Line 17: Line 17:
| event date = 01/02/2015 09:25 EST
| event date = 01/02/2015 09:25 EST
| last update date = 03/11/2015
| last update date = 03/11/2015
| title = High Head Safety Injection Inoperable Due To Voids Identified In Piping
| title = High Head Safety Injection Inoperable Due to Voids Identified in Piping
| event text = At 0925 [EST] on 1/2/2015, Engineering personnel identified a gas void in each of two Unit 4 cold leg High Head Safety Injection (HHSI) discharge lines which exceeded procedural gas accumulation acceptance criteria. This condition rendered the cold leg HHSI flow path inoperable and required entry into Technical Specification 3.0.3. The voids were vented and Technical Specification (TS) 3.0.3 was exited at 1032.
| event text = At 0925 [EST] on 1/2/2015, Engineering personnel identified a gas void in each of two Unit 4 cold leg High Head Safety Injection (HHSI) discharge lines which exceeded procedural gas accumulation acceptance criteria. This condition rendered the cold leg HHSI flow path inoperable and required entry into Technical Specification 3.0.3. The voids were vented and Technical Specification (TS) 3.0.3 was exited at 1032.
The testing for gas voids conducted on 1/2/2015 was a follow-up to a gas void found in one Unit 4 HHSI line on 12/26/2014. On 12/26/14, TS 3.0.3 was entered at 1020 and exited at 1048 after the gas void was vented. After further review, the 12/26/2014 event was also reportable in accordance with 10 CFR 50.72(b)(3)(v)(D).
The testing for gas voids conducted on 1/2/2015 was a follow-up to a gas void found in one Unit 4 HHSI line on 12/26/2014. On 12/26/14, TS 3.0.3 was entered at 1020 and exited at 1048 after the gas void was vented. After further review, the 12/26/2014 event was also reportable in accordance with 10 CFR 50.72(b)(3)(v)(D).

Latest revision as of 21:48, 1 March 2018

ENS 50714 +/- *RETRACTED*
Where
Turkey Point NextEra Energy icon.png
Florida (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
Time - Person (Reporting Time:+2.33 h0.0971 days <br />0.0139 weeks <br />0.00319 months <br />)
Opened: Dirk Drinkard
16:45 Jan 2, 2015
NRC Officer: Vince Klco
Last Updated: Mar 11, 2015
50714 - NRC Website