(BSEP-2-89)
TABLE 3.6.3-1 (Continued) t, g PRIMARY CONTAINHENT ISOLATION VALVES 5
C ISOLATION TIHE h VALVE FUNCTION VALVE CROUP II (Seconds)
IIPCI steam line isolation valves 4 50
.O E41-F002 U E41-F003 w
!!PCI torus suction isolation valves 4 80 E41-F042 E41-F041 RCIC steam line isolation valves 5 20* l E51-F007 E51-F008 w Drywell purge exhaust backup valve 6 15 g CAC-V10 i Containment air purge isolation valve 6 15 G CAC-V15 Suppression chamber vent valve 6 15 CAC-V22
~
Drywell purge exhaust valve 6 15 CAC-V23
- The Isolation Time for valve E51-F007 is extended to 30 seconds until December 6, 1986 at which I time the 20 second limit will be re-established.
E 8
8606090208 860604 z PDR ADOCK 05000324 P png '
__________ _ ____ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _