| Title | Failure to identify a non-conservative error in the quarterly TS surveillance for the Unit 1 A battery |
| Description | The inspectors identified a Green NCV of 10 CFR 50, Appendix B, Criterion XVI, Corrective Action for failure to identify that a non-conservative error had been introduced into the Unit 1 A main station battery quarterly technical specification surveillance procedure (CR366388). The licensee modified the procedure to eliminate the non-conservative error. The inspectors determined the failure to identify a non-conservative error which was introduced into the TS quarterly surveillance procedure following the replacement of individual battery cells, was a condition adverse to quality and a performance deficiency which was reasonably within the licensees ability to foresee and correct, and should have been prevented. The finding was more than minor because if left uncorrected the non-conservative error in 1-EPT-0103-01 would have the potential to lead to a more significant safety concern. Specifically, this is because the error was large enough to mask cell degradation and an inoperable cell. The finding was associated with the equipment performance attribute of the reactor safety mitigating systems cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of the safety related 125 VDC station batteries that provide class 1Ebackup power to risk significant components needed to prevent undesirable consequences during a loss of offsite power event. The finding was evaluated using MC-0609, Attachment 4, Phase 1 - Initial Screening and Characterization of Findings, and determined to be of very low safety significance (Green) because operability of the Unit 1 A battery was not lost and the error was removed prior to the next quarterly surveillance. This finding had a cross cutting aspect in the area of problem identification and resolution because the licensee did not evaluate and communicate relevant external OE, including vendor recommendations, to affected internal stakeholders in a timely manner P.2(a). Specifically, the caveat to have cells on a float charge for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> was not fully evaluated when the battery cells were replaced. |
| Site: | Surry |
|---|---|
| Report | IR 05000280/2010002 Section 1R19 |
| Date counted | Mar 31, 2010 (2010Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.19 |
| Inspectors (proximate) | W Lewis C Smith J Nadel C Welch G Mccoy R Fanner J Hamman R Patterson T Lighty A Sengupta |
| CCA | P.5, Operating Experience |
| INPO aspect | CL.1 |
| ' | |
Finding - Surry - IR 05000280/2010002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Surry) @ 2010Q1
Self-Identified List (Surry)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||