ENS 41543: Difference between revisions

From kanterella
Jump to navigation Jump to search
Created page by program invented by Mark Hawes
 
Created page by program invented by StriderTol
 
Line 16: Line 16:
| event date = 03/29/2005 14:00 EST
| event date = 03/29/2005 14:00 EST
| last update date = 03/29/2005
| last update date = 03/29/2005
| title = 24 - Hr Condition Of License Report Due To T.S. Not Met
| title = 24 - Hr Condition of License Report Due to T.S. Not Met
| event text = The licensee provided the following information:
| event text = The licensee provided the following information:
On March 29, 2005, Seabrook determined that the requirements of T.S. 3.8.1.1 were not met when the Reserve Auxiliary Transformer (RAT), AC supply to the Bus E5, was removed from service on February 14, 2005.  T.S. 3.8..1.1, Action a. requires that the operability of the remaining AC power source be verified within 1 hour, and at least once every 8 hours thereafter.  This action requirement was not completed on February 14, 2005 when the RAT AC power supply to Bus E5 was removed from service.  At the time of this event the unit Auxiliary Transformer AC power supply to Bus E5 and E6, and the RAT AC power supply to bus E6, were in service.  This event is reportable pursuant to Seabrook Station license, Condition 2.G., as a violation of the Technical Specifications.
On March 29, 2005, Seabrook determined that the requirements of T.S. 3.8.1.1 were not met when the Reserve Auxiliary Transformer (RAT), AC supply to the Bus E5, was removed from service on February 14, 2005.  T.S. 3.8..1.1, Action a. requires that the operability of the remaining AC power source be verified within 1 hour, and at least once every 8 hours thereafter.  This action requirement was not completed on February 14, 2005 when the RAT AC power supply to Bus E5 was removed from service.  At the time of this event the unit Auxiliary Transformer AC power supply to Bus E5 and E6, and the RAT AC power supply to bus E6, were in service.  This event is reportable pursuant to Seabrook Station license, Condition 2.G., as a violation of the Technical Specifications.

Latest revision as of 21:21, 1 March 2018

ENS 41543 +/-
Where
Seabrook 
New Hampshire (NRC Region 1)
Reporting
Other Unspec Reqmnt
Time - Person (Reporting Time:+-3.6 h-0.15 days <br />-0.0214 weeks <br />-0.00493 months <br />)
Opened: Damon Ritter
15:24 Mar 29, 2005
NRC Officer: John Knoke
Last Updated: Mar 29, 2005
41543 - NRC Website
Loading map...