ML100550641

From kanterella
Revision as of 00:19, 24 August 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Watts Bar Nuclear Plant, Unit 2, Developmental Revision B - Technical Requirements Manual Bases B 3.6 - Containment Systems
ML100550641
Person / Time
Site: Watts Bar 
Issue date: 02/02/2010
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
References
Download: ML100550641 (12)


Text

Ice Bed Temperature Monitoring System B 3.6.1 (continued)Watts Bar - Unit 2 B 3.6-1 Technical Requirements (developmental) A B 3.6 CONTAINMENT SYSTEMS

B 3.6.1 Ice Bed Temperature Monitoring System

BASES BACKGROUND The Ice Bed Temperature Monitori ng System consists of Resistance Temperature Detectors (RTDs) which are located in various parts of the

ice condenser. They serve to verify the attainment of a uniform

equilibrium temperature in the ice bed and to detect general gradual

temperature rise in the cooling system if breakdown occurs.

Forty-seven RTDs are mounted on ice bed probes which are located

throughout the ice bed. These 47 RTDs tie into a temperature scanner

unit, located in the Incore Instrument Room. The scanner multiplexes the

ice condenser RTD's signals to a Westronics recorder in the Main Control

Room. There are also six temperature switches located at various points

in the ice bed to serve as backup indication should the scanner unit or

recorder fail to operate. These inputs provide an alarm on the control

room annunciator panel should the ice bed temperature exceed preset

value (Ref. 1). In addition, the 47 RTDs can be read from the local ice

condenser temperature monitoring panel.

APPLICABLE

SAFETY ANALYSES The ice condenser is a passive device requiring only maintenance of the ice inventory in the ice bed. As such there are no actuation circuits or

equipment which are required for the ice condenser to operate in the

event of a Loss of Coolant Accident (LOCA). The Ice Bed Temperature

Monitoring System serves only to moni tor the ice bed temperature. Since the ice bed has a very large thermal capacity, postulated off-normal

conditions can be successfully tolerated for a week to two weeks.

Therefore, the Ice Bed Temperature M onitoring System provides an early warning of any incipient ice condenser temperature anomalies. The Ice

Bed Temperature Monitoring System is not assumed to be OPERABLE to mitigate the consequences of a DBA or transient. Based on the PRA

Summary Report (Ref. 2), the Ice Bed Temperature Monitoring System has not been identified as a significant risk contributor.

Ice Bed Temperature Monitoring System B 3.6.1 BASES (continued)

Watts Bar - Unit 2 B 3.6-2 Technical Requirements (developmental) A TR TR 3.6.1 states that the Ice B ed Temperature Monitoring System shall be OPERABLE with at least two OPERABLE RTD channels in the ice bed at

each of three basic elevations: 10'6", 30'9", and 55' above the floor of the

ice condenser, for each one-third of the ice condenser.

The OPERABILITY of the Ice Bed Temperature Monitoring System

ensures that the capability is available for monitoring the ice bed

temperature. The ice bed temperature may be determined at the local ice

condenser temperature monitoring panel as well as in the Main Control

Room and the Monitoring System w ould still be considered OPERABLE.

In the event the Monitoring System is inoperable, the Required Actions

provide assurance that the ice bed heat removal capacity will be retained

within the specified time limits.

APPLICABILITY The Ice Bed Temperature Monitoring System is required to be OPERABLE in MODES 1, 2, 3, and 4. This corresponds to the

Applicability requirements for the ice bed in Technical Specification

LCO 3.6.11, "Ice Bed."

ACTIONS A.1

With the ice bed temperature not available in the Main Control Room, the

ice bed temperature must be determined at the local ice condenser

temperature monitoring panel (local panel) every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. Since the ice

bed has a very large thermal capacity, postulated off-normal conditions

can be successfully tolerated for one or two weeks. Therefore, a 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

surveillance of the ice bed temperature will give sufficient warning of any

incipient ice condenser temperature anomalies.

B.1.1, B.1.2, and B.1.3

With the Ice Bed Temperature Monitoring System inoperable and being

unable to determine the ice bed temperature at the local panel, Required

Actions B.1.1, B.1.2, and B.1.3 require verification that: the ice

compartment lower inlet doors, intermediate deck doors, and top deck

doors are closed; the last recorded mean ice bed temperature was less

than or equal to 20 F (value does not account for instrument error) and steady; and the Ice Condenser Cooling System is OPERABLE.

Ice Bed Temperature Monitoring System B 3.6.1 BASES (continued)

Watts Bar - Unit 2 B 3.6-3 Technical Requirements (developmental) A ACTIONS B.1.1, B.1.2, and B.1.3 (continued)

The Completion Time of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter to perform

Required Actions B.1.1 and B.1.3 and 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to perform Required

Action B.1.2 is reasonable and based upon the typical time necessary to

perform the Required Actions. These Required Actions, along with the

high thermal capacity of the ice bed, ensure that the ice bed will remain

below critical temperatures while the Monitoring System is inoperable.

B.2.1 and B.2.2

With the Ice Bed Temperature Monitoring System inoperable and being

unable to determine the ice bed temperature at the local panel, either the

Monitoring System or the local monitoring panel must be restored to

OPERABLE status within 30 days. A Completion Time of 30 days is

given, provided that Required Actions B.1.1, B.1.2, and B.1.3 are met.

These Required Actions, along with the high thermal capacity of the

ice bed, ensure that the ice bed will remain below critical temperatures

during the 30 day Completion Time. Also, the six alarmed temperature

switches (which provide an alarm at 25 F) will continue to monitor the ice bed temperature. If the Ice Condenser Cooling System becomes inoperable before the Ice Bed Temperature Monitoring System is

OPERABLE, then Required Action C must be performed.

C.1.1 and C.1.2

With the Ice Bed Temperature Monitoring System inoperable and being

unable to determine the ice bed temperature at the local panel and with

the Ice Condenser Cooling System not satisfying the minimum

components OPERABILITY requirements of Required Action B.1.3, Required Actions C.1.1 and C.1.2 require verification that: the ice

compartment lower inlet doors, intermediate deck doors, and top deck

doors are closed; and that the last recorded mean ice bed temperature

was less than or equal to 15 F (value does not account for instrument error) and steady. The Completion Time of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

thereafter to perform Required Action C.1.1 and 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to perform

Required Action C.1.2 is reasonable and based upon the typical time

necessary to perform the Required Actions. These Required Actions, along with the high thermal capacity of the ice bed, ensure that the

ice bed will remain below critical temperatures while the Monitoring

System and Ice Condenser Cooling System are inoperable.

Ice Bed Temperature Monitoring System B 3.6.1 BASES (continued)Watts Bar - Unit 2 B 3.6-4 Technical Requirements (developmental) A ACTIONS (continued)

C.2.1, C.2.2, and C.2.3

With the Ice Bed Temperature Monitoring System inoperable and being

unable to determine the ice bed temperature at the local panel and with

the Ice Condenser Cooling System not satisfying the minimum

components OPERABILITY requirements of Required Action B.1.3, the

Ice Condenser Cooling System, Ice Bed Temperature Monitoring System or the local temperature monitoring panel must be restored to

OPERABLE status. A Completion Time of 6 days is given, provided that

Required Actions C.1.1 and C.1.2 are met. These Required Actions, along with the high thermal capacity of the ice bed, ensure that the

ice bed will remain below critical temperatures during the 6 day

Completion Time. Also, the six alarmed temperature switches (which

provide an alarm at 25 F) will continue to monitor the ice bed temperature.

D.1 and D.2

If the Required Action and associated Completion Time of Condition A, B

or C is not met, the integrity of the ice bed may be threatened. Therefore, the plant must be placed in a MODE in which the TR does not apply.

This is done by placing the plant in MODE 3 in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and MODE 5 in

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The allowed Completion Times are reasonable based on

operating experience to reach the required plant conditions from full

power conditions in an orderly manner and without challenging plant systems.

TECHNICAL

SURVEILLANCE

REQUIREMENTS TSR 3.6.1.1

Performance of a CHANNEL CHECK on the Ice Bed Temperature

Monitoring System once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ensures that a gross failure of

instrumentation has not occurred. A CHANNEL CHECK is a comparison

of the parameter indicated on one channel to a similar parameter on other

channels. It is based on the assumption that instrument channels

monitoring the same parameter should read approximately the same

value. Significant deviations between the instrument channels could be

an indication of excessive instrument drift in one of the channels or of

even something more serious. The Surveillance Frequency, about once

every shift, is based on operating experience that demonstrates the rarity

of channel failure. Thus, TSR 3.6.1.1 ensures that loss of function will be

identified within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

Ice Bed Temperature Monitoring System B 3.6.1 BASES (continued)

Watts Bar - Unit 2 B 3.6-5 Technical Requirements (developmental) A REFERENCES 1. Watts Bar FSAR, Section 6.7.15, "Ice Condenser Instrumentation" 2. WCAP-11618, "MERITS Program-Phase II, Task 5, Criteria Application," including Addendum 1 dated April, 1989.

Inlet Door Position Monitoring System B 3.6.2 (continued)Watts Bar - Unit 2 B 3.6-6 Technical Requirements (developmental) A B 3.6 CONTAINMENT SYSTEMS

B 3.6.2 Inlet Door Position Monitoring System

BASES BACKGROUND Ninety-six limit switches monitor the position of the lower inlet doors.

Two switches are mounted on the door frame for each door panel.

The position and movement of the switches are such that the doors must

be effectively sealed before the switches are actuated. A single

annunciator window in the control room gives a common alarm signal

when any door is open. Open/shut indication is also provided at the lower

inlet door position display panel located in the Main Control Room. For

door monitoring purposes, the ice condenser is divided into six zones, each containing four inlet door assemblies, or a total of eight door panels.

The limit switches on the doors in any single zone are wired to a single

light on the inlet door position display panel such that a closed light

indicates that all the doors in that zone are shut and an open light

indicates that one or more doors in that zone are open (Ref. 1). The

display panel is considered the Inlet Door Position Monitoring System.

Monitoring of inlet door position is necessary because the inlet doors form

the barrier to air flow through the inlet ports of the ice condenser for

normal unit operation. Failure of the Inlet Door Position Monitoring

System requires an alternate OPER ABLE monitoring system to be used to ensure that the ice condenser is not degraded.

APPLICABLE

SAFETY ANALYSES Proper operation of the inlet doors is necessary to mitigate the consequences of a loss of coolant accident or a main steam line break

inside containment. The Inlet Door Position Monitoring System, however, is not required for proper operation of the inlet doors, nor is it considered

OPERABLE as an initial condition for a DBA. Hence, the Inlet Door

Position Monitoring System is not a consideration in the analyses of

DBAs. Based on the PRA Summary Report in Reference 2, the Inlet

Door Position Monitoring System has not been identified as a significant

risk contributor.

Inlet Door Position Monitoring System B 3.6.2 BASES (continued)

(continued)Watts Bar - Unit 2 B 3.6-7 Technical Requirements (developmental) A TR The Inlet Door Position Monitoring Sy stem provides the only direct means of determining that the inlet doors are shut. Since an open door would

allow heat input that could cause sublimation and mass transfer of ice in

the ice condenser compartment, the Inlet Door Position Monitoring

System must be OPERABLE whenever the ice bed is required to be

OPERABLE. This ensures early detection of an inadvertently opened or

failed door, allowing prompt action before ice bed degradation can occur.

APPLICABILITY The Inlet Door Position Monitoring System is required to be OPERABLE in MODES 1, 2, 3 and 4. This corresponds to the Applicability

requirements for the ice bed.

ACTIONS A.1 and A.2

If the Inlet Door Position Monitoring System is inoperable in MODE 1, an

alternate OPERABLE monitoring system must be used to ensure that the

ice condenser is not degraded. This is done by confirming the Ice Bed

Temperature Monitoring System is OPERABLE with the ice bed

temperature 27 F (value does not account for instrument error). This Action must be completed within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> thereafter.

The Frequency of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> is based on the fact that temperature changes

cannot occur rapidly in the ice bed because of the large mass of ice

involved. Since this is an indirect means of monitoring inlet door position, operation in MODE 1 may continue for a maximum of 14 days in this

condition. If the ice bed temperature increases to above 27 F, the ice bed must be declared inoperable in accordance with Technical

Specification 3.6.11, "Ice Bed".

B.1 If the Required Action and associated Completion Time for Condition A

are not met or if the Inlet Door Position Monitoring System is inoperable in

MODES 2, 3, or 4, the Inlet Door Position Monitoring System must be

restored to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />. The 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> Completion

Time is based on the fact that, with the very large mass of ice involved, it

would not be possible for the temperature to increase to the melting point

and a significant amount of ice to melt in a 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> period.

Inlet Door Position Monitoring System B 3.6.2 BASES (continued)Watts Bar - Unit 2 B 3.6-8 Technical Requirements (developmental) A ACTIONS (continued)

C.1 and C.2

If the Required Action and associated Completion Time of Condition B

cannot be met, the plant must be placed in a condition where

OPERABILITY of the Inlet Door Position Monitoring System is not

required. This is accomplished by placing the plant in MODE 4 within

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and MODE 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The allowed Completion Times are

reasonable, based on operating experience, to reach the required

MODES from full power in an orderly manner and without challenging

plant systems.

TECHNICAL

SURVEILLANCE

REQUIREMENTS TSR 3.6.2.1

Performance of the CHANNEL CHECK for the Inlet Door Position

Monitoring System once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ensures that a gross failure of

instrumentation has not occurred. A CHANNEL CHECK is a comparison

of the parameter indicated on one channel to a similar parameter on other

channels. It is based on the assumption that instrument channels

monitoring the same parameter should read approximately the same

value. Significant deviations between the two instrument channels could

be an indication of excessive instrument drift in one of the channels or of

something even more serious. Performance of the CHANNEL CHECK

helps to ensure that the instrumentation continues to operate properly

between each TADOT. The dual switch arrangement on each door

allows comparison of open and shut indicators for each zone as well as a

check with the annunciator window. An alternate to the use of the

annunciator window as the channel check, is to perform a continuity

check of the same circuit used by the annunciator window. This

continuity check will confirm if one or more inlet door zone switch contacts

are closed which would represent an open inlet door. The Surveillance

Frequency, about once every shift, is based on operating experience that

demonstrates the rarity of channel failure. Thus, TSR 3.6.2.1 ensures that

loss of function will be identified within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

Inlet Door Position Monitoring System B 3.6.2 BASES Watts Bar - Unit 2 B 3.6-9 Technical Requirements (developmental) A TECHNICAL SURVEILLANCE

REQUIREMENTS (continued)

TSR 3.6.2.2

TSR 3.6.2.2 is the performance of a TADOT every 18 months. It checks

trip devices (limit switches) that provide actuation signals directly.

The 18 month Frequency was developed considering the plant conditions

needed to perform TSR 3.6.2.2. The 18 month Frequency is also

acceptable based on consideration of the design reliability (and

confirming operating experience) of the equipment.

TSR 3.6.2.3

TSR 3.6.2.3 requires verification that the monitoring system correctly

indicates the status of each inlet door as the door is opened and reclosed

during its Technical Specification testing. This provides ongoing

operational testing of the indicating system. The Frequency coincides

with the Technical Specifications testing performed.

REFERENCES 1. Watts Bar FSAR, Section 6.7, "Ice Condenser System." 2. WCAP-11618, "MERITS Program-Phase II, Task 5, Criteria Application," including Addendum 1 dated April, 1989.

Lower Compartment Cooling System B 3.6.3 (continued)Watts Bar - Unit 2 B 3.6-10 Technical Requirements (developmental) B B 3.6 CONTAINMENT SYSTEMS

B 3.6.3 Lower Compartment Cooling (LCC) System

BASES

BACKGROUND The Lower Compartment Cooling (L CC) fans provide non-safety related cooling for the lower compartment spaces after all accidents, except

those that initiate a Phase B Containment Isolation Signal (Ref. 1), when

the non-safety related cooling coils and cooling water supply are

available. LCC fans perform a safety related air recirculation function in

the lower containment pocketed (dead ended) spaces after a main steam

line break (MSLB) to prevent the formation of localized hot spots which

could exceed the qualification temperatures of equipment required to

operate post accident. The LCC fans are not required to operate during

or after a loss of coolant accident (LOCA).

After an MSLB, one LCC train will be manually started a minimum of 1 1/2

hours, but less than 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, after the accident to ensure that the dead

ended compartment temperatures ar e kept below the environmental qualification limit. Each train consists of two 50% capacity fans, backdraft

damper, instrumentation and controls, and associated ductwork. Each

train is powered from separate class 1E power sources.

APPLICABLE

SAFETY ANALYSES The LCC fans recirculate air in the lower compartment spaces after an MSLB. Under these circumstances, the intact Reactor Coolant System

piping will serve as a long term heat source. After the ice is melted, the

heat from the Reactor Coolant System (RCS) will result in a gradual

temperature increase in the sub-compartments of the lower containment.

If the recirculation of air should fail during or after the accident, the

Containment Spray System and Air Return Fan System can be started to

provide the necessary containment cooling. The temperatures in the sub-

compartments of the lower containment are not input to the safety

analyses. Containment area temperatures have not been identified as significant risk contributors.

Lower Compartment Cooling System B 3.6.3 BASES (continued)

(continued)Watts Bar - Unit 2 B 3.6-11 Technical Requirements (developmental) A TR The TR specifies the equipment which needs to be OPERABLE in order to ensure that air can be circulated in the sub-compartments if an

accident should take place. At least one LCC train must be placed in

operation after the accident. The LCC fans do not perform a cooling

function, which means that the coils and the secondary cooling water

circuits need not be OPERABLE. However, secondary side failures

which could impair the operation of the fans and the circulation of the air

must be prevented.

APPLICABILITY The flow of air to the sub-compartments is necessary following an MSLB where the RCS represents a major heat source in lower containment.

Based on the temperature of the RCS, this could be in MODES 1

through 4. In MODES 5 and 6, the probability for an accident is small

and, in any case, the heat capacity of the RCS is limited and, therefore, not able to heat up the lower compartment spaces to such an extent that

equipment could degrade. The specification is therefore only applicable

in MODES 1, 2, 3 and 4.

ACTIONS A.1

With one fan inoperable, the inoperable fan must be restored to

OPERABLE status within 7 days. During this period, the remaining

three fans are available to circulate the air in the lower compartments of

the containment. However, only two fans are necessary to prevent the

hot spots. Hence, there is one spare fan available. The 7 day

Completion Time is based on the low probability of an event requiring

emergency fan operation, the availability of one fan more than required, and the availability of alternate cooling means.

B.1 With two fans inoperable the plant has still adequate fan capacity to

circulate air if an accident should take place. However, in this case no

spare capacity is available. Hence, it is required to restore at least

one fan to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. With one fan restored, three fans will be OPERABLE and Condition A must be entered. This will

allow another 7 days to restore the last inoperable fan to OPERABLE

status. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time in Condition B is based on the low

probability of an event requiring fan operation simultaneous with further

fan deterioration, and the availability of alternate cooling means.

Lower Compartment Cooling System B 3.6.3 BASES Watts Bar - Unit 2 B 3.6-12 Technical Requirements (developmental) B ACTIONS (continued)

C.1 and C.2

If the Required Actions of A.1 and B.1 cannot be completed within the

required Completion Time or if more than two fans are inoperable, the

plant must be placed in a MODE in which the TR does not apply. This is

done by placing the plant in at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in

MODE 5 within an additional 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The allowed Completion Times

are reasonable, based on operating experience, to reach the required

plant conditions from full power conditions in an orderly manner and

without challenging plant systems.

TECHNICAL

SURVEILLANCE

REQUIREMENTS TSR 3.6.3.1

During normal operation, three of the four LCCs operate to remove heat

from the lower compartments of the containment. This means that three

of the four fans are operating at all times. Hence, this gives certainty that

at least three fans are OPERABLE. The test is for the fan that has not

been in operation during the preceding 31 days and to verify that all fans

can be manually started from the control room. The 15 minutes running

test is optional for fans that have been running the previous 31 days, or

will be running after the Surveillance has been carried out.

REFERENCES 1. Watts Bar FSAR, Section 6.2.2, "Containment Heat Removal Systems." 2. Thomas E. Murley (NRC) letter to W. S. Wilgus, dated May 9, 1988, forwarding the NRC Staff review of the "Nuclear

Steam Supply System Vendor Owners Groups' Application of the

Commission's Interim Policy Statement Criteria to the Standard

Technical Specifications."