Letter Sequence Approval |
|---|
|
|
MONTHYEARRS-07-069, Request for a License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink2007-06-29029 June 2007 Request for a License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink Project stage: Request RS-07-112, Additional Information Supporting Request for a License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink, and Request for Processing on an Emergency Basis2007-08-0101 August 2007 Additional Information Supporting Request for a License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink, and Request for Processing on an Emergency Basis Project stage: Request ML0721408442007-08-0202 August 2007 License Amendments, Issuance of Amendment Nos. 183/170 Ultimate Heat Sink Emergency Amendment Project stage: Approval ML0721408522007-08-0202 August 2007 Technical Specificatiosns, Issuance of Amendment Nos. 183/170 Ultimate Heat Sink Emergency Amendment Project stage: Approval RS-07-113, Additional Information Supporting Request for Emergency License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink2007-08-0202 August 2007 Additional Information Supporting Request for Emergency License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink Project stage: Request RS-07-114, Additional Information Supporting Request for Emergency License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink2007-08-0202 August 2007 Additional Information Supporting Request for Emergency License Amendment to Technical Specification 3.7.3, Ultimate Heat Sink Project stage: Request 2007-08-01
[Table View] |
Text
UHS 3.7.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.3.1 Verify cooling water temperature supplied 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to the plant from the CSCS pond is 10 11.25°F.
SR 3.7.3.2 Verify sediment level is
- 1.5 ft in the 24 months intake flume and the CSCS pond.
SR 3.7.3.3 Verify CSCS pond bottom elevation is 24 months 686.5 ft.
LaSalle I and 2 3.7.3-2 Amendment No. 183 / 170