ML072140852

From kanterella
Revision as of 01:13, 23 October 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

LaSalle County Station, Units 1 & 2, Technical Specificatiosns, Issuance of Amendment Nos. 183/170 Ultimate Heat Sink Emergency Amendment (TAC Nos. MD6014 and MD6015)
ML072140852
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 08/02/2007
From:
NRC/NRR/ADRO/DORL/LPLIII-2
To:
Thorpe-Kavanaugh, Meghan, LPL3-1
Shared Package
ML072140838 List:
References
TAC MD6014, TAC MD6015
Download: ML072140852 (1)


Text

UHS 3.7.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.3.1 Verify cooling water temperature supplied 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to the plant from the CSCS pond is 10 11.25°F.SR 3.7.3.2 Verify sediment level is 1.5 ft in the 24 months intake flume and the CSCS pond.SR 3.7.3.3 Verify CSCS pond bottom elevation is 24 months 686.5 ft.LaSalle I and 2 3.7.3-2 Amendment No. 183 / 170