Finding | |
---|---|
Title | Failure to identify and Promptly Correct Degraded 480 Volt Switchgear Room Fire Door |
Description | The inspectors identified a NCV of very low safety significance related to License Condition 2.K., fire protection program, because personnel did not promptly identify and correct a degraded three-hour rated fire door latch mechanism on the west entrance of the 480-Volt switchgear room. Specifically, inspectors identified the fire door in a nonfunctional state on several instances over the course of a month. Entergy personnel replaced the fire door latch mechanism on March 3, 2009. This issue was entered into the corrective action program as six condition reports spanning several weeks and included an extent of condition walkdown of site fire doors. The finding was more than minor because it is associated with the protection against external factors attribute of the Mitigating Systems cornerstone and affected the cornerstone objective of ensuring the reliability of systems that respond to initiating events to prevent undesirable consequences. This fire door, when degraded, impacts the reliability of mitigating systems in the 480-Volt switchgear room that are relied upon during a postulated large fire in the turbine building, and vice versa. This finding was evaluated using Phase 1 of IMC 0609 Appendix F, Fire Protection Significance Determination Process. Since the area in question had a fire watch posted during the time the door was degraded for an unrelated issue, an adequate level of protection was maintained to compensate for the degraded door. As such, according to task 1.3.1, the inspectors determined the finding was Green. The inspectors determined that the finding had a cross-cutting aspect in the area of problem identification and resolution because Entergy personnel did not thoroughly evaluate a degraded fire door latch on several occasions, such that the resolution of the problems addressed the causes. (P.1(c) per IMC 0305 |
Site: | Indian Point |
---|---|
Report | IR 05000247/2009002 Section 1R05 |
Date counted | Mar 31, 2009 (2009Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | C Hott G Malone J Commiskey M Gray |
CCA | P.2, Evaluation |
INPO aspect | PI.2 |
' | |
Finding - Indian Point - IR 05000247/2009002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Indian Point) @ 2009Q1
Self-Identified List (Indian Point)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||