Pages that link to "05000302/LER-1982-017, Forwards LER 82-017/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000302/LER-1982-017, Forwards LER 82-017/03L-0:
Displayed 50 items.
- 05000302/LER-1982-043, Forwards LER 82-043/03L-0 (← links)
- 05000302/LER-1982-042, Forwards LER 82-042/03L-0 (← links)
- 05000302/LER-1982-040, Forwards LER 82-040/03L-0 (← links)
- 05000302/LER-1982-039, Forwards LER 82-039/03L-0 (← links)
- 05000302/LER-1982-038, Forwards LER 82-038/03L-0 (← links)
- 05000302/LER-1982-036, Forwards LER 82-036/03L-0 (← links)
- 05000302/LER-1982-035, Forwards LER 82-035/03L-0 (← links)
- 05000302/LER-1982-020, Forwards LER 82-020/03L-0 (← links)
- 05000302/LER-1982-026, Forwards LER 82-026/03L-0 (← links)
- 05000302/LER-1982-033, Forwards LER 82-033/03L-0 (← links)
- 05000302/LER-1982-016, Forwards LER 82-016/03L-0 (← links)
- 05000302/LER-1982-045, Informs That Special Rept Supposedly Encl in 821001 Submitted LER 82-045 Determined to Be More Useful as Basis of Tech Spec Change Request to Be Submitted at Later Date (← links)
- 05000302/LER-1982-059, Forwards LER 82-059/03L-0 (← links)
- 05000302/LER-1982-057, Forwards LER 82-057/03L-0 (← links)
- 05000302/LER-1982-052, Forwards LER 82-052/03L-0 (← links)
- 05000302/LER-1982-051, Forwards LER 82-051/03L-0 (← links)
- 05000302/LER-1982-049, Forwards LER 82-049/03L-0 (← links)
- 05000302/LER-1982-048, Forwards LER 82-048/03L-0.Detailed Event Analysis Encl (← links)
- 05000302/LER-1982-050, Forwards LER 82-050/01T-0.Detailed Event Analysis Encl (← links)
- 05000302/LER-1982-046, Forwards LER 82-046/03L-0 (← links)
- 05000302/LER-1982-047, Forwards LER 82-047/04T-0 (← links)
- 05000302/LER-1982-073, Forwards LER 82-073/04T-0 (← links)
- 05000302/LER-1982-004, Forwards LER 82-004/01T-0 (← links)
- 05000302/LER-1982-003, Forwards LER 82-003/01T-0 (← links)
- 05000302/LER-1982-069, Forwards LER 82-069/03L-0 (← links)
- 05000302/LER-1982-067, Forwards LER 82-067/03L-0 (← links)
- 05000302/LER-1982-064, Forwards LER 82-064/01T-0 (← links)
- 05000302/LER-1982-076, Forwards LER 82-076/03L-0 (← links)
- 05000302/LER-1982-005, Forwards LER 82-005/03L-0 (← links)
- 05000302/LER-1982-007, Forwards LER 82-007/03L-0 (← links)
- 05000302/LER-1982-044, Forwards LER 82-044/03T-0 (← links)
- 05000302/LER-1982-061-03, /03X-1:on 820929,fan Damper Operator on Industrial Cooler Failed & Reactor Bldg Average Temp Exceeded 130 F Limit of Tech Specs.Caused by Water in Instrument Air Sys Due to Personnel Error.Procedures Reviewed (← links)
- 05000302/LER-1982-033-03, Reactor Bldg Pressure Indicator BS-16-PI Discovered Inoperable.Caused by Instrument Drift.Bailey Transmitters BS-16-PT & BS-17-PT Replaced W/Rosemount Transmitters & Calibr (← links)
- 05000302/LER-1982-076-03, /03L-0:on 821220,feedwater Ultrasonic Flow Indicator FW-313-FI & Emergency Feedwater Train B Discovered Inoperable.Caused by Excessive Heat in Emergency Feedwater Line.Line Cooled.Indicators Will Be Replaced (← links)
- 05000302/LER-1982-013-03, Leak Discovered on Pressure Side of MUV-292 in Heat Affected Area of Weld. Caused by Vibration.Supports/Restraints Added to Makeup Sys. Vibration Eliminated (← links)
- 05000302/LER-1982-002-03, After Removing MUP-1B Pump Casing by MP-126,discovered Pump Casing Was Seismic Anchor.Caused by Failure of Procedure MP-126 to Identify Required Seismic Evaluation.Maint Procedure Revised (← links)
- 05000302/LER-1982-005-03, /03L-0:on 820119,175 & 33-ft Wind Direction & Ambient Temp Monitoring Channels Found Out of Calibr.Caused by Instrument Drift.Instruments Recalibr & Returned to Svc 820126.Meteorological Monitoring Tower Design Under Review (← links)
- 05000302/LER-1982-007-03, /03L-0:on 820123,starting Air Pressure for Emergency Diesel Generator B Too Low for Automatic Start & Air Pressure Low Alarm Did Not Actuate.Caused by EGV-16,air Tank Blowdown Valve Not Fully Closed & Alarm Malfunction (← links)
- 05000302/LER-1982-006-03, /03L-0:on 820125,during Weekly Battery Check, SP-520,on Station Battery 3B,pilot Cell 115 Failed to Meet Acceptance Criteria.Caused by Dissipation of Charge Between Surveillances.Battery Recharged & Returned to Svc (← links)
- 05000302/LER-1982-074-03, /03L-0:on 821116,during Performance of SP-186, Control Complex Charcoal Filters Failed Freon Portion of Surveillance Required by Tech Specs.Caused by Moisture Absorption by Charcoal Filters.Filters Replaced & Tested (← links)
- 05000302/LER-1982-071-03, /03L-0:on 821114,during Mode 1,radiation Monitor RM-A5,control Room Iodine Channel Found Inoperable.Caused by Failure of Rotary Selector Switch.Switch Replaced & Monitor Placed in Svc (← links)
- 05000302/LER-1982-070-03, /03L-0:on 821107,during Mode 1,nuclear Overpower Channel B Tripped Due to Failure of Reactor Coolant Flow Transmitter RC-14A-FT2.Caused by Shorted Capacitor in Power Supply.Capacitor Replaced & Transmitter Returned to Svc (← links)
- 05000302/LER-1982-072-03, /03L-0:on 821125,determined Reactor Coolant Water Leaking to Nuclear Svcs Closed Cycle Cooling Sys Through Letdown Cooler B.Caused by Thermal Shock Due to Long Isolation During Rapid Restoration to Svc.Cooler Replaced (← links)
- 05000302/LER-1982-073-04, /04T-0:on 821126,isolation Setpoint on Liquid Waste Effluent Monitor (RM-L7) Not Sufficiently Conservative to Preclude Release in Excess of 10CFR20.Caused by Inadequate Process.Procedure Revised (← links)
- 05000302/LER-1982-058-01, /01T-0:on 820924,valve Lineups Identified Which Allow Once Through Steam Generator Drain Lines to Be Used for Blowdown Operations & Also Allows High Energy Fluid Through Lines.Caused by Inadequate Review of Sys Design (← links)
- 05000302/LER-1982-004-01, /01T-0:on 820129,during Visual Insp of RCP-A Seal Package,Crack in Weld Between Third Stage Cavity & Vent Pipe Discovered.Caused by Crack in Weld Joint Where Vent Pipe Meets Cavity.Rebuilt Spare Seal Package Installed (← links)
- 05000302/LER-1982-003-01, /01T-0:on 820128,RCS Pressure Boundary Leak Found in Valve Body of MUV-43.Caused by Thermally Induced Cyclic fatigue.MUV-43 Removed.New Valve Will Be Installed in Improved Location (← links)
- 05000302/LER-1982-069-03, /03L-0:on 821029,remote & Local 175-ft Wind Direction Channels Found Out of Tolerance.Caused by Failed Direction Sensor.Sensor Replaced & Instrument Recalibr. Meteorological Monitoring Sys Under Evaluation (← links)
- 05000302/LER-1982-067-03, /03L-0:on 821028,feedwater Ultrasonic Flow Indicator FW-313-FI Discovered Inoperable.Caused by Defective Scale Card.Scale Card Replaced & Functional Check Satisfactorily Completed (← links)
- 05000302/LER-1982-068-03, /03L-0:on 821029,feedwater Ultrasonic Flow Indicator FW-312-FI Found Inoperable During Daily Surveillance,Rendering Emergency Feedwater Train a Inoperable.Caused by Insufficient Cable Clearance (← links)