LER-2002-005, Engineered Safety Features Actuation includin Emergency Diesel Generator Start
Wolf Creek Generating Station
Event date: 09-09-2002
Report date: 10-24-2002
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation
4822002005R00 - NRC Website

Background:

Power to Engineered Safety Features (ESF — System SA) [EIIS Code: JE] buses NB01 and NB02 (NB) [EIIS Code: EB] is normally provided from off-site sources via dedicated ESF transformers and normal feeder breakers. Each ESF bus also has an emergency power source available from an onsite Emergency Diesel Generator (EDG) [EIIS Code: EK], which is designed to start automatically on an undervoltage signal and load onto the bus. When a diesel generator successfully loads onto an affected ESF bus, the Load Shedder Emergency Load Sequencer,(LSELS — System NF) [EIIS Code: EK] for that bus will automatically start predetermined loads at programmed time intervals.

Plant Conditions Prior to the Event:

MODE —1 Power —100 Percent Normal Operating Temperature and Pressure

Event Description:

On September 9, 2002, at 3:59 p.m., the Control Room received an alarm indicating the existence of a degraded voltage condition on bus NB01. Bus voltage was immediately verified to be normal. Approximately 90 seconds later, when the degraded voltage alarm had not cleared, the normal feeder breaker to NB01 opened, resulting in loss of power to the bus. The "A" EDG started and loaded onto the bus as expected.

The LSELS started loads as required on the shutdown sequencer, including the "A" Centrifugal Charging Pump (CCP) [EIIS Code: BQ], and the "A" Motor Driven Auxiliary Feedwater Pump [EllS Code: BA]. Also, the undervoltage condition on NB01 resulted in an automatic start of the Turbine Driven Auxiliary Feedwater Pump (TDAFWP) [EIIS Code: BA], as designed.

After the NB01 bus voltage was returned to normal by the EDG, the degraded voltage alarm remained actuated, indicating a circuit failure. All safety related equipment performed as designed. The ESF Systems performed as required. Control Room Operators immediately began a power reduction to compensate for the reactivity addition caused by the addition of auxiliary feedwater to the Steam Generators. The power reduction was completed at 5:03 p.m., and at 5:10 p.m., the TDAFWP was secured. Other than one unrelated slave relay surveillance test in progress on Train 'A' Steam Line Isolation, there were no structures, systems, or components (SSCs) out of service that contributed to this event.

Basis for Reportability:

The actuation of ESF Systems described in this event is reportable per 10 CFR 50.73(a)(2)(iv)(A), which states, in part, that the Licensee shall report "Any event or condition that resulted in manual or automatic actuation of any of the systems listed in paragraph (a)(2)(iv)(B) of this section." The systems involved are Emergency Diesel Generators and Auxiliary Feedwater.

Root Cause:

The failure that initiated the degraded voltage alarm and subsequent opening of the normal feeder breaker to bus NB01 has been identified as occurring in an integrated circuit (IC) on a relay driver board in the NF039A cabinet. Specifically, a logic gate between pins 4, 6 and 7 in the "Ur IC on relay driver board #17 in the NF039A cabinet experienced a hardware failure to a logic HI condition. This caused LSELS output relays 1148 and 1149 to energize and trip the NB01 feeder breakers.

Corrective Actions:

Troubleshooting activities performed following this event concluded that the failure of the "U1" chip on the relay driver board described in the root cause was the initiator of this event, and was classified as a random failure of an electronic semi-conductor integrated circuit. Following successful testing of a replacement board, it was installed and the system restored to service. LSELS was declared operable at 11:53 p.m. on September 9, 2002.

Safety Significance:

The safety significance of this event is low. This event is bounded by the current licensing basis analysis as reported in Wolf Creek Generating Station (WCGS) Updated Safety Analysis Report (USAR), section 8.3.1, "AC Power Systems", as indicated in Table 8.3.4. All safety related equipment performed as designed and there were no adverse effects on the health and safety of the public.

Previous Events:

Research into the corrective action program database was conducted for keywords "LSELS" and "sequencer", as well as systems NF and SA. No similar failures were found, nor were any other ESF actuations found attributed to these electronic cards. There are sixty (60) cards of this type used at WCGS.

They are all used in the NF and SA systems. Twenty-eight (28) are used in the NF cabinets, and thirty-two (32) are used in the SA cabinets. There have been six (6) failures in seventeen (17) years. The reliability of these boards, over a one-year period, is 99.4%. Three of these failures have occurred in NF039A, two in SA075B and one in the SA075A cabinet. One failure occurred in 1988, one in 1992, one in 1993, one in 2001 and two in 2002. To date, this event has been the only significant incident resulting from a failure of these electronic cards. The other failures have been minor equipment failures and were corrected under the work controls process.