ENS 49634
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
23:03 Dec 14, 2013 | |
Title | Unanalyzed Condition Affecting Unit 1 Emergency Diesel Generator |
Event Description | At 1503 PST on December 14, 2013, Pacific Gas and Electric Company identified that, if atmospheric conditions were to develop that had both sustained high winds exceeding 60 miles per hour from the NW to NNE direction, and ambient air temperature exceeding 97 degrees Fahrenheit, the combination of these conditions could result in inadequate heat removal to support continuous operation of the Unit 1 emergency diesel generators. Upon identification of this condition, shift orders were issued requiring implementation of existing procedural guidance to open plant doors to allow additional air flow that would provide adequate emergency diesel generator cooling to support continuous operation of the U1 emergency diesel generators.
This report addresses a condition as described in 10 CFR 50.72(b)(3)(ii)(B). The NRC Resident Inspector has been notified of this condition. This condition was discovered during a license basis verification review. |
Where | |
---|---|
Diablo Canyon California (NRC Region 4) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+-3.52 h-0.147 days <br />-0.021 weeks <br />-0.00482 months <br />) | |
Opened: | Michael Quitter 19:32 Dec 14, 2013 |
NRC Officer: | Daniel Mills |
Last Updated: | Dec 14, 2013 |
49634 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 544172019-11-30T19:00:00030 November 2019 19:00:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Both Trains of Containment Spray Removed from Service ENS 522602016-09-21T03:47:00021 September 2016 03:47:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Steam Line Pipe Whip Restraint Coupling Sleeve Found Not Engaged ENS 503342014-08-01T00:29:0001 August 2014 00:29:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Unanalyzed Condition ENS 498792014-03-06T17:06:0006 March 2014 17:06:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Regarding Potential Tornado Missile Damage to Emergency Diesel Exhaust Plenum ENS 496632013-12-19T15:52:00019 December 2013 15:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Two of Three Emergencey Diesel Generators Inoperable at the Same Time ENS 496342013-12-14T23:03:00014 December 2013 23:03:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Affecting Unit 1 Emergency Diesel Generator ENS 491482013-06-26T04:58:00026 June 2013 04:58:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Plant Shutdown Required Due to Rhr System Socket Weld Leak ENS 491472013-06-24T23:15:00024 June 2013 23:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Diesel Generators Unavailable for Auto-Start ENS 487262013-02-06T23:24:0006 February 2013 23:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Room Ventilation ENS 483952012-10-04T01:15:0004 October 2012 01:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Fire Protection Deficiencies ENS 482462012-08-29T00:00:00029 August 2012 00:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mitigating Actions Implemented for Inoperable Control Room Envelope ENS 475642011-12-31T10:00:00031 December 2011 10:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Barrier Rating of Vital Swtichgear Walls May Not Meet Standards ENS 474142011-11-03T22:50:0003 November 2011 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Control Room Ventilation Single Point Vulnerability ENS 472582011-09-13T00:45:00013 September 2011 00:45:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Control Room Envelope Declared Inoperable ENS 472232011-08-30T00:24:00030 August 2011 00:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Maintenance Inadvertently Renders Control Room Ventilation System Inoperable ENS 465312011-01-10T21:21:00010 January 2011 21:21:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Both Trains of Auxiliary Building Ventilation Became Inoperable ENS 457542010-03-10T03:16:00010 March 2010 03:16:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Loss of 1E Pumps Due to Degraded Voltage During Postulated Accidents ENS 454612009-10-23T15:00:00023 October 2009 15:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Post Loca Recirculation Valve Position Interlocks ENS 449272009-03-22T20:34:00022 March 2009 20:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unit 1 Steam Generator Found in an Unanalyzed Condition Related to Gaps on Seismic Washer Plates 2019-11-30T19:00:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_49634&oldid=84955"