Title | Failure of the Auto-Start Feature on Two Containment Coolers |
Event Description | This is a non-emergency notification in accordance with 10 CFR 50.72(b)(3)(v)(D) which requires a report when any event or condition at time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident.
On 9/9/14, FPL discovered the automatic feature associated with the swing 4A emergency containment cooling (ECC) unit was inoperable due to a design change inadequacy. During breaker replacement activities performed on 9/3/14, a one hour shutdown action statement pursuant to TS 3.6.2.2.b was exceeded due to two ECC's being unable to automatically start on an SI [Safety Injection] signal. [This was not known until the 4A was declared inoperable on 9/9/14 at 1936 EDT]. The 4A ECC was declared inoperable at 1936 EDT on 9/9/14, and in accordance with TS 3.6.2.2.a, must be returned to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of discovery. The licensee notified the NRC Resident Inspector. |
Where | |
---|---|
Turkey Point Florida (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
LER: | 05000251/LER-2014-003 |
Time - Person (Reporting Time:+10.8 h0.45 days <br />0.0643 weeks <br />0.0148 months <br />) | |
Opened: | Robert Pell 10:24 Sep 10, 2014 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Sep 10, 2014 |
50440 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 50440\u003C/a\u003E - \u003Ca href=\"/Turkey_Point\" title=\"Turkey Point\"\u003ETurkey Point\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EFailure of the Auto-Start Feature on Two Containment Coolers\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 50440 - Turkey Point\n","link":"","lat":25.435330555555556,"lon":-80.33125833333334,"icon":"/w/images/9/9b/NextEra_Energy_icon.png"}],"imageoverlays":null} | |
Unit 4 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |