05000237/FIN-2015002-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | |
Description | A finding of very low safety significance (Green), and an associated NCV of TS 5.4.1, Procedures, was self-revealed on May 19, 2015, when the 2/3 EDG was made inoperable to Unit 2 due to the incorrect manipulation of a test switch by operations personnel during a TS required surveillance test. Specifically, while the licensee performed procedure DIS 1500-05, Division I and II Low-Pressure Coolant Injection ECCS Initiation Circuitry Logic System Functional Test, Step 106 ofChecklist B, operations personnel incorrectly opened test switch TS-159SD2/3 at motor control center 23-1 removing the under-voltage trip associated with the feed breaker for the Division I safety-related 4.16 kV engineered safeguards bus, causing the 2/3 EDG to be inoperable to Unit 2. The licensees failure to properly implement steps in the procedure was a performance deficiency that was determined to be more than minor, and thus a finding, because it was associated with the Mitigating Systems Cornerstone Attribute of Configuration Control, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding was determined to be of very- low safety significance (Green), because each of the questions provided in IMC 0609, Appendix A, Exhibit 2, Mitigating Systems Screening Questions, were answered No. The finding has a cross-cutting aspect in the area of Human Performance, Field Presence, for failing to ensure senior managers applied the appropriate oversight of infrequently performed and first time work activities. Specifically, the licensee field supervisor or another senior operations manager was not present for the switching activities, which led to the configuration control error. In this instance, the surveillance test is infrequently performed (every 24 months), and the activity, which included using a maintenance procedure vice an operating procedure, was a first time evolution for both equipment perators involved. [H.2] |
Site: | Dresden |
---|---|
Report | IR 05000237/2015002 Section 1R22 |
Date counted | Jun 30, 2015 (2015Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71111.22 |
Inspectors (proximate) | A Boland D Lords G Roach M Bielby M Learn M Porfirio M Ziolkowski T Go |
Violation of: | Technical Specification - Procedures Technical Specification |
CCA | H.2, Field Presence |
INPO aspect | LA.2 |
' | |
Finding - Dresden - IR 05000237/2015002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Dresden) @ 2015Q2
Self-Identified List (Dresden)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||