05000250/FIN-2016008-01
From kanterella
Revision as of 07:56, 25 September 2017 by StriderTol (talk | contribs) (Created page by program invented by Mark Hawes)
Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | Turkey Point Nuclear Generating Station, Unit 4, Renewed Facility Operating License 3.D, Fire Protection, stated that Florida Power and Light (FPL) shall implement and maintain in effect all provisions of the approved fire protection program that comply with 10 CFR 50.48 (c), National Fire Protection Association (NFPA) 805. NFPA 805, Section 2.4.2.2.2 (b), Common Enclosure Circuits, required circuits that share a common enclosure with circuits required to achieve nuclear safety performance criteria shall be identified for their impact on the ability to achieve nuclear safety performance criteria. Contrary to the above, since 2014, the licensee failed to identify circuits that impact the ability to achieve nuclear safety performance criteria as a result of the effects of fire on circuits that share a common enclosure with the Unit 4 4kV switchgear. The violation was determined to be of very low safety significance based on risk evaluation provided by the licensee and reviewed by NRC senior reactor analyst. The licensee entered this issue into their corrective action program as action request 2134673. |
Site: | Turkey Point |
---|---|
Report | IR 05000250/2016008 Section 4OA7 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | J Dymek J Montgomery J Patel M Riley M Singletary P Lain S Shaeffer |
Violation of: | 10 CFR 50.48 |
INPO aspect | |
' | |
Finding - Turkey Point - IR 05000250/2016008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Turkey Point) @ 2016Q4
Self-Identified List (Turkey Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||