05000263/FIN-2011005-04
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Properly Block and Brace a Radioactive Package for Transport |
| Description | The inspectors reviewed a self-revealed finding of very low safety significance and an associated NCV of 10 CFR 71.5. Specifically, the licensee failed to appropriately block and brace a radioactively contaminated condensate demineralizer vessel within a transport package, such that, the package contents would not compromise and penetrate the transport package. The issue has been entered into the licensees corrective action program as CR [condition report] 01294652. Corrective actions were implemented to address supervisions responsibilities during shipment preparation regarding appropriate blocking and bracing of package contents. The finding was more than minor because the performance deficiency could be reasonably viewed as a precursor to a significant event, in that, the penetration of the transportation package by its contents could lead to the inadvertent spread of radioactive contamination in the public domain. Using IMC 0609, Attachment D, for the Public Radiation Safety SDP, the inspectors determined the finding to be of very low safety significance. The inspectors also determined that this finding had a cross-cutting aspect in the area of problem identification and resolution (operating experience) |
| Site: | Monticello |
|---|---|
| Report | IR 05000263/2011005 Section 2RS8 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | NCV: Green |
| cornerstone | Pr Safety |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71124.08 |
| Inspectors (proximate) | M Munir C Zoia K Riemer M Phalen K Stoedter S Thomas R Walton P Voss J Beavers S Bell |
| CCA | P.5, Operating Experience |
| INPO aspect | CL.1 |
| Finding closed by | |
| IR 05000263/2011005 (1 February 2012) | |
| ' | |
Finding - Monticello - IR 05000263/2011005 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Monticello) @ 2011Q4
Self-Identified List (Monticello)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||