05000261/FIN-2013007-05
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Have Appropriate Procedure to Verify Degraded Voltage Relay Circuit Status |
| Description | The team identified a Green non-cited violation of 10 CFR 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the licensees failure to prescribe an adequate procedure that verified DGVR circuit operability following degraded voltage disable switch operation for reactor coolant pump (RCP) starts. This was a performance deficiency. The licensee entered the issue into the corrective action program as Nuclear Condition Report 602516, developed a test procedure, and verified the DGVR operability on both emergency buses. The performance deficiency was more than minor because if left uncorrected, it could become a more significant safety concern. Specifically, by not properly testing the DGVR circuit to ensure continuity following switch manipulation for RCP starts, the circuit could unknowingly become inoperable and non-functional for an entire operating cycle. The finding was determined to be of very low safety significance (Green) because the finding was not a design or qualification deficiency, did not represent a loss of system function, did not represent an actual loss of function of at least a single train for greater than its technical specification (TS) allowed outage time or two separate safety systems out-of-service for greater than its TS allowed outage time, and did not represent an actual loss of function of one or more non-TS trains. No cross-cutting aspect was assigned to this finding because the team determined that the cause of the finding was not indicative of current licensee performance due to the age of the modification that added the degraded voltage disable switches. |
| Site: | Robinson |
|---|---|
| Report | IR 05000261/2013007 Section 1R21 |
| Date counted | Jun 30, 2013 (2013Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | A Alen G Nicely G Ottenberg H Campbell J Bartleman M Riley P Cooper R Nease S Walker |
| Violation of: | 10 CFR 50 Appendix B Criterion V Technical Specification Technical Specification - Procedures |
| INPO aspect | |
| ' | |