05000272/FIN-2012003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Correct Repeat Failures in SAFETY-RELATED Solenoid Valves in a Timely Manner |
Description | A self-revealing NCV of 10 Code of Federal Regulation (CFR) Part 50, Appendix B, Criterion XVI, Corrective Action, was identified because PSEG did not correct a condition adverse to quality. Specifically, repeat failures of solenoid operated valves (SOVs) with voltage applied greater than design voltage was not been corrected in a timely manner and caused a failure of the 11 control area chiller (CAC). The performance deficiency was determined to be more than minor because it was associated with the equipment performance attribute of the Mitigating Systems cornerstone and affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Using IMC 0609, Attachment 4, Initial Screening and Characterization of Findings, the inspectors determined that a single train of a safety-related system was unavailable for eight hours, less than the TS allowed outage time. Therefore, the issue was of very low safety significance (Green) because it did not result in a loss of system safety function, loss of a single train for greater than TS allowed outage time, or potentially risk-significant due to a fire, flooding, or severe weather initiating event. Immediate corrective actions taken included replacement of the failed SOV, and compensatory measures include periodic temperature monitoring of similar energized SOVs. This finding has a cross-cutting aspect in the area of problem identification and resolution, corrective action program, because PSEG did not take appropriate corrective actions to address a safety issue in a timely manner, commensurate with the safety significance and complexity. Specifically, the premature failure of SOVs, due to a higher than design voltage that created higher than design heat in the coil and insulation, was a known issue that was not corrected in a timely manner |
Site: | Salem |
---|---|
Report | IR 05000272/2012003 Section 1R12 |
Date counted | Jun 30, 2012 (2012Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | D Schroeder R Nimitz A Burritt P Mckenna |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |
Finding - Salem - IR 05000272/2012003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Salem) @ 2012Q2
Self-Identified List (Salem)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||