05000282/FIN-2009002-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Follow Procedures During Performance of Operability Evaluations |
Description | The inspectors identified a finding of very low safety significance and a Non-Cited Violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure to adequately implement Procedure FP-OP OL-01, Operability Determination, to assess the capability of the 122 Control Room Chilled Water Pump to meet its mission time following the discovery of increased pump vibrations. Corrective actions for this issue included revising the operability recommendation and repairing the degraded pump. This finding was more than minor because, if left uncorrected, failure to adequately implement the operability procedure could result in safety-related components been incorrectly declared operable rather than inoperable or operable, but non-conforming (a more significant safety concern). This finding was of very low safety significance because the finding did not represent an actual loss of safety function of a single train for longer than its Technical Specification allowed outage time. The inspectors concluded that this finding was cross-cutting in the Human Performance, Decision Making area because the licensee failed to validate the underlying assumptions made when determining the continued operability of a safety-related component (H.1(b)). (Section 1R15.1 |
Site: | Prairie Island |
---|---|
Report | IR 05000282/2009002 Section 1R15 |
Date counted | Mar 31, 2009 (2009Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | D Betancourt J Giessner K Stoedter N Feliz P Zurawski |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Prairie Island - IR 05000282/2009002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Prairie Island) @ 2009Q1