ENS 42254
ENS Event | |
---|---|
14:20 Jan 12, 2006 | |
Title | Control Room Air Conditioning And Control Room Emergency Ventilation Systems Inoperable |
Event Description | At 0400 hours0.00463 days <br />0.111 hours <br />6.613757e-4 weeks <br />1.522e-4 months <br /> on January 12, 2006, 2A Control Building Standby Instrument Air Compressor was taken out of service for scheduled maintenance. Subsequently, at 0920 hours0.0106 days <br />0.256 hours <br />0.00152 weeks <br />3.5006e-4 months <br />, the in-service 2B Control Building Standby Instrument Air Compressor failed, resulting in the loss of control air. As a result, the three Control Room Air Conditioning subsystems required by Technical Specification (TS) 3.7.4, "Control Room Air Conditioning (AC) System," and the two Control Room Emergency Ventilation subsystems required by TS 3.7.3, "Control Room Emergency Ventilation (CREV) System," became inoperable. As a result, this condition could have prevented the fulfillment of the safety function for these systems. The Control Room AC and CREV systems became inoperable due to loss of control air to the systems. Because Brunswick has a shared control room, Unit 1 and Unit 2 entered TS 3.7.3 Required Action B.1, for two CREV subsystems inoperable (i.e., be in Mode 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />) and TS 3.7.4, Required Action E.1, for three Control Room AC subsystems inoperable (i.e., enter LCO 3.0.3 immediately).
Operability of two Control Room AC subsystems and one CREV subsystem was restored and LCO 3.0.3 was exited, at 1014 hours0.0117 days <br />0.282 hours <br />0.00168 weeks <br />3.85827e-4 months <br />, when the 2A Control Building Standby Instrument Air Compressor was restored to service. [The licensee stated the actual maintenance was completed on 2A Control Building Standby Instrument Air Compressor at the time it was restored to service.] No power reduction took place as a result of the LCO 3.0.3 entry. This report applies to both Units 1 and 2 and is being made in accordance with 10 CFR 50.72(b)(3)(v)(D), as a condition that at the time of discovery could have prevented fulfillment of the safety function of systems that are needed to mitigate the consequences of an accident. The safety significance of this event is considered minimal. The condition existed for approximately 54 minutes. Plant staff took immediate actions to return the equipment to service. For the brief time the Control Room AC and CREV systems were inoperable, performance of plant personnel and equipment in the Control Room was not adversely affected. The maximum Control Room back panel temperature during this event was approximately 73 degrees F. Operability of the Control Room AC system and one subsystem of the CREV system were restored at 1014 hours0.0117 days <br />0.282 hours <br />0.00168 weeks <br />3.85827e-4 months <br /> when the 2A Control Building Standby Instrument Air Compressor was restored to service. Troubleshooting activities are under way to determine the cause of the 2B Control Building Standby Instrument Air Compressor failure. Initial indications are that the unloading ability of the 2B Control Building Standby Instrument Air Compressor failed. The licensee notified the NRC Resident Inspector. |
Where | |
---|---|
Brunswick North Carolina (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
LER: | 05000325/LER-2006-001 |
Time - Person (Reporting Time:+1.78 h0.0742 days <br />0.0106 weeks <br />0.00244 months <br />) | |
Opened: | Dave Jester 16:07 Jan 12, 2006 |
NRC Officer: | John Knoke |
Last Updated: | Jan 12, 2006 |
42254 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 42254\u003C/a\u003E - \u003Ca href=\"/Brunswick\" title=\"Brunswick\"\u003EBrunswick\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EControl Room Air Conditioning and Control Room Emergency Ventilation Systems Inoperable\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 42254 - Brunswick\n","link":"","lat":33.95840833333333,"lon":-78.00979722222222,"icon":"/w/images/7/75/Duke_Energy_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Brunswick with 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
WEEKMONTHYEARENS 559972022-07-16T00:20:00016 July 2022 00:20:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (HPCI) Inoperable ENS 557802022-03-10T01:13:00010 March 2022 01:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (HPCI) Inoperable ENS 541162019-06-13T01:27:00013 June 2019 01:27:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Inoperable ENS 531232017-12-17T08:16:00017 December 2017 08:16:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable ENS 527882017-06-05T17:52:0005 June 2017 17:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Emergency Ventilation Systems Inoperable ENS 526792017-04-14T04:15:00014 April 2017 04:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Drywell and Suppression Chamber Simultaneously Aligned for Venting ENS 520642016-07-05T20:40:0005 July 2016 20:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable ENS 517692016-03-04T17:35:0004 March 2016 17:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Emergency Diesel Generator Declared Inoperable ENS 508162015-02-12T18:36:00012 February 2015 18:36:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable During Weekly Inspection ENS 485962012-12-14T18:06:00014 December 2012 18:06:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Building Emergency Ventilation System Inoperable for Two Minutes ENS 478932012-05-02T21:58:0002 May 2012 21:58:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inoperable Due to Erratic Governor Operation ENS 474932011-12-01T18:44:0001 December 2011 18:44:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Control Room Emergency Ventilation Systems Inoperable ENS 467632011-04-17T02:52:00017 April 2011 02:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Lube Oil Pressure Low Out of Band ENS 467402011-04-07T21:40:0007 April 2011 21:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of the Control Room Emergency Ventilation System ENS 452642009-08-14T23:58:00014 August 2009 23:58:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Automatic Closure of Inboard Isolation Valve ENS 448102009-01-28T01:07:00028 January 2009 01:07:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unit 2 Hpci System Inoperable for Two Hours Due to Condensate in Exhaust Line ENS 447932009-01-21T18:00:00021 January 2009 18:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Control Room Air Conditioning and Emergency Ventilation System ENS 447482009-01-01T19:30:0001 January 2009 19:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Two Emergency Diesel Generators Declared Inoperable Due to Component Failure ENS 443092008-06-19T21:35:00019 June 2008 21:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Ventilation Inoperable ENS 442622008-06-03T17:13:0003 June 2008 17:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Control Room Emergency Ventillation System for 12 Minutes ENS 441792008-04-30T03:13:00030 April 2008 03:13:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable Due to Seal Leak ENS 437112007-10-11T02:45:00011 October 2007 02:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unit 2 Hpci Pump Seal Failure ENS 431972007-02-28T03:26:00028 February 2007 03:26:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) Inoperability ENS 429062006-10-13T17:57:00013 October 2006 17:57:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Declared Inoperable Due to Potential Turbine Exhaust Diaphragm Failure ENS 424882006-04-10T20:30:00010 April 2006 20:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Emergency Ventilation System Declared Inoperable Due to Design Deficiency ENS 423052006-02-03T04:36:0003 February 2006 04:36:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable Due to One Hpci Turbine Exhaust Vacuum Breaker Isolation Valve Failure ENS 422542006-01-12T14:20:00012 January 2006 14:20:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Air Conditioning and Control Room Emergency Ventilation Systems Inoperable ENS 418952005-08-05T22:40:0005 August 2005 22:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperability of All Emergency Diesel Generators ENS 416922005-05-12T08:11:00012 May 2005 08:11:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.73(a)(1), Submit an LER Technical Specification Required Shutdown Due to Loss of Emergency Bus E1 ENS 408332004-06-22T13:00:00022 June 2004 13:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Presure Coolant Injection System Inoperable Due to Maintenance ENS 407142004-04-29T02:30:00029 April 2004 02:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci System Inoperable Following Planned Maintenance ENS 406362004-04-03T08:00:0003 April 2004 08:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 403182003-11-13T03:22:00013 November 2003 03:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Isolation During Testing 2022-07-16T00:20:00 | |