ML100550612
ML100550612 | |
Person / Time | |
---|---|
Site: | Watts Bar |
Issue date: | 02/02/2010 |
From: | Tennessee Valley Authority |
To: | Office of Nuclear Reactor Regulation |
References | |
Download: ML100550612 (24) | |
Text
Definitions 1.1 (continued)
Watts Bar - Unit 2 1.1-1 Technical Requirements (developmental) A 1.0 USE AND APPLICATION 1.1 Definitions
NOTE----------------------------------------------------------
The defined terms of this section appear in capitalized type and are applicable throughout these
Technical Requirements and Bases.
Term Definition ACTIONS ACTIONS shall be that part of a Requirement that prescribes Required Actions to be taken under designated Conditions
within specified Completion Times. CHANNEL CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel so that it responds within the
required range and accuracy to known input. The CHANNEL
CALIBRATION shall encompass the entire channel, including
the required sensor, alarm, interlock, display, and trip
functions. Calibration of instrument channels with resistance
temperature detector (RTD) or thermocouple sensors may
consist of an inplace qualitative assessment of sensor
behavior and normal calibration of the remaining adjustable
devices in the channel. Whenever a sensing element is
replaced, the next required CHANNEL CALIBRATION shall
include an inplace cross calibration that compares the other
sensing elements with the recently installed sensing element.
The CHANNEL CALIBRATION may be performed by means
of any series of sequential, overlapping calibrations or total
channel steps so that the entire channel is calibrated.
CHANNEL CHECK A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation. This
determination shall include, where possible, comparison of
the channel indication and status to other indications or
status derived from independent instrument channels
measuring the same parameter.
Definitions 1.1 1.1 Definitions (continued)
(continued)
Watts Bar - Unit 2 1.1-2 Technical Requirements (developmental) A Term Definition CHANNEL OPERATIONAL TEST (COT)
A COT shall be the injection of a simulated or actual signal
into the channel as close to the sensor as practicable to verify
the OPERABILITY of required alarm, interlock, display, and
trip functions. The COT shall include adjustments, as
necessary, of the required alarm, interlock, and trip setpoints
so that the setpoints are within the required range and accuracy.
CORE ALTERATION CORE ALTERATION shall be the movement of any fuel, sources, or other reactivity control components, within the
reactor vessel with the vessel head removed and fuel in the
vessel. Suspension of CORE ALTERATIONS shall not
preclude completion of movement of a component to a safe
position.
ENGINEERED SAFETY
FEATURE (ESF) RESPONSE
TIME The ESF RESPONSE TIME shall be that time interval from
when the monitored parameter exceeds its ESF actuation
setpoint at the channel sensor until the ESF equipment is
capable of performing its safety function (i.e., the valves
travel to their required positions, pump discharge pressures
reach their required values, etc.). Times shall include diesel
generator starting and sequence loading delays, where
applicable. The response time may be measured by means
of any series of sequential, overlapping, or total steps so that
the entire response time is measured. In lieu of
measurement, response time may be verified for selected
components provided that the components and the
methodology for verification have been previously reviewed
and approved by the NRC.
LEAKAGE LEAKAGE shall be:
- a. Identified LEAKAGE
- 1. LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal
water injection or leakoff), that is captured and
conducted to collection systems or a sump or
collecting tank;
Definitions 1.1 1.1 Definitions (continued)
Watts Bar - Unit 2 1.1-3 Technical Requirements (developmental) A LEAKAGE (continued) 2. LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage
detection systems or not to be pressure boundary
LEAKAGE; or
- 3. Reactor Coolant System (RCS) LEAKAGE through a steam generator (SG) tube to the Secondary
System; b. Unidentified LEAKAGE
All LEAKAGE (except RCP seal water injection or
leakoff) that is not identified LEAKAGE;
LEAKAGE (except SG tube LEAKAGE) through a non-
isolable fault in an RCS component body, pipe wall, or
vessel wall. MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor
coolant temperature, and reactor vessel head closure bolt
tensioning specified in Table 1.1-1 with fuel in the reactor vessel. OPERABLE - OPERABILITYA system, subsystem, train, component, or device shall be
OPERABLE or have OPERABILITY when it is capable of
performing its specified function(s) and when all necessary
attendant instrumentation, controls, normal or emergency
electrical power, cooling and seal water, lubrication, and
other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its
specified safety function(s) are also capable of performing
their related support function(s).
Definitions 1.1 1.1 Definitions (continued)
(continued)
Watts Bar - Unit 2 1.1-4 Technical Requirements (developmental) B Term Definition QUADRANT POWER TILT RATIO (QPTR)
QPTR shall be the ratio of the maximum upper excore
detector calibrated output to the average of the upper excore
detector calibrated outputs, or the ratio of the maximum lower
excore detector calibrated output to the average lower excore
detector calibrated outputs, whichever is greater.
RATED THERMAL POWER (RTP) RTP shall be a total reactor core heat transfer rate to the
reactor coolant of 3411 MWt.
REACTOR TRIP SYSTEM (RTS) RESPONSE TIME The RTS RESPONSE TIME shall be that time interval from
when the monitored parameter exceeds its RTS trip setpoint
at the channel sensor until loss of stationary gripper coil
voltage. The response time may be measured by means of
any series of sequential, overlapping, or total steps so that
the entire response time is measured. In lieu of
measurement, response time may be verified for selected
components provided that the components and the
methodology for verification have been previously reviewed
and approved by the NRC. SHUTDOWN MARGIN (SDM) SDM shall be the in stantaneous amount of reactivity by which the reactor is subcritical or would be subcritical from its
present condition assuming:
- a. All rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity
worth, which is assumed to be fully withdrawn. With any
RCCA not capable of being fully inserted, the reactivity
worth of the RCCA must be accounted for in the
determination of SDM; and
- b. In MODES 1 and 2, the fuel and moderator temperatures are changed to the nominal zero power design level.
Definitions 1.1 1.1 Definitions (continued)
Watts Bar - Unit 2 1.1-5 Technical Requirements (developmental) A Term Definition STAGGERED TEST BASIS A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other
designated components during the interval specified by the
Surveillance Frequency so that all systems, subsystems, channels, or other designated components are tested during
n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other
designated components in the associated function. THERMAL POWER THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.
TRIP ACTUATING DEVICE
OPERATIONAL TEST (TADOT) TADOT shall consist of operating the trip actuating device
and verifying OPERABILITY of required alarm, interlock, display, and trip functions. The TADOT shall include
adjustment, as necessary, of the trip actuating device so that
it actuates at the required setpoint within the required accuracy.
Definitions 1.1 Watts Bar - Unit 2 1.1-6 Technical Requirements (developmental) A Table 1.1-1 (page 1 of 1)
MODES MODE TITLE REACTIVITY CONDITION (k eff) % RATED THERMAL POWER (a) AVERAGE REACTOR COOLANT TEMPERATURE
( F) 1 Power Operation 0.99 > 5 NA 2 Startup 0.99 5 NA 3 Hot Standby < 0.99 NA 350 4 Hot Shutdown (b) < 0.99 NA 350 > Tavg > 200 5 Cold Shutdown (b) < 0.99 NA 200 6 Refueling (c) NA NA NA (a) Excluding decay heat.
(b) All reactor vessel head closure bolts fully tensioned.
(c) One or more reactor vessel head closure bolts less than fully tensioned.
Logical Connectors 1.2 (continued)
Watts Bar - Unit 2 1.2-1 Technical Requirements ( developmental) A 1.0 USE AND APPLICATION 1.2 Logical Connectors PURPOSE The purpose of this section is to explain the meaning of logical connectors.
Logical connectors are used in Technical Requirements (TRs) to
discriminate between, and yet connect, discrete Conditions, Required
Actions, Completion Times, Surveillances, and Frequencies. The only
logical connectors that appear in TRs are AND and OR. The physical arrangement of these connectors constitutes logical conventions with
specific meanings.
BACKGROUND Several levels of logic may be used to state Required Actions. These levels are identified by the placement (or nesting) of the logical
connectors and by the number assigned to each Required Action. The
first level of logic is identified by the first digit of the number assigned to a
Required Action and the placement of the logical connector in the first
level of nesting (i.e., left justified with the number of the Required Action).
The successive levels of logic are identified by additional digits of the
Required Action number and by successive indentations of the logical
connectors.
When logical connectors are used to state a Condition, Completion Time, Surveillance, or Frequency, only the first level of logic is used, and the logical connector is left justified with the statement of the Condition, Completion Time, Surveillance, or Frequency.
Logical Connectors 1.2 1.2 Logical Connectors (Continued)
(continued)
Watts Bar - Unit 2 1.2-2 Technical Requirements ( developmental) AEXAMPLES The following examples illustrate the use of logical connectors. EXAMPLE 1.2-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. TR not met.
A.1 Verify . . .
AND A.2 Restore . . .
In this example the logical connector AND is used to indicate that when in Condition A, both Required Actions A.1 and A.2 must be completed.
Logical Connectors 1.2 1.2 Logical Connectors Watts Bar - Unit 2 1.2-3 Technical Requirements ( developmental) A EXAMPLES (continued)
EXAMPLE 1.2-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. TR not met.
A.1 Trip . . .
OR A.2.1 Verify . . .
AND A.2.2.1 Reduce . . .
OR A.2.2.2 Perform . . .
OR A.3 Align . . .
This example represents a more complicated use of logical connectors.
Required Actions A.1, A.2, and A.3 are alternative choices, only one of
which must be performed as indicated by the use of the logical connector OR and the left justified placement. Any one of these three Actions may be chosen. If A.2 is chosen, then both A.2.1 and A.2.2 must be
performed as indicated by the logical connector AND. Required Action A.2.2 is met by performing A.2.2.1 or A.2.2.2. The indented
position of the logical connector OR indicates that A.2.2.1 and A.2.2.2 are alternative choices, only one of which must be performed.
Completion Times 1.3 (continued)
Watts Bar - Unit 2 1.3-1 Technical Requirements ( developmental) A 1.0 USE AND APPLICATION 1.3 Completion Times PURPOSE The purpose of this section is to establish the Completion Time convention and to provide guidance for its use.
BACKGROUND Technical Requirements (TRs) specify minimum requirements for ensuring safe operation of the unit. The ACTIONS associated with an TR
state Conditions that typically describe the ways in which the
requirements of the TR can fail to be met. Specified with each stated
Condition are Required Action(s) and Completion Time(s).
DESCRIPTION The Completion Time is the amount of time allowed for completing a Required Action. It is referenced to the time of discovery of a situation (e.g., inoperable equipment or variable not within limits) that requires
entering an ACTIONS Condition unless otherwise specified, providing the
unit is in a MODE or specified condition stated in the Applicability of the
TR. Required Actions must be completed prior to the expiration of the
specified Completion Time. An ACTIONS Condition remains in effect and
the Required Actions apply until the Condition no longer exists or the unit
is not within the TR Applicability.
If situations are discovered that require entry into more than one
Condition at a time within a single TR (multiple Conditions), the Required
Actions for each Condition must be performed within the associated Completion Time. When in multiple Conditions, separate Completion Times are tracked for each Condition starting from the time of discovery
of the situation that required entry into the Condition.
Once a Condition has been entered, subsequent trains, subsystems, components, or variables expressed in the Condition, discovered to be
inoperable or not within limits, will not result in separate entry into the Condition, unless specifically stated. The Required Actions of the
Condition continue to apply to each additional failure, with Completion
Times based on initial entry into the Condition.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-2 Technical Requirements ( developmental) A DESCRIPTION (continued)
However, when a subsequent train, subsystem, component, or variable expressed in the Condition is discovered to be inoperable or not within limits, the Completion Time(s) may be extended. To apply this
Completion Time extension, two criteria must first be met. The
subsequent inoperability:
- a. Must exist concurrent with the first inoperability; and
- b. Must remain inoperable or not within limits after the first inoperability is resolved.
The total Completion Time allowed for completing a Required Action to
address the subsequent inoperability shall be limited to the more
restrictive of either:
- a. The stated Completion Time, as measured from the initial entry into the Condition, plus an additional 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; or
- b. The stated Completion Time as measured from discovery of the subsequent inoperability.
The above Completion Time extensions do not apply to those
Specifications that have exceptions that allow completely separate
re-entry into the Condition (for each train, subsystem, component, or
variable expressed in the Condition) and separate tracking of Completion
Times based on this re-entry. These exceptions are stated in individual
Specifications.
The above Completion Time extension does not apply to a Completion
Time with a modified "time zero." This modified "time zero" may be
expressed as a repetitive time (i.e., "once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />," where the
Completion Time is referenced from a previous completion of the
Required Action versus the time of Condition entry) or as a time modified
by the phrase "from discovery . . ." Example 1.3-3 illustrates one use of
this type of Completion Time. The 10 day Completion Time specified for
Conditions A and B in Example 1.3-3 may not be extended.
Completion Times 1.3 1.3 Completion Times (continued)
(continued)
Watts Bar - Unit 2 1.3-3 Technical Requirements (3 developmental) AEXAMPLES The following examples illustrate the use of Completion Times with different types of Conditions and changing Conditions.
EXAMPLE 1.3-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and
associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> Condition B has two Required Actions. Each Required Action has its own separate Completion Time. Each Completion Time is referenced to the
time that Condition B is entered.
The Required Actions of Condition B are to be in MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND in MODE 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. A total of 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> is allowed for reaching MODE 3 and a total of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> (not 42 hours4.861111e-4 days <br />0.0117 hours <br />6.944444e-5 weeks <br />1.5981e-5 months <br />) is allowed for
reaching MODE 5 from the time that Condition B was entered. If MODE 3
is reached within 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />, the time allowed for reaching MODE 5 is the
next 33 hours3.819444e-4 days <br />0.00917 hours <br />5.456349e-5 weeks <br />1.25565e-5 months <br /> because the total time allowed for reaching MODE 5 is
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
If Condition B is entered while in MODE 3, the time allowed for reaching
MODE 5 is the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-4 Technical Requirements (3 developmental) AEXAMPLES (continued) EXAMPLE 1.3-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One pump inoperable.
A.1 Restore pump to OPERABLE status.
7 days B. Required Action and associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> When a pump is declared inoperable, Condition A is entered. If the pump is not restored to OPERABLE status within 7 days, Condition B is entered
and the Completion Time clocks for Required Actions B.1 and B.2 start. If
the inoperable pump is restored to OPERABLE status after Condition B is
entered, Condition A and B are exited, and therefore, the Required
Actions of Condition B may be terminated.
When a second pump is declared inoperable while the first pump is still
inoperable, Condition A is not re-entered for the second pump. TR 3.0.3
is entered, since the ACTIONS do not include a Condition for more than
one inoperable pump. The Completion Time clock for Condition A does
not stop after TR 3.0.3 is entered, but continues to be tracked from the time Condition A was initially entered.
While in TR 3.0.3, if one of the inoperable pumps is restored to
OPERABLE status and the Completion Time for Condition A has not
expired, TR 3.0.3 may be exited and operation continued in accordance
with Condition A.
While in TR 3.0.3, if one of the inoperable pumps is restored to
OPERABLE status and the Completion Time for Condition A has expired, TR 3.0.3 may be exited and operation continued in accordance with
Condition B. The Completion Time for Condition B is tracked from the
time the Condition A Completion Time expired.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-5 Technical Requirements (3 developmental) AEXAMPLES EXAMPLE 1.3-2 (continued)
On restoring one of the pumps to OPERABLE status, the Condition A
Completion Time is not reset, but continues from the time the first pump
was declared inoperable. This Completion Time may be extended if the
pump restored to OPERABLE status was the first inoperable pump. A
24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> extension to the stated 7 days is allowed, provided this does not
result in the second pump being inoperable for > 7 days.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-6 Technical Requirements (3 developmental) AEXAMPLES (continued) EXAMPLE 1.3-3 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One Function X train inoperable.
A.1 Restore Function X train to OPERABLE
status. 7 days AND 10 days from
discovery of failure to
meet the TR B. One Function Y train inoperable.
B.1 Restore Function Y train to OPERABLE
status 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND 10 days from
discovery of failure to
meet the TR C. One Function X train inoperable.
C.1 Restore Function X train to OPERABLE
status. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND OR One Function Y
train inoperable C.2 Restore Function Y train to OPERABLE
status. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-7 Technical Requirements (3 developmental) AEXAMPLES EXAMPLE 1.3-3 (continued)
When one Function X train and one Function Y train are inoperable, Condition A and Condition B are concurrently applicable. The Completion Times for Condition A and Condition B are tracked separately for each
train starting from the time each train was declared inoperable and the
Condition was entered. A separate Completion Time is established for
Condition C and tracked from the time the second train was declared
inoperable (i.e., the time the situation described in Condition C was
discovered).
If Required Action C.2 is completed within the specified Completion Time, Conditions B and C are exited. If the Completion Time for Required
Action A.1 has not expired, operation may continue in accordance with Condition A. The remaining Completion Time in Condition A is measured from the time the affected train was declared inoperable (i.e., initial entry
into Condition A).
The Completion Times of Conditions A and B are modified by a logical
connector with a separate 10 day Completion Time measured from the
time it was discovered the TR was not met. In this example, without the
separate Completion Time, it would be possible to alternate between
Conditions A, B, and C in such a manner that operation could continue
indefinitely without ever restoring systems to meet the TR. The separate
Completion Time modified by the phrase "from discovery of failure to
meet the TR" is designed to prevent indefinite continued operation while
not meeting the TR. This Completion Time allows for an exception to the
normal "time zero" for beginning the Completion Time "clock". In this
instance, the Completion Time "time zero" is specified as commencing at
the time the TR was initially not met, instead of at the time the associated
Condition was entered.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-8 Technical Requirements (3 developmental) AEXAMPLES (continued) EXAMPLE 1.3-4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more valves inoperable.
A.1 Restore valve(s) to OPERABLE status.
4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> B. Required Action and
associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 4.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
A single Completion Time is used for any number of valves inoperable at the same time. The Completion Time associated with Condition A is
based on the initial entry into Condition A and is not tracked on a per
valve basis. Declaring subsequent valves inoperable, while Condition A
is still in effect, does not trigger the tracking of separate Completion
Times.
Once one of the valves has been restored to OPERABLE status, the
Condition A Completion Time is not reset, but continues from the time the
first valve was declared inoperable. The Completion Time may be
extended if the valve restored to OPERABLE status was the first inoperable valve. The Condition A Completion Time may be extended for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> provided this does not result in any subsequent valve being
inoperable for > 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
If the Completion Time of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> (including the extension) expires while
one or more valves are still inoperable, Condition B is entered.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-9 Technical Requirements (3 developmental) AEXAMPLES (continued) EXAMPLE 1.3-5 ACTIONS --------------------------------------------NOTE--------------------------------------------
Separate Condition entry is allowed for each inoperable valve.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more valves inoperable.
A.1 Restore valve to OPERABLE status.
4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> B. Required Action and associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 4.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> The Note above the ACTIONS table is a method of modifying how the Completion Time is tracked. If this method of modifying how the
Completion Time is tracked was applicable only to a specific Condition, the Note would appear in that Condition rather than at the top of the
ACTIONS table.
The Note allows Condition A to be entered separately for each inoperable
valve, and Completion Times tracked on a per valve basis. When a valve
is declared inoperable, Condition A is entered and its Completion Time
starts. If subsequent valves are declared inoperable, Condition A is
entered for each valve and separate Completion Times start and are
tracked for each valve.
If the Completion Time associated with a valve in Condition A expires, Condition B is entered for that valve. If the Completion Times associated
with subsequent valves in Condition A expire, Condition B is entered
separately for each valve and separate Completion Times start and are
tracked for each valve. If a valve that caused entry into Condition B is
restored to OPERABLE status, Condition B is exited for that valve.
Completion Times 1.3 1.3 Completion Times (continued)
Watts Bar - Unit 2 1.3-10 Technical Requirements (3 developmental) AEXAMPLES EXAMPLE 1.3-5 (continued)
Since the Note in this example allows multiple Condition entry and tracking of separate Completion Times, Completion Time extensions do not apply.
EXAMPLE 1.3-6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One channel inoperable.
A.1 Perform SR 3.x.x.x.
Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> OR A.2 Reduce THERMAL POWER to 50% RTP.
8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> B. Required Action and associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Entry into Condition A offers a choice between Required Action A.1 or A.2. Required Action A.1 has a "Once per" Completion Time, which
qualifies for the 25% extension, per TSR 3.0.2, to each performance after
the initial performance. The initial 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval of Required Action A.1
begins when Condition A is entered and the initial performance of
Required Action A.1 must be complete within the first 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval. If
Required Action A.1 is followed, and the Required Action is not met within
the Completion Time (plus the extension allowed by TSR 3.0.2),
Condition B is entered. If Required Action A.2 is followed and the
Completion Time of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> is not met, Condition B is entered.
If after entry into Condition B, Required Action A.1 or A.2 is met, Condition B is exited and operation may then continue in Condition A.
Completion Times 1.3 1.3 Completion Times Watts Bar - Unit 2 1.3-11 Technical Requirements ( developmental) AEXAMPLES (continued) EXAMPLE 1.3-7 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One subsystem inoperable A.1 Verify affected subsystem isolated.
1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />
thereafter AND A.2 Restore subsystem to OPERABLE
status. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> B. Required Action and associated
Completion
Time not met.
B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> Required Action A.1 has two Completion Times. The 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Completion Time begins at the time the Condition is entered and each "Once per
8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter" interval begins upon performance of Required
Action A.1.
If after Condition A is entered, Required Action A.1 is not met within either
the initial 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or any subsequent 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval from the previous
performance (plus the extension allowed by TSR 3.0.2), Condition B is
entered. The Completion Time clock for Condition A does not stop after
Condition B is entered, but continues from the time Condition A was initially entered. If Required Action A.1 is met after Condition B is entered, Condition B is exited and operation may continue in accordance
with Condition A, provided the Completion Time for Required Action A.2
has not expired.
IMMEDIATE
COMPLETION
TIME When "Immediately" is used as a Completion Time, the Required Action
should be pursued without delay and in a controlled manner.
Frequency 1.4 (continued)
Watts Bar - Unit 2 1.4-1 Technical Requirements ( developmental) A 1.0 USE AND APPLICATION 1.4 Frequency
PURPOSE The purpose of this section is to define the proper use and application of Frequency requirements.
DESCRIPTION Each Technical Surveillance Requirement (TSR) has a specified Frequency in which the Surveillance must be met in order to meet the
associated Technical Requirement (TR). An understanding of the correct
application of the specified Frequency is necessary for compliance with
the TSR.
The "specified Frequency" is referred to throughout this section and each
of the Requirements of Section 3.0, Technical Surveillance Requirement (TSR) Applicability. The "specified Frequency" consists of the
requirements of the Frequency column of each TSR as well as certain
Notes in the Surveillance column that modify performance requirements.
Situations where a Surveillance could be required (i.e., its Frequency could expire), but where it is not possible or not desired that it be
performed until sometime after the associated TR is within its
Applicability, represent potential TSR 3.0.4 conflicts. To avoid these
conflicts, the TSR (i.e., the Surveillance or the Frequency) is stated such
that it is only "required" when it can be and should be performed. With an
TSR satisfied, TSR 3.0.4 imposes no restriction.
Frequency 1.4 1.4 Frequency (Continued)
(continued)
Watts Bar - Unit 2 1.4-2 Technical Requirements ( developmental) AEXAMPLES The following examples illustrate the various ways that Frequencies are specified. In these examples, the Applicability of the TR (TR not shown) is MODES 1, 2, and 3.
EXAMPLE 1.4-1 TECHNICAL SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Example 1.4-1 contains the type of TSR most often encountered in the TRs. The Frequency specifies an interval (12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />) during which the
associated Surveillance must be performed at least one time.
Performance of the Surveillance initiates the subsequent interval.
Although the Frequency is stated as 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, an extension of the time
interval to 1.25 times the interval specified in the Frequency is allowed by
TSR 3.0.2 for operational flexibility. The measurement of this interval
continues at all times, even when the TSR is not required to be met per
TSR 3.0.1 (such as when the equipment is inoperable, a variable is
outside specified limits, or the unit is outside the Applicability of the TR).
If the interval specified by TSR 3.0.2 is exceeded while the unit is in a
MODE or other specified condition in the Applicability of the TR, and the
performance of the Surveillance is not otherwise modified (refer to Example 1.4-3), then TSR 3.0.3 becomes applicable.
If the interval as specified by TSR 3.0.2 is exceeded while the unit is not
in a MODE or other specified condition in the Applicability of the TR for
which performance of the TSR is required, the Surveillance must be
performed within the Frequency requirements of TSR 3.0.2 prior to entry
into the MODE or other specified condition. Failure to do so would result
in a violation of TSR 3.0.4.
Frequency 1.4 1.4 Frequency (continued)
Watts Bar - Unit 2 1.4-3 Technical Requirements ( developmental) AEXAMPLES (continued) EXAMPLE 1.4-2 TECHNICAL SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Verify flow is within limits.
Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after 25% RTP AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter
Example 1.4-2 has two Frequencies. The first is a one time performance Frequency, and the second is of the type shown in Example 1.4-1. The
logical connector " AND" indicates that both Frequency requirements must be met. Each time reactor power is increased from a power level
< 25% RTP to 25% RTP, the Surveillance must be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
The use of "once" indicates a single performance will satisfy the specified
Frequency (assuming no other Frequencies are connected by " AND"). This type of Frequency does not qualify for the extension allowed by
TSR 3.0.2. "Thereafter" indicates future performances must be
established per TSR 3.0.2, but only after a specified condition is first met (i.e., the "once" performance in this example). If reactor power decreases
to < 25% RTP, the measurement of both intervals stops. New intervals
start upon reactor power reaching 25% RTP.
Frequency 1.4 1.4 Frequency Watts Bar - Unit 2 1.4-4 Technical Requirements ( developmental) AEXAMPLES (continued) EXAMPLE 1.4-3 TECHNICAL SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY
NOTE----------------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after 25% RTP.
Perform channel adjustment.
7 days The interval continues, whether or not the unit operation is < 25% RTP between performances.
As the Note modifies the required performance of the Surveillance, it is construed to be part of the "specified Frequency." Should the 7 day
interval be exceeded while operation is < 25% RTP, this Note allows 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after power reaches 25% RTP to perform the Surveillance.
The Surveillance is still considered to be performed within the "specified Frequency." Therefore, if the Surveillance were not performed within the
7 day interval (plus the extension allowed by TSR 3.0.2), but operation
was < 25% RTP, it would not constitute a failure of the TSR or failure to
meet the TR. Also, no violation of TSR 3.0.4 occurs when changing
MODES, even with the 7 day Frequency not met, provided operation does not exceed 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> with power 25% RTP.
Once the unit reaches 25% RTP, 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> would be allowed for
completing the Surveillance. If the Surveillance were not performed
within this 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> interval, there would then be a failure to perform a
Surveillance within the specified Frequency and the provisions of
TSR 3.0.3 would apply.