| Title | Modifications to Fire Doors did not Receive Engineering Equivalency Evaluations |
| Description | An NRC-identified Green non-cited violation (NCV) of Oconee Nuclear Station Units 1, 2, and 3 Renewed Facility Operating License Condition 3.D and NFPA 805 was identified for the licensees modification of five fire doors from their tested configurations without performing engineering equivalency evaluations. The licensee entered this issue into the corrective action program as Problem Investigation Program O-13-06900, and declared the door nonfunctional and implemented fire watches in accordance with Selected License Commitment 16.9.5 Fire Barriers. The licensees modification of fire doors from their tested configuration without performing engineering equivalency evaluations was a performance deficiency. The performance deficiency was more than minor because it was associated with the Mitigating Systems cornerstone attribute of protection against external events (i.e., fire) and it adversely affected the cornerstone objective in that the modifications performed on the five fire doors adversely affected the capability of the doors to provide the required level of fire resistance. The finding was determined to be of very low safety significance (Green) because the fire doors would have either provided a two-hour or greater fire endurance rating, or would have provided a minimum of 20 minutes fire endurance protection; and the fixed fire ignition sources, and combustible or flammable materials, were positioned such that the degraded fire doors would not have been subjected to direct flame impingement. A cross-cutting aspect was not assigned because the performance deficiency did not reflect current licensee performance. |
| Site: | Oconee |
|---|---|
| Report | IR 05000269/2013007 Section 1R05 |
| Date counted | Sep 30, 2013 (2013Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | D Terri Ward J Dymek J Eargle J Montgomery M King M Thomas P Braxton R Rodriguez S Sanchez |
| Violation of: | License Condition - Fire Protection License Condition |
| INPO aspect | |
| ' | |
Finding - Oconee - IR 05000269/2013007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Oconee) @ 2013Q3
Self-Identified List (Oconee)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||