Attachment 4 to Procedure EM-09-13,Rev 1, ISI Pressure Testing Program Procedure.
ML18059B048
Person / Time
Site: Palisades 
Issue date: 06/03/1994
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18059B047 List:
References
EM-09-13, EM-9-13, NUDOCS 9406130139
Download: ML18059B048 (1)


Text

RELIEF REQUEST BASIS NUMBER 1 Proc No EM-09-13 Attachment 4 Revision 1 Page 1 of 1 SYSTEM: Primary Coolant System (PCS)

SUBJECT:

Use of PI-0104 in lieu of digital pressure instrument meeting requirements of Code Case N-437. CLASS: 1 -FUNCTION:

PI-0104 is used to monitor test pressure during the Primary Coolant System hydrostatic test.

  • TEST REQUIREMENT:

Nuclear Code Case N-437 requires for digital pressure measuring instruments that "the intended maximum test pressure does not

  • exceed 70% of the calibrated range of the_ instrument.

Accuracy shall be within 0.5% of calibrated range." BASIS FOR RELIEF: ALTERNATIVE:

Specification and installation of a test pressure instrument of proper range in order to meet Code requirements would not obtain information more useful than presently available using Installed Plant Instruments.

PI-0104 has a full scale range of Oto 3000 psia. PCS hydrostatic test pressure is 2101 psia with a maximum allowable pressure of 2125 allowed for control purposes.

2125 psia is equivalent to 71% of the maximum PI-0104 range. This exceeds the 70% limit allowed by Nuclear Code Case N-437. However. a difference of 1% will not make a significant difference in the. quality of test pressure data..

  • Palisades will perform PCS hydrostatic testing using PI-0104 as the test pressure instrument.

Accuracy requirements for this gage shall meet the 0.5% requirement of Nuclear Code Case N-437. However. the maximum expected PCS hydrostatic test pressure . (2125 psia) will of the maximum gauge range C0-3000

(_

940603 \, ___ -ADOCK 05000255 . . i -----------------__ PDR . ._ )