| Title | Failure to provide adequate instructions when working on the reactor protection system results in reactor trip |
| Description | A self-revealing non-cited violation (NCV) of 10 CFR 50 Appendix B, Criterion V, Instructions, Procedures, and Drawings, was identified when the licensee started corrective maintenance on the Unit 4 reactor protection system with an inadequate procedure. As a result, a reactor trip occurred when a reactor trip circuit was not placed on bypass as an initial condition needed to safely complete the work. During the event investigation, the licensee determined that neither the work order, nor the pre-job review identified the need to place the affected train of the reactor protection system on the bypass breaker. The finding was determined to be more than minor because it affects the Initiating Events cornerstone attribute of procedure quality and adversely affected the cornerstone objective to limit the likelihood of an event that upsets plant stability by resulting in a reactor trip. The finding was evaluated in accordance with IMC 0609, Attachment 4, and determined to be of very low safety significance (Green) per SDP Phase 1 determination because the finding did not contribute to both the likelihood of a reactor trip and the likelihood that mitigation equipment or functions would not be available. This finding has a cross-cutting aspect in the area of Human Performance, Work Control H.3(b) because the licensee did not appropriately coordinate work activities by incorporating actions to address the need to keep personnel apprised of the operational impact of work and plant conditions that may affect work activities, resulting in a reactor trip. |
| Site: | Turkey Point |
|---|---|
| Report | IR 05000250/2010004 Section 1R12 |
| Date counted | Sep 30, 2010 (2010Q3) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71111.12 |
| Inspectors (proximate) | C Fletcher R Chou R Carrion W Rogers M Barillas S Stewart D Rich |
| CCA | H.5, Work Management |
| INPO aspect | WP.1 |
| ' | |
Finding - Turkey Point - IR 05000250/2010004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Turkey Point) @ 2010Q3
Self-Identified List (Turkey Point)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||