected the ability to confine a fire. Using IMC 0609, Appendix F, Attachment 1, Fire Protection SDP Phase 1 Worksheet, dated September 20, 2013, the finding was assigned to the Fire Confinement category because the degraded penetrations were located in a fire barrier that separated two fire areas. Proceeding to Task 1.3.1 of IMC 0609, Appendix F, Attachment 1, the inspectors determined the finding was of very low safety significance (Green) because safety significant equipment was located a sufficient distance from the degraded penetrations and the reactors ability to reach and maintain a safe shutdown condition was not impacted. The finding does not have a cross-cutting aspect since the performance deficiency is not indicative of current plant performance. (Section 1R05) |
| Site: | Brunswick |
|---|---|
| Report | IR 05000324/2015002 Section 1R05 |
| Date counted | Jun 30, 2015 (2015Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | G Hopper M Catts M Orr M Riches M Schwieg |
| Violation of: | License Condition - Fire Protection License Condition |
| INPO aspect | |
| ' | |
Finding - Brunswick - IR 05000324/2015002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Brunswick) @ 2015Q2