05000313/FIN-2008007-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Licensee-Identified Violation |
| Description | Unit 1, Technical Specification 5.4.1 and Unit 2, Technical Specification 6.4.1 require written procedures be established, implemented, and maintained covering the applicable procedures recommended in Regulatory Guide 1.33, Quality Assurance Program Requirements (Operation), Revision 2, Appendix A, February 1978. Section 7 of Appendix A includes procedures for the control of radioactivity. Procedure EN-RP-121, Radioactive Material Control, Revision 3, Section 5.7[1] states, No item shall be given an unconditional release if any detectable licensed by-product material is known or suspected to be on or in the subject item. Contrary to this requirement, on December 13, 2006, the licensee discovered a contaminated nylon lifting sling outside of a remote radioactive material storage area. When measured by direct frisk, the contamination level was found to be approximately 8000 disintegrations per minute. The finding was determined to be of very low safety significance because it was not associated with ALARA planning or work controls, there was no overexposure or a substantial potential for an overexposure, and the ability to assess dose was not compromised. This issue was placed into the corrective action program as Condition Report C-2006-02056 |
| Site: | Arkansas Nuclear |
|---|---|
| Report | IR 05000313/2008007 Section 4OA7 |
| Date counted | Sep 30, 2008 (2008Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Licensee-identified |
| Inspection Procedure: | |
| Inspectors (proximate) | L Ricketson C Graves D Stearns G Werner L Carson J Razo C Conley |
| INPO aspect | |
| ' | |
Finding - Arkansas Nuclear - IR 05000313/2008007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Arkansas Nuclear) @ 2008Q3
Self-Identified List (Arkansas Nuclear)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||