05000313/FIN-2008003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Adequately Monitor the Performance of the Unit 2 Service Water Intake Structure Roof Drains |
Description | The inspectors identified a noncited violation of 10 CFR 50.65 (a)(2) for the licensees failure to demonstrate that Unit 2 service water intake structure roof drains performance was being effectively controlled through preventive maintenance. Specifically, the licensee has never tested or checked the drains for blockages. The failure (or blockage) of the drains could result in channeling water to the service water pump motors during design basis rain events. The licensee entered this issue in their corrective action program as Condition Report ANO-2-2008-1302. The finding was more than minor because it was similar to nonminor Maintenance Rule Example 7.b in NRC Manual Chapter 0612, Appendix E, Examples of Minor Issues, in that the problem could involve degraded equipment performance. This finding had very low safety significance because the failure to properly categorize failures in accordance with the Maintenance Rule Program did not create, in itself, additional operability or functionality concerns. The inspectors determined that the finding did not have a crosscutting aspect because the opportunity to identify that performance monitoring was inadequate had not occurred recently and therefore was not indicative of current licensee performanc |
Site: | Arkansas Nuclear |
---|---|
Report | IR 05000313/2008003 Section 1R12 |
Date counted | Jun 30, 2008 (2008Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | L Ricketson P Elkmann G George S Graves A Sanchez W Walker W Sifre J Josey S Alferink C Young G Apger S Makor B Rice |
INPO aspect | |
' | |
Finding - Arkansas Nuclear - IR 05000313/2008003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Arkansas Nuclear) @ 2008Q2
Self-Identified List (Arkansas Nuclear)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||