LER-2024-002, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 4982024002R01 - NRC Website |
|
text
June 27, 2024 NOC-AE-24004047 10 CFR 50.73 STI: 35609717 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555- 0001 South Texas Project Unit 1 Docket No. STN 50-498 Licensee Event Report 20 24-002 -01 Supplement to Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function
Reference: Letter; J. Tomlinson (STP) to Document Control Desk (NRC); Licensee Event Report 2024-002- 00 Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function; May 9, 2024; (NOC-AE-24004040) (ML24130A271).
On May 9, 2024, STP Nuclear Operating Company (STPNOC) submitted the referenced Licensee Event Report. This letter is a supplement to the report to provide the updates results of the causal evaluation. The updated information is denoted by revision bars located in the right-hand margin. The report is submitted in accordance with 10 CFR 50.73.
The event did not have an adverse effect on the health and safety of the public.
There are no commitments in this submittal.
If there are any questions regarding this submittal, please contact Zachary Dibbern at 361-972-4336 or me at 361 -972-8945.
Jason R. Tomlinson Site Vice President
Attachment: Unit 1 LER 2024 -002 -01, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function
cc:
Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 1600 E. Lamar Boulevard Arlington, TX 76011-4511
NOC-AE-24004047 Attachment
Attachment
Unit 1 LER 2024-002-01
Unit 1 LER 2024- 002-01, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function
Abstract
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000499/LER-2024-001, Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators | Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000499/LER-2024-001-01, Supplement to Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators | Supplement to Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators | | | 05000498/LER-2024-001, Re Two Steam Generator Power Operated Relief Valves (Porvs) Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | Re Two Steam Generator Power Operated Relief Valves (Porvs) Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000499/LER-2024-002, Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000498/LER-2024-002-01, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000499/LER-2024-002-01, Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000499/LER-2024-003, Containment Isolation Valve Inoperable Resulting in Condition Prohibited by Technical Specification and Prevention of Fulfillment of Safety Function | Containment Isolation Valve Inoperable Resulting in Condition Prohibited by Technical Specification and Prevention of Fulfillment of Safety Function | 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000498/LER-2024-003, Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Low Head Safety Injection Pump | Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Low Head Safety Injection Pump | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000498/LER-2024-004, Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps | Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | | 05000498/LER-2024-004-01, Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps | Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps | | | 05000498/LER-2024-006, Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Pressurizer Power Operated Relief Valve | Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Pressurizer Power Operated Relief Valve | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000498/LER-2024-007-01, Supplement to Condition Prohibited by Technical Specifications | Supplement to Condition Prohibited by Technical Specifications | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000498/LER-2024-007, Condition Prohibited by Technical Specifications | Condition Prohibited by Technical Specifications | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
|