05000368/LER-1981-018-03, During Mode 6 Operation, Emergency Diesel Generator 2 Received Lockout During Load Rejection Test.Caused by Antimonitoring Relay Holding Coil Adjustment Found Out of Tolerance.Adjustments Made

From kanterella
Revision as of 09:29, 21 December 2024 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
During Mode 6 Operation, Emergency Diesel Generator 2 Received Lockout During Load Rejection Test.Caused by Antimonitoring Relay Holding Coil Adjustment Found Out of Tolerance.Adjustments Made
ML20009E893
Person / Time
Site: Arkansas Nuclear 
Issue date: 06/26/1981
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20009E887 List:
References
LER-81-018-03X, NUDOCS 8107280526
Download: ML20009E893 (1)


LER-1981-018, During Mode 6 Operation, Emergency Diesel Generator 2 Received Lockout During Load Rejection Test.Caused by Antimonitoring Relay Holding Coil Adjustment Found Out of Tolerance.Adjustments Made
Event date:
Report date:
3681981018R03 - NRC Website

text

'

o l

e REVISED REPORT - PREVIOUS REPORT DATE 5-27-81 Nnc FORM 3E,4 U. 5. NUCLE AR REGULATORY COMMIS$60N LICENSEE EVENT REPORT EXHIBIT A CONTROL SLOCK: l l l l l l !h (PLE ASE 8'RINT OR TYPE ALL REOutRED INFORMATIONI i

6 l AlR l Al Nl 0 l 2 lgl 0 l0 l - 10 l 0 l 0l 0l 0 l-l 0 l0 [gj4 l1 l 1l1 l _1 gj l lg

_ J o i I

e 3 LICENste CODE 84 it UCEN54 NUMSEM 2%

26 LK L Nat I,,4 JO blCAF 58 p'T 1"l"c' LL_)@l0 I s p 10 i ois I 6_i8Ji0 i s 01 si all i@l Oi 6 i 216 i 811 l@

CON 60 et DOCKE T NuMetR i

69 EvtNT DATE 34 FS HE,OHTDAft 80 8

EVENT DESCRIPTION AND PROS ABLE CONSEQUENCES h'a l During Mode 6 operation, Emergency Diesel Generator (EDG) #2 received a i o

i generator lockout during the load rejection test portion of the 18 month i o 3 i surveillance. This is a non-valid failure as defined by Reg. Guide 1.108L o.

n s i Rev.1, Position C.2.e(2), as the anti-motoring relay is by-passed on a i i SIAS signal. There has beer, mie failure in the last 100 valid tests. The o o I redundant EDG and offsite power was available meeting requirements of I

o >

I T.S. 3.8.1.2..

Similar to LER 50-368/81-016.

Reportable per T.S. 4.8.1.153 o.

' pursuants,tquT.S. c5J.1.Lh m,,

COoE LCDE SUSCODE COM,0NENT Cout sueef out bu,, Coot L,o L'_I I E I EIO L,, Ej@ L,, Aj @ l RI E l L l A l Y ! xlO L.,OJ O O,o @

,2 i

LEA NO NTvgAR m

T O E

k

@,arg la Il l L-J 1 01118I M

1013 i LxJ 1---J Lij u

_2n 27 23 24 16 27 78 29 Jo 31 3J s'u TAK N

,L T

MET HOURS s SM i F

,e i R M N FA TuRER LEJ@LZJ@ LZJ@

tzJ O I0 IO!0 101 LNJ@

LyJO lA_J@ lGl0l8[Ol@

3J 34 35 36 32 40 48 41 43 44 el CAUSE OESCA.PTION AND CORRECitVE ACTIONS h l Thic anti-mntnring relay hniding enil adiustment was found to be out of I i o i tolerance. This adjustment is normally considered to be a " factory settipg".

rrTT) i Ad.iustments were made and EDG load re.iection test successfully completed.:

i The procedure was revised to include relay checks.

Similar relays on i

i 2 i EDG #1 and Main Generator are being checked utilizing revised procedure.

i.

'd'.'Ws' o1. status @ ",Jat? #

o,scov,ov o.sc,,,,,,o @

~

uo.

[fLJ@ l 01 010 l@l NA l [Bj@l Surveillance Testing l

i s

'2 is a

e oc

=

" J1,,,,, es,.,

r

.MouNr e,,ct,,,,, @ l tmonoNo,,,,u.s,@

.cu.s.o o,anu.s.

LZ_J @ LZJ@l NA l

NA l

i c

,. so~ '.1,,,ose.,

=

oisca.,rio @

uuM...

nn lo 101 Ol@LZ J@l NA l

i i

=

.cosoN.!',N,u',!,es onsca,,r oN@

NuM.ca 10l0l01@l NA l

i =

$# ' " b',V1 '"" @

[Zj@l NA l

' 9

, su,'Ol'"$c.,1,o,.@

~

Nac ust mtv U

NA l llllllll: ;g;l 2 o Chris N. Shively NhMGB mE OP PREPAnEn