Finding | |
|---|---|
| Title | Scaffolding Impairs Fire Sprinkler Systems in Safety Related Fire Areas |
| Description | The inspectors identified a Green, NCV of CCNPP Renewed Facility Operating License for Units One and Two, paragraph 2.E for Exelons failure to maintain in effect all provisions of the approved fire protection program as described in the Updated Final Safety Analysis Report (UFSAR). Specifically, Exelon installed scaffolding in safety related areas not in accordance with approved procedures and, therefore, impaired fire sprinkler systems that were required by the approved fire protection program without establishing approved contingency measures. The inspectors determined that Exelons impairment of fire sprinkler systems by installing scaffolding with dimensions exceeding those approved in Exelon procedure MA-AA-716-025 was a performance deficiency that was within Exelons ability to foresee and prevent. The performance deficiency led to the violation of CCNPP Renewed Facility Operating License, paragraph 2.E, because Exelon failed to maintain in effect all provisions of the approved fire protection program. Exelons immediate corrective actions included stationing continuous fire watches and removal of the scaffolding deck boards which were impairing the fire sprinkler systems. Exelon entered these issues in to their corrective action program (CAP) as issue reports (IR): 02642463, 02642549, 02642844, 02644495, 02647104, 02647454, and 02647455. The inspectors reviewed IMC 0612, Appendix B, Issue Screening, and determined the issue is more than minor because it adversely affected the protection against external factors attribute of the Mitigating Systems cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, Exelon installed scaffolding that exceeded the allowed dimensions in MA-AA-716-025 and impaired the function of fire sprinkler systems in areas containing safety related equipment. The inspectors evaluated the finding using IMC 0609, Attachment 4, Initial Characterization of Findings, issued on June 19, 2012, and IMC 0609, Appendix F, The Fire Protection SDP Worksheet issued on September 20, 2013 and determined the finding to be of very low safety significance (Green) because, in all cases of impairment, the fire sprinkler systems were still capable of protecting their intended targets or were still capable to suppress fires such that no additional equipment important to safety would have been affected. The inspectors determined that the finding had a cross-cutting aspect in the area of Human Performance, Procedure Adherence, because Exelon failed to properly implement procedure MA-AA-716-025, Scaffold Installation, Modification, and Removal Request Process, Revision 11, which limits scaffolding dimensions and locations when installing scaffolding in safety related areas. [H.8] |
| Site: | Calvert Cliffs |
|---|---|
| Report | IR 05000317/2016002 Section 1R05 |
| Date counted | Jun 30, 2016 (2016Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | A Dimitriadis A Rosebrook C Roettgen J Petch M Modes R Clagg |
| Violation of: | License Condition - Fire Protection |
| CCA | H.8, Procedure Adherence |
| INPO aspect | WP.4 |
| ' | |
Finding - Calvert Cliffs - IR 05000317/2016002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Calvert Cliffs) @ 2016Q2
Self-Identified List (Calvert Cliffs)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||