05000219/FIN-2015003-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Non-Conservative Temperature Input in the Electromatic Relief Valve Voltage Drop Calculation |
Description | The inspectors identified an NCV of 10 Code of Federal Regulations (CFR) 50, Appendix B, Criterion III, Design Control, in that Exelons measures for verifying the adequacy of design of the electromatic relief valve (EMRV) voltage drop calculation were inadequate. Specifically, non-conservative temperature inputs were used for the safety related EMRV direct current voltage drop calculation, which reduced the margin of available voltage to the EMRV solenoids. Exelon entered this issue into the corrective action program for resolution as issue report 2522756, and corrective actions included revising the calculation to include the correct temperature values and conduct an extent of condition of other voltage drop calculations that could have similar temperature values. The performance deficiency is more than minor because it is associated with the design control attribute of the Mitigating Systems cornerstone and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, lower voltage to the EMRV solenoid at higher temperatures could affect the reliability and capability of the EMRV to perform its design function. In addition, the performance deficiency is determined to be more than minor because it is similar to example 3.j of NRC IMC 0612, Appendix E, Example of Minor Issues, in that as a result of the calculation errors and the magnitude of the decrease of margin, there was a reasonable doubt on the operability of the component. The inspectors evaluated the finding using 0609.04, Initial Characterization of Findings, and IMC 0609, Appendix A, Exhibit 2, Mitigating System Screening Questions. The inspectors determined that this finding is a deficiency that affected the design or qualification of a mitigating structure, system or component (SSC), where the SSC maintained its operability or functionality. Therefore, inspectors determined the finding to be of very low safety significance (Green). The finding is not assigned a cross-cutting aspect because it is not reflective of current performance. Specifically, the last time Exelon had an opportunity to evaluate this issue was in 2010 when Exelon identified that the EMRV solenoid voltage had low margin. |
Site: | Oyster Creek |
---|---|
Report | IR 05000219/2015003 Section 1R15 |
Date counted | Sep 30, 2015 (2015Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | A Patel B Dionne B Lin E Andrews S Kennedy |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
INPO aspect | |
' | |
Finding - Oyster Creek - IR 05000219/2015003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Oyster Creek) @ 2015Q3
Self-Identified List (Oyster Creek)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||