05000270/LER-2015-001, Regarding Valid Emergency Feedwater System Actuation Caused by a Main Feedwater System Block Valve Malfunction

From kanterella
(Redirected from 05000270/LER-2015-001)
Jump to navigation Jump to search
Regarding Valid Emergency Feedwater System Actuation Caused by a Main Feedwater System Block Valve Malfunction
ML15275A088
Person / Time
Site: Oconee 
Issue date: 09/25/2015
From: Batson S
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ONS-2015-102 LER 15-001-00
Download: ML15275A088 (6)


LER-2015-001, Regarding Valid Emergency Feedwater System Actuation Caused by a Main Feedwater System Block Valve Malfunction
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2702015001R00 - NRC Website

text

LII~~%~~Vice President ENEGY°Oconee Nuclear Station Duke Energy ONOIVP I 7800 Rochester Hwy Seneca, SC 29672 o: 864.873.3274

  • . 864.873.4208 Scott.Batson~duke-energy.com ONS-201 5-102 10 CER 50.73 September 25, 2015 Attn: Document Control Desk U. S. Nuclear Regulatory Commission 11555 Rockville Pike Rockville, MD 20852-2746 Subject: Duke Energy Carolinas, LLC (Duke Energy)

Oconee Nuclear Station Unit 2 Docket No. 50-270 Licensee Event Report 270/2015-001, Revision 0 Nuclear Condition Report No.: 01939072 Enclosed is Licensee Event Report (LER) 270/2015-001, Revision 0, for Oconee Nuclear Station (ONS), Unit 2, describing an event in which the unit experienced a valid Emergency Feedwater Actuation caused by a Main Feedwater System Block Valve malfunction.

This report is being submitted in accordance with 10 CFR 50.73(a)(2)(iv)(A),

"System Actuation." There are no regulatory commitments contained in this LER.

If you have any questions regarding this this report, please contact Stephen C. Newman, ONS Regulatory Affairs Group Lead Engineer, at (864) 873-4388.

Sincerely, Scott L. Batson Vice President Oconee Nuclear Site Enclosure

NRC Document Control Desk September 25, 2015 Page 2 cc:

Mr. Leonard D. Wert Jr.

Administrator, Region II (Acting)

U.S. Nuclear Regulatory Commission Marquis One Tower 245 Peachtree Center Ave., NE, Suite 1200 Atlanta, GA 30303-1257 Mr. James R. Hall, Senior Project Manager (by electronic mail only)

U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation 11555 Rockville Pike Mailstop: O-8G9A Rockville, MD 20852 Jeffrey A. Whited, Project Manager (by electronic mail only)

U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation 11555 Rockville Pike Mailstop: O-8B1A Rockville, MD 20852 Mr. Eddy Crowe NRC Senior Resident Inspector Oconee Nuclear Station INPO (Word File via E-mail)

MOP ~Ab~A ~OCA Mfl ~fl4fl~

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 01/3112017

  • 02-2014)
  • ,,,'*,*,,Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.

iv

  • AReported lessons learned are incorporated into the licensing process and fed back to industry.

s=Send comments regarding burden estimate to the FOIA, Privacy and Information Collections

°"*-1*-* ICEN EE VENTREP RT (ER)

Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by LIE SEE E TR P R L 1,

intemnet e-mail to Infocollects.Resource@nrc.gov, and to the Desk Officer, Office of Information and (See Page 2 for required number of Regulatory Affairs, NE09-10202, (3150-0104), Office of Management and Budget, Washington, DC dgt/hrtrsfor each block) 20503. If a means used to impose an information collection does not display a currently valid 0MB digis/caracerscontrol number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

13. PAGE Oconee Nuclear Station, Unit 205 027 1O 4.. TITLE Valid Emergency Feedwater System Actuation Caused by a Main Feedwater System Block Valve Malfunction.
5. EVENT DATE
6. LER NUMBER I
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAYBYEARO.

MONTH DAY YEAR 07 27 2015 2015 -

001

- 00I 09 25 2015 F~UYAEDCENME
9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply)

LI 20.2201(b)

LI 20.2203(a)(3)(i)

LI 50.73(a)(2)(i)(C)

LI 50.73(a)(2)(vii)

LI 20.2201(d)

LI 20.2203(a)(3)(ii)

LI 50.73(a)(2)(ii)(A)

LI 50.73(a)(2)(viii)(A)

LI 20.2203(a)(1)

LI 20.2203(a)(4)

LI 50.73(a)(2)(ii)(B)

LI 50.73(a)(2)(viii)(B)

L 20.2203(a)(2)(i)

LI 50.36(c)(1)(i)(A)

LI 50.73(a)(2)(iii)

LI 50.73(a)(2)(ix)(A)

10. POWER LEVEL LI 20.2203(a)(2)(ii)

LI 50.36(c)(1)(ii)(A)

[] 50.73(a)(2)(iv)(A)

LI 50.73(a)(2)(x)

LI 20.2203(a)(2)(iii)

LI 50.36(c)(2)

LI 50.73(a)(2)(v)(A)

LI 73.71(a)(4)

LI 20.2203(a)(2)(iv)

LI 50.46(a)(3)(ii)

LI 50.73(a)(2)(v)(B)

LI 73.71(a)(5) 16.6 LI 20.2203(a)(2)(v)

LI 50.73(a)(2)(i)(A)

LI 50.73(a)(2)(v)(C)

LI OTHER L

20.2203(a)(2)(vi)

LI 50.73(a)(2)(i)(B)

LI 50.73(a)(2)(v)(D) specify in Abstract below or in

12. LICENSEE CONTACT FOR THIS LER LICENSEE CONTACT TLPOENME IcueAe oeFATRR T ICE I
14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED MONTH DAY iYEAR

[]YES (If ye*, complete 15. EXPECTED SUBMISSION DATE)

[]NO SUBMISSION LIJDATE L

L ABSTRACT (Limit to 1400 spaces, iLe., approximately 15 single-spaced typewritten lines)

Upon return from a Unit 2 forced outage, at 0957 hours0.0111 days <br />0.266 hours <br />0.00158 weeks <br />3.641385e-4 months <br /> on July 27, 2015, at approximately 16.6% power and increasing, there was an unexpected water level reduction in the 2B Steam Generator due to a malfunctioning main feedwater block valve that failed to open on demand. The level reduction resulted in a valid Emergency Feedwater System actuation and subsequently, reactor power was decreased so that feedwater/Steam Generator level could be controlled by only the startup control valve.

An investigation determined that 2FDW-40 failed to open due to the Automatic Feedwater Isolation System (AFIS) testing links not being fully closed and engaged. The root cause was due to a procedure use and adherence error by personnel performing the last AFIS Circuitry Test in the Fall of 2013.

This event had a negligible impact on nuclear safety. A planned corrective action is to revise applicable procedures for each Unit. This event is reportable under 10 CFR 50.73(a)(2)(iv)(A) due to the automatic actuation of the Unit's Emergency Feedwater System.

NRC FORM 366 (02-2014)

qJRC =

EVALUATION:

BACKGROUND The Main Feedwater System (FDW) [ElIS: S J] receives water from the Condensate System [EllS: SD], increases the water's pressure using the turbine driven feedwater pumps [EllS: P], increases the water's temperature using the high pressure feedwater heaters (heaters B and A) [EIlS: HTR], and controls the rate at which water is supplied to the steam generators (SGs) [EIlS: SG] using the startup FDW control valves [EIlS: FCV] and the main FDW control valves. The FDW pumps and control valves are controlled by the Integrated Control System (ICS)

[EllS: JAI, The startup and main feedwater control valves 2FDW-32, 35, 41, 44 are pneumatically operated valves that are designed to fail as is on loss of instrument air [EllS: LD]. These valves, on the affected header, are designed to automatically close following a Main Steam Line Break (MSLB).

Steam generator 2B main feedwater control valve 2FDW-41 controls the flow of feedwater to steam generator 2B between approximately 15% and 100% reactor power. Whether 2FDW-41 is in AUTO or manual control, an Automatic Feedwater Isolation System (AFIS) circuitry actuation due to a MSLB on the 2B header will automatically close 2FDW-41. The AFIS circuitry actuates various components including the main and startup feedwater control valves in order to mitigate a MSLB with or without a Loss of Offsite Power (LOOP). Technical Specification 3.7.3 requires the flow control valves to be operable. The flow control valves fail as-is and require Instrument Air (IA) to close.

Steam generator 2B startup feedwater control valve 2FDW-44 controls the flow of feedwater to steam generator 2B between approximately 0 and 15 percent reactor power. *Whether 2FDW-44 is in AUTO or manual control, an AFIS circuitry actuation on the 2B header will automatically close 2FDW-44. The valve's control signal normally controls steam generator level to 25 inches as measured on the startup range level transmitters.

Steam generator 2B main block valve 2FDW-40 is a motor-operated valve that isolates the feedwater supply to the main feedwater control valve, 2FDW-41. Manual controls for 2FDW-40 are located in* the control room. For normal operation, an AUTO-OPEN-CLOSE switch is provided and 2FDW-40 is opened by turning the switch to OPEN. When the switch is set to AUTO, 2FDW-40 is opened automatically when the feedwater demand signal to startup feedwater control valve 2FDW-44 is 90% or more. Conversely, 2FDW-40 is automatically closed if the feedwater demand signal to startup feedwater control valve 2FDW-44 is 50% or less. Also, when the switch is set to AUTO, 2FDW-40 is automatically closed if the AFIS circuitry actuates due to a MSLB on the 2B header. When the feedwater demand signal to 2FDW-44 reaches 98% increasing it receives a signal to close and the main feedwater control valve 2FDW-41 receives a signal to open to begin controlling Feedwater flow to the 2B Steam Generator.

EVENT DESCRIPTION

Upon return from a forced outage, at 0957 hours0.0111 days <br />0.266 hours <br />0.00158 weeks <br />3.641385e-4 months <br /> on July 27, 2015, Unit 2 reactor power was at approximately 16.6% power and increasing when the feedwater valve demand for the 2B main feedwater header reached the point in which the 2B startup control valve (2FDW-44) is driven to close and the 2B main control valve (2FDW-41) is driven to open to transition to the condition in which a significant portion of the feedwater flow for the 2B Steam Generator (SG) is through the main control valve. Specifically, feedwater demand to startup feedwater control valve 2FDWV-44 reached 98% increasing and it went closed. Main feedwater control valve 2FDW-41 went open to begin controlling Feedwater to the 2B Steam Generator, however, main feedwater block valve 2FDW-40 had not

received an open signal since the AFIS testing link, through which the open signal passes, was not closed.

Consequently, there was insufficient feedwater flow to the 2B Steam Generator and the level dropped from setpoint (25 inches) to a level that feeds into the dryout protection circuit (21 inches) in less than one minute. This resulted in an emergency feedwater system actuation and subsequently, reactor power was decreased so that feedwater/SG level could be controlled by only the startup control valve.

Units 1 and 3, were operating in MODE 1 at approximately 100% power and were unaffected by the event. No structures, systems or components (SSCs) were out of service such that they contributed to this event.

On July 27, 2015, this event was reported as an 8-hour notification (EN 51268) pursuant to 10 CFR 50.72(b)(3)(iv)(A) due to the valid actuation of the Emergency Feedwater System [EllS: BA]. This event is reportable under 10 CFR 50.73(a)(2)(iv)(A) due to the automatic actuation of the Unit's Emergency Feedwater System.

CAUSAL FACTORS An investigation determined that 2FDW-40 failed to open due to the Automatic Feedwater Isolation System (AFIS) testing links not being engaged. The subject links are Weidm011er links that must be "snapped" closed to be fully engaged. The root cause was due to a procedure use and adherence error by personnel performing the last AFIS Circuitry Test in the Fall of 2013. Noteworthy is that during reactor restart following this AFIS test, 2FDW-40 successfully operated as expected. Additionally, when restarting from an October 2014 forced unit outage to repair control rod drive head fans, 2FDW-40 again operated successfully.

CORRECTIVE ACTIONS

Immediate:

A Failure Investigation Process (FIP) Team was assembled to assess the event including its cause(s), necessary corrective actions, and pastlfuture unit operational impacts.

Subsequent:

1. The AFIS links were verified closed and the unit restarted without incident.
2.

The Unit 1 and 3 AFIS testing links were verified to be in the fully-closed position.

Planned:

For each Unit, applicable procedures will be revised to include additional detail on ensuring that the links are fully closed.

SAFETY ANALYSIS

The EFW system responded as expected to an actual SG dryout protection signal on low SG level. Initiation of EFW on low SG level is not credited for any design basis accidents or transients. In addition, the AFIS was effectively in its' fail-safe position and there were no other complications or equipment failures. This event had a negligible impact on nuclear safety.

ADDITIONAL IN FORMATION Energy Industry Identification System (EIlS) codes are identified in the text as [XX]. This event did not include a Safety System Functional Failure. There were no releases of radioactive materials, radiation exposures in excess of limits or personnel injuries associated with this event.

SIMILAR EVENTS

A search of the Oconee Corrective Action Program (CAP) database was conducted for the preceding five (5) year period. Similarly, a review of industry Operating Experience (OE) databases was conducted using keyword searches, i.e., "Weid moiler," "emergency feedwater actuation," "AFIS," "test links," "steam generator dryout," etc., to determine other similarly-reported events.

Although there have been two (2) instances in the past 2 years where Unit 3 was manually tripped due to feedwater oscillations, no prior LERs or other industry-related OE could be found in the previous 5-year period that compared similarly to this event.