Title | Unanalyzed Condition - Missing Backflow Preventer |
Event Description | On 4/12/2013 at 1010 EDT, it was determined that a floor drain line between the Turbine Building and Intermediate Building did not have a backflow preventer as expected. Backflow protection is provided to prevent the possible spread of a fire via the drain system. The Turbine Building and the Intermediate Building are considered two different fire areas within the scope of the fire protection program. The discovery of this condition is being reported as an unanalyzed condition as defined by 10CFR50.72(b)(3)(ii)(B).
In accordance with the Technical Requirements Manual, an hourly fire watch inspection and fire detector operability verification have been established until an equivalent level of protection is provided or until permanent corrective actions can be implemented. The NRC Resident Inspector has been notified. |
Where | |
---|---|
Ginna New York (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+0.58 h0.0242 days <br />0.00345 weeks <br />7.94484e-4 months <br />) | |
Opened: | Dale Bisaillon 14:45 Apr 12, 2013 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Apr 12, 2013 |
48918 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 499142014-03-13T20:30:00013 March 2014 20:30:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 493742013-09-20T20:00:00020 September 2013 20:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Design Basis Flooding Issues Related to Battery Room Wall Penetrations and Cable Vault Floor Drains ENS 489182013-04-12T14:10:00012 April 2013 14:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Missing Backflow Preventer ENS 483332012-09-21T18:00:00021 September 2012 18:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Identified in Appendix R Fire Scenario ENS 471672011-08-18T14:00:00018 August 2011 14:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition That Could Potentially Impact Both Trains of 480V Safeguards Buses ENS 467352011-04-06T19:30:0006 April 2011 19:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Degraded Fire Barrier ENS 428312006-09-07T02:00:0007 September 2006 02:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Historical Unanalyzed Condition Identified ENS 425882006-05-18T19:00:00018 May 2006 19:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unevaluated Failure of Charging Pump in Fire Scenario ENS 408932004-07-22T13:42:00022 July 2004 13:42:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Gap Discovered in Control Room Envelope ENS 401842003-09-19T22:00:00019 September 2003 22:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition 2014-03-13T20:30:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_48918&oldid=85640"